Document 85dqLVoOBeEeDBGO6DNQQMMJZ

PCBs, PCDFs, and PCDDs Resulting from Transfornwr/fapacitor Fires: An Overview Raul E. desRoslers Environmental Protection Agency Office of Research and Development Washington, OC 20460 Abstract The purpose of this paper Is to give an overview of what the author considers to be current Information concerning PtR transformer/capacitor fires In the U.S. On December 15, 19R3, the Environmental Protection Agency Issued a national dioxin strategy for Investigating, Identifying, and cleaning up sites contaminated by dioxin, within the framework o? this strategy Is a plan that calls for research to he conducted on PCD transformer/capacitor fires. This research will entail an Investigation into the characterization of sources of PCDFs and PCflfls, that is, the chemistry of PCR fires and theoretical products of thermal stress based on composition of askarel used; emergency response protocols for firemen. Including protective clothing; and practical remedial measures for building cleanup. The author also feels that only through the sharing of Information and full cooperation among electrical utilities, chemical manufacturers, firemen. Insurers, EPRI, EPA, and NIOSH can "preventive maintenance" he performed to minimize or preclude future Impacts of PCR transformer/capacitor fires. PREFACE On January 10, 1979, a railroad tank car carrying 75,DOO liters of crude o* chi or o phenol ruptured near Sturgeon,. Missouri, Forty-seven workers from the Norfolk I Western Railway Company were employed to clean up the spill and In the process were exposed to a variety of toxic chemicals. Including chlorinated phenols, phenol, and the toxic artifact, 2,3,7,8-TCOO (1). In fact, the concentration of this dioxin Isomer amounted to only ll ug/kg (ppb) (2), As a result of alleged exposure and the manifestation of certain perceived health effects and physiological symptoms, e.g>, rashes, dizziness, loss of memory, extreme fatigue. Impotence, upper respiratory difficulties, and In one case, cancer of the testicles and the skin, the workers brought suit In an Illinois court against the railroad company and the manufacturers of the tank car and the faulty coupling, Including Monsanto, the manufacturer of the orthochlorophenol. Do August 26, 19R2, the EdwardsvITle, Illinois jury awarded the highest monetary judgments ever made as a result of a 6-1 MOMS 215388 single tankcar spill $57.95 million (1). Prior to the conmencenent of the April 5 trial, Monsanto, General American Transportation, ami Dresser Industries settled out of court for an estimated $8 million. This court decision represents the first time a Jury has concluded that dioxin caused permanent harm to hianans and thus hat highlighted the more than 30 waste disposal sites within the State of Missouri that contain polychlorinated d1benzo-p-dtoxins (PCDDs)(3). Recently, in November and December of 1963, three separate suits (A)(5) were filed In St. Louis Circuit Court: In one ca*&,-hy $7 persons who contend they suffered general systemic effects from dtoxtn-tainted soils at six sites In eastern and central Missouri - for $664 million; In a second case, by 25 dockworkers and a widow of a former dockworker of a trucking firm In St. Louis - for $620 million; and finally, by 163 people at Times beech and Castlewood who assert that they suffered serious health deficiencies as a result of dioxin exposure - for $1.6 billion. Therrfore, this situation has catalyzed an acute public and governmental awareness of the potential severity and explosiveness o* the PCDD problem. PCS transformer fires, accidental spills, and Inapproprlate disposal have compounded the problem particularly In regards to PCDFs (furans) and to some extent PCBPs (btphenylenes). INTRODUCTION The most toxic and extensively studied polychlorinated dlbenzop><t1ox1n (PCDO) and *furan (PCDF) Isomers are 2,3,7,8-tetrachloro-pdloxln (2,3,7,8-TCOO) and 2,3,7,8-tetrachlorodlbenzofuran (2,3,7,8TCDF), respectively. There are pronounced differences In biological and toxicological effects between different PCDO and PCDF Isomers. Those Isomers with the highest acute toxicity are 2,3,7,8-TCDO, c. f ii>vr t (See Figure 1). un-i.i>i'<w ai'ifnirrir iawn4w umx-.i.