Document 80xMVYENqk7ZyGgo62wV02gd
Aerofin Corporation
Air System Equipment
Heat Transfer Surface
Aerofin Corporation
Air System Equipment
Heat'Transfei Surface
Pig. S
Universal Aerofin (Fig. 3) is distin guished by its "S" bend construction of tubing, units designed with steel headers on opposite ends, the ends of the "S" bends being connected thereto by com pression nuts, the bends taking care of the expansion and contraction of the tubing.
Recommended where close control is desired.
Headers--Pressed steel. Tubing--1 in. O.D. copper or admi ralty. Casings--Copper, aluminum or galvan ized iron.
Fig. 6
Booster Aerofin (Fig. 5)--straight tube type, single pass construction for pres sures from 1 to 200 lb gauge.
Headers--steel. Tubings--% in. O.D, copper. Casings--copper, aluminum or gal vanized iron. Recommended where small coils are needed or to raise the air temperatures in branch ducts.
Pig. 4
Aerofin Heavy-DutyIndustrial Heating Coil (Fig. 4) for use where extra-rugged coil is needed for close control. Steam pressures from 25 to 450 lb gauge; tem peratures to 550 F.
Headers--Pressed steel. Tubing--1 in. O.D. heavy copper. Casings--12-gauge galvanized iron.
Fig. 6
Narrow Width Aerofin: (Fig. 6) recom-mended for water cooling or for flooded Freon systems. Made in straight tubes only with headers on opposite ends, joint between headers and tubing being brazed. Construction similar to Flexitube Aerofin.
Fig. 7
Aerofin Continuous Tube Water Coils (Fig. 7) are designed for air cooling by circulating cold water through the Aerofin and air over extended fin surface. Made for either horizontal or vertical air flow.
Tubes and fins are copper, completely tinned with permanent metallic bond between fin and tubes. Headers are made of steel and casings of heavy gal- ; vanized iron or copper.
Tested to 250 lb air with coil sub merged in water.
Fig. 9
Aerofin Direct Expansion Units: (Fig. 9) Centrifugal Header Type--For cooling air, using Freon expanded directly into the coil.
Aerofin Sizes
Flexltube: 13 standard lengths, three widths, one and two rows deep.
Narrow: same as Flexitube.
Universal: 17 standard lengths, two widths, one and two rows deep.
Continuous Tube : 13 standard lengths, three widths, 2-3-4-5 and 6 rows deep.
Cleanable Tube: 17 standard lengths, one width, 2 and 4 rows deep.
Direct Expansion: Centrifugal Header --11 standard lengths, three widths, 2-3-4-5-6 rows deep.
Steel Supporting Legs: 18 in. and 24 in.
high. Punched same bolt hole centers as
standard' casings. Quickly, attached.
No other foundation required.
Fig. 8
Aerofin Cleanable Tube Units (Fig. 8) for cooling only made with headers re movable to permit cleaning tubes.
Sale: Aerofin is sold only by manu facturers of nationally advertised Fan System Apparatus. List upon request.
Recommended for use where sediment or Write Syracuse for Heating Bulletin
scale forming, chemicals are present in H-45; Direct Expansion Bulletin DE-48-1
the cooling water.
on refrigeration type units; Continuous
Headers--Fabricated steel.
Tube Bulletin C.T. 39-2 for Water Cool
Tubing--Copper or admiralty.
' ing coils; or pamphlet on Cleanable Type
Casings--Copper or galvanized iron. Aerofin for cooling.
1361