-cm ourr-.nn* Figure 1, The most toxic PCDO and PCDF isomers (6). HONS 2153B9 6-2 Each of these isomers has its respective four lateral positions substituted for chlorine and each has IDw) values In the range of 1*100 ug/kg for the most sensitive animal species (generally the male guinea pig). There exist 75 PCOO Isomers and 135 PCDF isomers. Acute toxicity among the Isomers can vary up to 100,000 times (See Table 1). In comparison, the most acutely toxic PCD Isomer Is only about one-fourth as toxic as 2,3,7,8-TCDD (8). Table 1. Acute oral toxicity of polychlorinated dlbenzo-pdloxlns as dose expected to cause death of SOT, of the animals within 30 days (7), Acute Oral LDsn. ug/kq tody Weight PCOO 01 2.7 2.8 Guinea Pig >300,000 Rat >1,000,000 Mouse >2,000,000 Trl 2,3,7 Tetra l,3|6,8}Mfxed 1.3,7,9' 2,3.7.8 30,000 0.6 2.1 2 >100,000 22 (M) 45 (F) >3,000 280 Penta 1,2,3,7,8 1.2.4,7,8 < 3 1,100 340 >5,000 Hexa 1,2,3,4,7,8 1.2.3.6.7.8 1.2.3.7.8.9 Mixed Isomers Hepta 1,2,3,6,6,7,8 Octa 1,2,3,4,6,7,8,9 73 70-100 60-100 >600 100,000 825 1,250 >1,460 >1,000,000 >6,000,000 MOMS 215390 Recent Information arising from a 1983 National Cancer Institute carcinogenicity study of a mixture of 1,8,3,6,7,8- and 1.2,3,7,8,9-HCDD 1 fantie rats led to the preliminary conclusion that this mixture of hexachlorodioxlns was carcinogenic. Recause public comment criticized the manner in which the experiments were conducted, the National Institute of Environmental Health Sciences/National Toxicological Program (NICHS/NTP) was asked to reexamine the results of the study. It Is therefore the opinion of NJEHS/NTP that the hexachlorodloxln mixture was Indeed carcinogenic under the conditions of the test (9). _ Analyses of Coernierclal PCB Mixtures PCBs contain a complex mixture of PCOFs with up to 4ft isomers helnq present. Nappe and Buser (6) have analyzed a number of coemerclal PCBs and their findings are shown In Table 2. The highest concentration of PCOFs, found In a Mitsubishi PCB fluid used for over two years, amounted to 10 ug/g (ppm), with 1.25 ug/g being the 2,3,7,8-TCDF Isomer. When coemerclal mixtures or well defined Isomers are heated In air In a sealed glass container or ampoule, yields of PCDFs have been observed In the 1-51 range and this technique has been successfully employed to prepare PCDF standards (ID). Using the synthetic standards currently available, the major PCDF Isomers present In commercial PCBs have been Identified (See Figure 2). UtttMtur uiMVM.or MV..-ar WIVK|li<W ur<<MtKe inrtrMrar uuhhw utuitrvnrw iHtrimur LUU...<? Figure 2. PCDF Isomers Identified In commercial PCBs (6) MOMS 215391 Table 2. Concentrations of PCDFs in commercial PCBs, 09/9 (6). Sample 3-C1 a-Cl 5-C1 ________________________ Aroclor 1248 (I960) Arodor 1254 (1969) Aroclor 1254 (1970) Aroclor 1254 Aroclor 1254 (lot KK 60?) Aroclor 1260 (1969) Aroclor (Lot AK 3} Aroclor 1260 Aroclor 1016 (1972) Clophen A 60 Clophen T 64 Phenoclor DP*6 Prodelec 3010 Mitsubishi (used) n.io * . n,06 - 0.10 * 0.41 2.13 0.5 n.i 0.2 0.25 0.05 O.l 0.? 0.30 <0.001 1.4 0.30 0.7 1.00* 4.00b 1.2 0.2 0.4 0.70 n.in 0.4 0.3 l.D <0.001 5.0 1.73 10.0 0.35 3.30 6-C1 7-C1 O.T 1.4 0.9 " 0.81 0.02 0.5 O.T 1.10 <0.001 2.2 2.45 2.9 0.07 0.53 - 1.35 0.82 Total 2.0 1.7 1.5 1.9 0.2 1.0 0.8 3.8 a 8.* 5.4 13.6 2.0 io.n Major Isomer 2,3,7,8-TCPF > Contains 1.25 ug/g 2,3,7,8-TCOF Discussion of Various PCB Fires * Binghamton, Hew York On February 5, 1981 at approximately 5:3(1 a.m., an electrical panel In the basement of a 22 story office building located In a governmental complex was Involved In an Incident described as an explosion. A nearby electrical transformer containing about 1100 gallons o' Aroclor 1254 (657.) and trl- and tetrachlor Inated benzenes (357) was Involved, leakage occurred and about 180 to 200 gallons of fluid leaked from the transformer, (lue to the ventilation system of the building, smoke contaminated with soot-containing chemicals, was spread In a non-uniform fashion to most work areas of the building as well as to Interstices within air conditioning ducts, false celling areas, elevator shafts, and within desks and file cabinets. This appears to have been facilitated by air ducts or simply open shafts running from the basement area, up to the top o' the building, with openings Into the men's and women's bathrooms on each floor. These bathrooms had only metal gratings separating them from the open shaft area. In addition to this architectural arrangement, fire or smoke safety doors, which were designed to open In the presence of smoke as a health measure, did just that during the series of explosions that occurred at the time of the Incident. Because the outside air temperature was below freezing at the time, the opening of safety doors on the roof, which were located above the building's two stairways, caused a small vacuum that sucked air containing smoke, soot, and as was later found, toxic chemicals from the bathroom areas on each floor and deposited the residue In a non-uniform fashion Into most areas of the office building later tested. HOMS 215392 6-5 PC OF Chemical analyses were performed at: Galson Laboratory In Syracuse, New York and at General Electric Laboratory In Schenectady, New York and revealed PCBs In soot and air, which was strongly suggestive o' PCDFs present In substantial amounts; The National fish and Wlldll'e Laboratory In Colunbla, Missouri, which established the presence of many of the dioxin Isomers; and by the New York State Health Department's Division of Laboratories and Research, which established the presence of 2,3,7,BTCDD. A later examination of material from the underground garage that was contaminated and washed (twice with steam and detergent) was found still to have trace amounts (nanograms per square meter) of PCOFs and PCDOs In some areas hy Wright State University. Total PCDF Isomers In the soot were Initially found to be as high as 21(H) ug/g, PCDOs 10-20 ug/g, and PCBs 100,000-200,000 ug/g (See Table 3). It Is noteworthy that the most toxic isomers are the major components within each group, viz., 2,3,7,8-TCW), 2,3,7,8-TCDF, 1,2,3,7,8-PCW>, 1,2,3,7,8-PCDF, and 2,3,4,7,8-PCOF (See Figure 1). Since the trl- and tetrachlorInated benzenes comprise 35$ of the dielectric fluid, It Is not unreasonable to assume that this diluent mixture represents the precursor to the PCDOs produced as a result of the fire. Nearby Binghamton City Hall, which was used as a staging area during the Initial cleanup efforts In February 19f!l, was also contaminated. The County Building also next door to the Binghamton State Office Building was contaminated to a lesser extent. There have been $12 million allocated so far by the State of New York for the cleanup* The building Is self-insured so no Insurance funds are available* It has been closed since February 5, 19P.1, Over $1 hillIra In lawsuits have been threatened by some of the rare than 500 persons who were, or believe they were* exposed to toxic chemicals, and who are themselves concerned with physical or psycholog leal/medical damages. * Stockholm. Sweden In August 1981, a fire broke out In a 10 KV capacitor battery in an electrical power station In Stockholm, which was probably caused by a malfunctioning electrical system. Wipe tests were taken about one meter from the capacitor (13). Inspection of the chromatograms revealed several peaks* In addition to PCBs, with molecular weights corresponding to dl-* trl-, tetra-* and pentachl or obi phenylenet (PCOPs). It Is probable that these PCBPs were formed by a direct cycllzatlon of PCBs present. The level of PCDFs was found to be 1375 ng/m? (See Table 4), whereas a rough estimate for PCBPs gave levels of 25,000-30,00(1 ng/m?. Polychlorinated pyrenes (PCPYs) were also detected, hut not quantified. MONS 215393 6-6 Table 3. Levels of PCOFs (ug/g) from accidental burning of PCB-contalnlng electrical equipment. Isomer s Capacitor Tr ansformer Skovde, Sweden(lO) 8lnghamton(10) 0.5m* 3m** Total PCOFs Total Trl-CDFs Total Tetra-COFs 2,3,7,8-Tetra-COF Other Isomers 0.8 0.6 0.1 0.5 0.2 0.1 0.02 0.06 2160 28 12 16 Total Penta-COFs l,3,4,7,B-Penta-COF 1.2.4.7,8- " 1.2.4.7.9- " 1,2,3,7,8- M 1,2,3,6,7- " 1,2,6,7.8- " 2,3,4,7,8- " 2,3,4,6,7- " Other Isomers 0.1 0.04 670 65 25 22 31" 60 25 48 12 110 Total Hexa-CDFs 1,2,3,4,6,8-Hexa-CDF 1,3,4,6,7,8- " 1,2,4,6,7,8- * 1,2,3,4,7,8- " 1,2,3,6,7,8- * 1,2,3,6,8,9- 2,3,4,6,7,8- Other Isomers 0.04 0.04 965 50 125 50 510 150 58 10 250 Total Hepta-COFs 0,01 1,2,3,4,6,7,8-Hepta-CDF 1,2,3,4,6,7,9- - 1,2,3,4,6,8,9- - 1,2,3,4,7,8,9- 0.01 460 230 120 55 55 Octa-COF 0.005 0.005 40 Tr ansformer Miami (11)# n.d.-1.79n.d.-0.18 n,d.-0.53 n.d. n*d**l.O n.d.-0.18 n.d. n.d. Tr ansformer Boston (1?)< 165 50 60 3 35 15 2 n.d * soot sample taken 0.5m from capacitor on the floor * soot sample taken 3m above capacitor on the wall f Detection limit: 10 ng/g t Oetectlon limit: 100 ng/g MOMS 215394 6-7 Table 3. Levels of PCDDs (ug/g) from accidental burning o' CR*conta1n Ing electr leal equipment. (cont'd) Isomer s Total PCDDs Total Trl-CDDs Total Tetra-CODs 2,3,7,8-Tetra-COFs Other Isomers Capacitor Skttvde, 5weden(io) 0.5m* 3m** . Tr antformer Binghamton(lO) 20 1.2 n.6 0.6 Total Penta-CODs 1,2,3,7,8-Penta-CDDs Other Isomers 5.0 2.5 2.5 Total Hexa-CDDs 1,2,3,4,6,6-Hexa-CDD 1.2,4,6,8,9 " 1,2,3,4.7,8 1,2,3.6,8,9 1,2.3,7,8,9 " 1,2,3,4,6,7 - 4.7 1.2 1.2 0.7 0.6 0.4 0.5 1,2,3,4,6,7,9-Hepti-C00 1,2,3,4,6.7,8- - 4 3 Octa-CDD "- 2 "r antformer Miami (11)# n.d. n.d. n.d. n.d. n.d. n.d. n.d. n.d. n.d. T? antformer Boston (12)d n.d. n.d. n.d. n.d. n.d. n.d. n.d. n.d. n.d. * soot sample taken 0.5m from capacitor on th floor ** toot smpl taken 3at above capacitor on the wall # Detection limit: ID ng/g t detection limit: IDO ng/g HONS 215*^5 6-8 Table 4. Analytes of wipe samples from various PC8 fires Isomer s Skovde(H) ng/2 Total PCDFs n.d.-873 2,3,7,8-Tetr a-CDF n.d.-100 1,2,7,8-Teti a-CDF 2,3,6,8-Tett a-CDF 1,4,6,9-Tetra-CDF 2,4,6,7-Tetia-COF 3,4,6,7-Teti a-CDF 1,3,6.7-/1.3,6,9-Tetra-CDF Other Tetra-CDfs Total Tetra-CDFs <1-600 2,3,4,7,8-Penta-CDF 1,2,4,7,8-Penta-COF I,2,3,6,7-Penta-CDF 1,3,4,7,8-Penta-COF 2,3,4,6,7-Penta-CDf 1,2,4,6,8-Penta-COF 1,2,4,7,B-P*nta-CDF 1,2,3.6.7-Penta-COF 1,2,4,8,9-Penta-COF 2,3,4.6.8-Penta-COF 1,2,3,7,8-/1,2,3,4,8-Penta-CDF Other Penta-CDFs Total Penta-CDFs n.d.-100 Total Hexa-CDFs n.d.-60 Total Hepta-CDFs n,4.-8 OcU-CDF n.d.-5 Total PCDDs Total Tetra-CDOs 7,3,7,8-Tetr a-CODs n.d. n.d. n.d. St0Ckhglm(14) ng/m? 1375 ISO 150 125 75 37 7.5 300 750 1200 45 38 IS 11 7.5 3.8 3.8 3.8 3.8 2 15 19 175 <0.5 Clne'nnat1(13) ng(r? p.d. n.d. n.d. n.d. n.d. n.d. KQNS 215396 6-9 Sfcovde. Sweden In March 1982, a 400 volt capacity battery, serving a high frequency oven In a casting line of a foundry In Sk&vde, experienced an electrical malfunction leading to a fire (13)(14). The dielectric fluid employed comprised either mineral oil or PCBs. The fire started In a mineral oil capacitor and burned for about two hours before being extinguished. Temperatures exceeding 1100*C were realized because copper.electrical wiring melted. The smoke spread from the basement into the building above, an area of 60 x 30 meters. The capacitor battery contefned 21 capacitors filled with S kgs of PCBs each. Post-fire Inspection showed leakage from 12 of these capacitors. Both wipe tests and moot aanplma were taken. Results are tabulated In Tables 3 and 4. These show that high levels of PCDFs (>100 ng/m2 and <800 ng/g) could only be found In an area near the fire. Concentrations of PCOFs dropped off dramatically with distance from the fire. The highly toxic 2,3,7,8-TCOF was one of the major tetra-CDF Isomers present. Other chlorinated compounds that may be present are the PCPYs, but verification could not bn obtained due to lack of standards. No PCOOs were Identified in samples taken from this fire (there were no chlorinated benzenes used as diluents). No PCBPs were observed. Miami. Florida On April 13, 1982, an underground electrical fire occurred In a transformer vault In Miami. City of Miami firemen were called In to extinguish the blaze. They also voiced their concerns about the possible contamination of fire equipment and protective clothing used during the performance of their duties. As a result, the International Association of Fire Fighters In Washington, OC, contacted the NIOSH Region IV representative and the latter agency conducted a thorough Investigation. Table S contains the results of the analyses of surface samples taken during the Investigation, As expected, samples removed from Inside the vault Indicate the heaviest contamination levels (up to 27,400 ug/100 cm* PCBs). Results of prior NIOSH Investigations Indicate that normal background levels of PCBs on uncontamlnated surfaces should be less than 0.5 ug/100 cm?. As Indicated by the sampling results, turnout coats, boots, helmets, and other personal protective equipment were not found to be contaminated from the fire. This Is probably due to the decision to allow the fire to self-extlngulsh, thus minimizing exposures to the smoke and soot. The only contaminated piece of equipment found at the station was the smoke ejector fan, which contained greater than 31 ug/100 cm2 PC8s because the area wiped for this particular sample was estimated to be less than the standard 100 cm2. The fan blade guard was found to be heavily coated with soot and dirt from the smoke exhausted from the vault fire. Results of PCDO and PCOF analyses are shown In Table 3. No PCOOs were detected, but trl-, tetra-, pent a-, and hexa-CDFs were found, tanging from non-detectable (n.d.) to 1790 ng/g. No 2,3,7,8-TCOF was detected In any of the samples. However, the samples did exhibit high levels of PCBs through Clio and polychlorinated diphenyl ethers (PCDPEs) through Cl3. 6-10 HONS 215397 Table 5. PCft residue from Miami transformer vault fire (II) Sample Location Inside transformer vault Wall behind transformer Top of primary cable above fire Primary cable support bracket Floor near Isolating switch Celling near fire location Secondary bus near vault celling Wall next to exit ladder Rung of exit ladder Above transformer vault: Sidewalk grating Water at curb near vault Firemen's clothlng/equlpnent: Miscellaneous clothing Smoke ejector fan Normal PC8 Background*** Type Sample* PCBs* . Tug/100 em^) (soot) wipe (soot) wipe (soot) wipe (dirt) wipe (soot) wipe (dirt) wipe (dust) smear tab--dr y (dust) smear tab--dry 434** 3m 704 27,400 R6n 195 2 79 smear tab--dry wipe 2 3 smear tab--dry smear tab--dry wipe <0.1 >31 <0.5 * As Aroclor 1260 (used as standard for quantifying samples). ** As mixture of Aroclor 1264 (231 ug) Aroclor 1260 (203 ug). *** As determined by previous NIOSH Health Hazard Evaluation. # Wipe samples were collected on sterile cotton pads soaked In n-hexane 6-11 HONS 211398 * Cincinnati. Ohio On December 3. I960, a capacitor containing PCRs for a 1/2 HP electric motor overheated In a basement storage room of a private elementary school. This capacltnr contained ?? ml of dielectric fluid comprised of 21.9 ml of a biodegradable fluid and 0.1 ml of PCRs. Approximately one-half of the fifth-grade students using three classrooms In the basement area complained of Itchiness of the skin. Power to the electric motor was shut off and the exterior door was opened to allow ventilation of the smoke from the room. Since air Is locally recirculated, central distribution via a mechanical system throughout the school did not occur. PCBs. were not detected In any air sample at a limit of detection of 0.0$ ug/sample, which Is equivalent to an airborne concentration of approximately I ug/m'. Table 6 sumnarlzes the results of 63 wipe samples collected by NIOSH. fifty-one of the 63 samples were taken from surfaces within the school Including books, desks, walls, floors, ceilings, and other surfaces. Two were taken from surfaces within a mobile classroom and ten were obtained from surfaces at three locations In eastern, central, and western Cincinnati to establish background levels of PC8s for this area. The 20 samples obtained from Room 27, which contained the overheated capacitor, ranged from non-detectable to 7200 ug/100 cm? PCBs. The remaining rooms ranged from non-detectable to 0.45 ug/100 cm?. The two wipe samples with the highest PCS concentrations were also analyzed for PCDDs and PCOFs, with particular emphasis on the 2,3,7,8-tetra-lsoaiers. Neither PCDDs nor PCDFs (See Table 4) were detected In either of the samples. The detection limits employed were 0.10 and 0.09 ug/sample, respectively. Boston. Massachusetts In January 1982, there was an electrical fire Involving PCBs In a 80s ton office building. One bulk soot sample was analyzed for PCDDs and PCDFs. Table 3 shows that high concentrations of the trl- through the hepta-COFs were found in the soot sample, ranging from 2-60 ug/g (detection limit 0.1 ug/g). No PCDOs were found. A considerable amount of the highly toxic 2,3,7,8-TCDF was detected--3 ug/g. Levels of PCBs were also found at 10 100 times that of the PCOFs. 6-12 HONS 215399 Table 6. Summary of PCBs wipe sample results, Our Lady of Visitation School, Cincinnati, 01 (capacitor fire) (15). Sample Location Room 27 (capacitor location) Room 25 Room 24 Room 26 Hallway Room 8 Room 22 Room 10 Room II Room 12 A.V. Room Principal1s Office Mobile Classroom Background Levels (3 Cincinnati locations) Mean PCB level. ug/IPP cm? * n.d. - 7200** * n.d. - 0,14 n.d. - 0,06 n.d. n.d, - 0.07 n.d. - 0.08 n.d. 0.29 n.d. 0.20 0.07 - 0.11 0.06 - 0.09 n.d. 0.05 - 0.45 0.06 n.d. - 0.13 * Detection limit: 0.05 ug/sample (sample quantity wiped per 100 cm2). ** Two wipe samples with highest concentrations of PCRs were found to contain no detectable PCDFs or PCDDs. St. Paul. Minnesota On June 22, 1982, a transformer fire occurred In a public fiYgh school in St. Paul. NIOSH took both surface wipe and air samples on June 23 (the day after the fire) and on July 7 (a'ter the area was decontaminated). Table 7 contains measurements of air contamination, pre- and post-cleanup, by PCBs, tr 1 chlorobenzenes, and tetrachlorohenzenes. The NIOSH recommended permlssable limit of 0.001 mg/m* (8-hr TWA) for PCBs was exceeded In all areas sampled except for two locations. The trl- and tetrachlorohenzenes found did not exceed any existing limits. Table B shows the effect of the decontamination methods employed. The transformer .vault room PCBs (wipes) were reduced from a high of 4,000 ug/100 caw to 120 ug/100 cm2 or less. No PCODs or PCDFs were found In the liquid sample of Askarel provided (detection limit 40 ng/o (40 ppb)). However, It Is Interesting to note that NIOSH did not analyze for PCDDs or PCOFs In the soot. The results may have shown significant concentrations of these Isomers, given the areal concentrations of tH> and tetrachlorohenzenes detected. 6-13 HONS 215+00 Table 7. Areal concentration of PC8s and chlorinated benienes, Hill-Hurray High School, St. Paul, MN (transformer ){16), Sample Site ___________ Airborne Concentration, mg/m3________ PCRs*# T3CBS T4CRS Transformer vault, 5 ft above floor Transformer vault, 1 ft above floor Outside of transformer vault doors Woodshop Head of stairs Cafeteria A 0.05 B 0.007C A 22.6 B 0.331 0.09 0.02 0.004 n.d. n.d. n.d. n.d. n.d. n.d. 17.6 - 10.2 0.73 0.12 0.35 0.048 0.020 0.011 0.010 A 18.2 B 0.651 25.7 * II.7 1.21 0.26 0.27 0.229 0.089 0.037 0.032 8-hr time-weighted average exposure criter la 0.001* Aft1* none A - June 23, 1982; B - July 7, 1962 * Detection limit : 0.001 mg/m3 # as Aroclor 1260 a HIOSH recommended permlssable exposure limit. OSHA permlssable exposure limit Is O.noi mg/m3 6-hour time weighted average. b AC6IH threshold limit value. Neither NJOSH nor OSHA has exposure criteria. C sample taken 3 ft above *loor 6-14 HONS 215401 Table 8. Analyzed PCBs< In *1pe samples, HI 11-Mumay High School, St. Paul, MN (transformer) <(16). Sample Site Vault room Ventilation dust Corridor outside vault room Cafeteria Gymnasium Rooms 106, 109, 138 Outside Room 106 Hbodshop PC8s<, ug/ion cm2 A n.d. - 4000 n.ri. 8 2 - 120 - n.d. 0.22 - 0.24 0.29 0.26 - 2.1 5.8 n.d. - n.d. Had* DB 0.8 - # Detection Limit : 5 ug/sample A June 23, 1982; 8 - July 7, 1982 t no analyses conducted for PCOFs or PCDDs. 6-15 MOMS 21S+02 01SCUSS1 ON The previous PCB transformer/capacitor incidents are but a representative sampling of cases where data are readily available. Other electrical equipment episodes Include: Toronto, Ontario, Canada In 1977; and Norrtalje and Suraharmar, Sweden and lmatra, Finland in 1982 (17), More recently, in the U.S., three such episodes have occurred: Oatc 5/15/83 9/28/83 12/21/83 Location San Francisco, CA Chicago, 1L Syracuse, ny PCB Fluid 1242 only 651 Aroclor/35*. Chlorobenzenes 879 1254 Because of the continuance of such Incidents, the Environmental Defense Fund and the Natural Resources Defense Council challenged the August 25, 1982 PCB Electrical Use Rule Issued by EPA. As a result, a Start Action Request has been Initiated by the EPA Office of Pesticides and Toxic Chemicals, which Includes the following court-ordered schedule for the issuance of an Advanced Notice of Proposed Rulemaking (ANPR) regarding PCB transformer fires (IB): ANPR: March 1984 Proposed Rule: October 1984 Final Rule: July 1985 The objective of an ANPR Is to present data that indicate a reason for concern and, more Importantly, to solicit data for the Proposed Rule. The major elements of the ANPR Include: a Description of risks associated with PCS transformer fires through analyses of Binghamton, San Francisco, Chicago, Syracuse, etc. events. a Description of nimber and distribution of PCB transformers, a Solicitation of data on number and location of such electrical equipment. a Presentation of information on other lesser-known fires, a Presentation of estimates of frequency of fires, e Solicitation of data on other fires and frequency of other fires, a Discussion of PCDF/PCDD formation (and PCBP, PCCV (crysenes), PCDPE, PCPY, etc. where data are available on these compounds), a Solicitation of data on mechanisms of formation, a Presentation of possible regulatory options, a Substitutes a Retrofllllng a Fire hazard inspections a Costs/benefits of various mechanisms to reduce spread of PCBs, PCDFs, PCDDs, etc. from fires - use of early warning protection devices 6-16 MONS 21S+03 Currently, the EPA Office of Research and Development (ORD), In support of the Agency's Dioxin Strategy (18), released publicly on December 15, 1983, is planning to conduct research on PCS fires, which Mill cover three areas: (a) the chemistry of PCB fires and a theoretical discussion of products of thermal stress based on composition of askarel used; (b) emergency response protocols for firemen, Including protective clothing (this research Mill be conducted In cooperation Mlth NIOSH); and (c) practical remedial measures for building cleanup. As a result of my participation In the preparation of the Dioxin Strategy document and in several Agency dioxin workgroups. Includingthe Oloxln Disposal Advisory Group and the PCB Transformer Fires workgroup and based upon my expertise concerning the subject matter (?0), 1 believe that I enjoy a perspective that few EPA technical staff have. Because of this, I can relate to you the following facts: Given that chemical production facilities In the U.S. no longer produce ?,A,5-trIchlorophenol (the most significant historical source of 2,3,7,8-TCDD), I can state that soot produced as a result of PCB transformer/capacitor fires contains the highest concentrations of PCDFs and PCDDs (the latter only If chlorobenzene diluents are present In the askarel mixture) found In the U.S. today; on a weight basis, however, municipal combustion devices account for the largest quantity of PCDFs and PCDDs produced currently. The soot from the Binghamton fire was evaluated by the New York State Department of Health In tests using chick embryos In 19B1 (21). Results were positive. In other words, the PCDDs and PCDFs In the soot were not Inactivated (as In the case of fly ash from an Incinerator or by activated carbon) as demonstrated by the chick embryo fetotoxlclty and teratogenicity tests performed. The soot can therefore be considered toxic and may contribute to "environmentally Induced or promoted cancers, reproductive abnormalities. Immunologic deficiency, and possibly premature death from infection, neurologic and gastrointestinal system pathology end possibly, by elevating set tan triglyceride and cholesterol levels, excess or avoidable cardiovascular and cerebrovascular pathology" (22, p. 67B). . I thus stand firmly behind the convictions that firemen responding to such incidents must have the most up-to-date Information at their disposal and that remedial methods employed must be practical, sound, and effective. As a result, EPA-ORD Is In the process of securing PCB samples from Binghamton, NY, Chicago, 1L, San Francisco, CA, and Syracuse, NY. The EPA analytical laboratory in Cincinnati, OH will conduct a chlorobenzene Isomer screen on the samples together with homologue analyses for PCBs, the purpose being an attempt to correlate PCDDs and PCDFs content of soot and wipe samples (In the vaults) with chlorobenzene and PCB content In the transformer fluid. The Information gathered will be shared among the electrical utilities, Insurers, firemen associations, EPR1 and N10SH. In closing, I wish to share some recent and quite pertinent Information. The NIEHS/NTP has concluded two animal studies Involving bloaccumulatlon of 2,3,7,8-TCDD from contaminated soils and has submitted these papers (23) to Science for publication. These papers conclude that 2,3,7,8-TCDD In soil from two sites In Missouri, namely, Times Beach and Mlnker-Stout, Is absorbed in a highly efficient manner (>5M) and that 2,3,7,8-TCDD -17 MOMS 215404 -contaminated soil presents a hazard to humans If Ingested. Thus, further laboratory evidence has been amassed regarding potential risk to humans for 2,3,7,8-TCDD. I believe that this audience Is sufficiently astute to comprehend the long-term Implications of these investigations. Refer ences 1. chemical Week. September 1, 1982, p. 14. 2. Harless, Robert. Deposition In Lowe v. Norfolk ft Western Railway Company, Circuit Court, Third Judicial Court of I'llnols, Kadi son County, No, 79-1-810, 3. Kleopfer, R.D., Bunn, W.M., Vue, K.T., and Harris, D.J. (1982). "Occurrence of TCDP In Environmental Samples fror Southwest Missouri." Paper presented at the 184th ACS National Meeting, Kansas City, MO, September 14, 1982. 4. Anonymous (1983). "57 Missourians File S684 million Dioxin Suit." Post Tribune. Jefferson City, MO, November 29, 1923. 5. Anonymous (1983). "Missouri Oloxln Suit Seeks $1.8 billion." New York Times. New York, NY, December 17, 1983. 6. Rappe, Christoffer and Suser, Hans Rudolf (1981). "Occupational Exposure to Polychlorinated Dioxins and Dlbenzofutans" In Chemical Hazards In the Workp1ace--Measurament and Control. ACS Symposium Series Mo. 149. 7. Leng, M. L. (1979). "Comparative Toxicology of Various Chlorinated Dioxins as Related to Chemical Structure" In CIPAC Proceedings Symposium Series 1. Heffers Printers Ltd., Cambridge, tngland. 8. Safe, S., t al. (1982). "PCBs: Structure-Activity Relationships." Paper presented at the Symposium: "Recent Advances In Exposure, Health, and Environmental Effects Studies of PCBs," Rethesda, HD, Nay 12-13, 1982. 9. Letter of October 31, 1983 from Paul K. H11 deferandt, D.V.M,, Tracer Jltco, Rockville, MD, to E.E. McConnell, NIEHS/NP, Research Triangle Park, NC, subject: Review of NCI Carcinogenicity Study of Hexechlorodlbenzo-p-dloxln In Rats. 10. Rappe, Chrlstoffer and Marklund, St el lan (1982). "Thermal Degradation of Pesticides and Xenoblotlcs: Formation of Polychlorinated uloxlns and Dlbenzofurans." Department of Organic Chemistry, University of Umel, Umel, Sweden. 11. Letter of October 27, 1982 from Stanley A. Salisbury, K10SH Region IV to Richard Duffy, International Association of Fi*e Fighters, subject: PC8 Transformer Vault Fire, Miami, FL. 6-18 MOMS 21S405 12. Memorandum of October 1, 1962 from G. Choudhary and J. C. Posner NIOSH, Cincinnati. OH to Kevin McManus, HIOSH Region I, subject:* PC6 Soot Analysis from Fire at U.S. DOL-OSHA. 13. Rappe. C., Marklund, S., Bergqvlst. P.-A., and Hansson, M. (1982). "Polychlorinated Dioxins. Oibenzofurans and Other Polychlorinated Polynuclear Aromatics Forming During Incineration and PCB Fires/' Department of Organic Chemistry, University of Umei. 5-901R7. Umel, Sweden. 14. Rappe, C., Marklund, S., Bergqvlst, P.-A., and Hansson, W. (1482). "Polychlorinated Dioxins (PCDDs), Oibenzofurans (PCDFs) and other Polynuclear Aromatics (PCPNAs) Formed During PCR Fires." Chemlca Scripts. Vol. 20, pp. 56-61. 15. Health Hazard Evaluation Report: Our Lady of Visitation Elementary School, Cincinnati. Off. NIOSH Report No. HETA 81-237-915, July 1981. 16. Letter of July 26, 1982 from John R. Komlnsky, NIOSH, Cincinnati, OH to Darrell E. Anderson, State of Minnesota Department of Health, Minneapolis, MN, subject: PCB Fire at Hlll-Murray High School, St. Paul, MN. 17. Vuceta, J., Marsh, J.R., Kennedy, S., HI 1 demann, l. and Wiley, S. (1983). "State-of-the-art Review: PCDOs and PCDFs In Utility PCR Fluid." Prepared by SCS Engineers, Inc. for the Electric Power Research Institute, Palo Alto, CA. EPR1 CS-3308, Research Project 1263-11, November 1983. 18. Memorandum of October 11, 1983 from Martin P, Helper, EPA Exposure Evaluation Division to Irwin P. Baumel, EPA Health and Environmental Review Division, subject: PCB Transformer Fires In Buildings. 19. Environmental Protection Agency (1983). "Dioxin Strategy." Office of Water Regulation and Standards and Office of Solid Waste and Emergency Response In conjunction with the Dioxin Strategy Task Force, Washington, D.C., November 28, 1983. 20. desRoslers, Paul E. (1983). "Remedial Measures for Wastes Containing Polychlorinated Dlbenzo-p-dloxlns (PCDDs) and Dlbenzofurans (PCDFs): Destruction, Containment or Process Modification." Ann, occup. Hyp.. Vol. 27, No. 1, pp. 57-72. 21. Seely. Hart (1983). "The Building That won't Come Clean." The Syracuse Herald. July 31, 1983. 22. Schecter, Arnold (1983). "Contamination of an Office Building In Binghamton, New York by PCBs, Dioxins, Fur ans, and Blphenylenes after an Electrical Panel and Electrical Transformer Incident." Chemotohere. Vol. 12, No. 4/5, pp. 669-680. 23. Letter of November 9, 1983 from Edward N. Brandt, Jr.t M.D., Assistant Secretary for Health, to La* Thomas, EPA, AA for Solid Waste and Emergency Response, subject: NIEhS/NTP Studies on Bloavallablllty In Guinea Pigs and Rats of Dioxin In Soli (with two abstracts submitted to Science for publication.) 6-19 MOMS 215406