CHAPTER 19
1962 Guide And Data Book
Marine Air Conditioning
237
Rg. 2 .... Mufti-Zone Central (Type C) System
to provide additional heating capacity, as required to main tain the desired room temperature.
Rg. 3 .:.. Terminal Reheat (Type 0) System
system, conditioned air is supplied to each space in accor dance with its maximum design load requirements. The room dry-bulb temperature is controlled by means of reheat in which a room thermostat automatically controls the volume of warm water or steam passing through the reheat coil which is provided for each controlled space. In t-his system a mix ture of outdoor and recirculated air is circulated through the ductwork to the conditioned spaces. A minimum of outdoor air is mixed with return or recirculated air in a central station system where it is filtered, dehumidified and cooled by the chilled water cooling coils, and distributed by the supply fan through conventional ductwork to the spaces treated. Automatic dampers are frequently provided to increase the outdoor air to a mtrimnm of 100 percent as the load falls off. In accordance with usual practice, no recirculated air is per mitted for operating rooms and hospital spaces. When 100 percent outdoor, air only is used, the system is designated as Type Dl. When heating is required, the conditioned' air is heated at the central station to a predetermined temperature. In addition, hot water or steam ts circulated to the reheat coil
Air-Wafer induction System
A second type of system for passenger staterooms and other small spaces is the air-water induction system (see Chapter 2) sometimes designated as the Type E system. In this system, shown in Pig. 4, a central station is provided for conditioning (dehumidifying and cooling) the primary air only. The pri mary air is distributed to induction units located in each of the spaces to be conditioned. Nozsles in the induction units, through which the primary air passes, induces a fixed ratio of room (secondary) air to flow through a water coil and mix with the primary air. The mixture of treated air is then dis charged to the room through the supply grille. The room air is either heated or cooled by the water coil. The flow of water (chilled or hot) to the coil can be controlled either manually or automatically to maintain the desired room conditions. In this system, no return or recirculated air ducts are required, since only a fixed amount of outdoor (primary) air need be conditioned at the central station equipment. This relatively small amount of conditioned air must be cooled to a sufficiciently low dew point to take care of the entire latent load. It is distributed at relatively high velocity and pressure and thus requites relatively little space for air distribution ducts. However, this space saving is offset to some degree by the additional space required for water piping, hot water con
verters, secondary water pumps, induction cpbinets in state rooms and drainpiping from same.
Any beating required with outdoor temperature above changeover point is accomplished by the primary air heated in the central system according to a predetermined tempera ture schedule. Chilled water is distributed to the induction units at this time. Below the changeover point hot water is circulated to the induction units to provide heating, as re quired to maintain the desired room temperature. Cool pri mary air is distributed to the induction units at this time.
Terminal Reheat System with Induction Units
A third type of system, known as the Type F system and used to a limited extent for mH individual spaces, em ploys reheat with induction units (Fig. 5). The primary air,
Fig. 5 .... Terminal Reheat System with Induction Units-(Type F) System
which iB filtered, cooled and dehumidified to a relatively low dew point in the central station system, is distributed through a duct system at moderately high velocities and pressures to the staterooms or individual spaces which are equipped with induction units. The primary air may be all fresh air or a mixture of fresh air and recirculation air. The primary air, in passing through the nossle in the induction unit, induces room air to pass over a hot water reheat coil. A room thermostat automatically controls the flow of hot water to the heating coils to maintain the desired room, temperature. In this system, as in the terminal reheat sys tem, the conditioned air must be cooled sufficiently to main tain the required room conditions under the maximum design load. Therefore, reheat is required when the load is less than the maximum design. With this system, the primary air may be cooled to a relatively low temperature, since it is mixed with warmed room air at the induction unit before the mixture is discharged into the room. Accordingly, the quan tity of air circulated through the ductwork can be sub stantially reduced, resulting in the use of smaller duct axes. When beating is required, the primary air is tempered in the central station system to a predetermined temperature by the preheater. In addition, hot water is circulated to the in duction units to provide additional heating capacity as may be required to maintain the desired room temperature.
High-Velocity Dual-Duct System
During tiie past few years this system also known as the Type G system has gained considerable popularity in the marine field.
In this system all the air is filtered, cooled and dehumidi fied in the central units (see Tig. 6). Blow-through cofl ar
rangements usually are essential to efficient design. A high pressure fan is used to circulate the air through a system of two ducts or pipes at high velocities approaching 6000 fpm. One duct (or pipe) carries cold air while the other handles Wajm air. A steam reheater in central unit heats the air ac cording to requirements of the outdoor air temperature. The supply of warm and cold air is delivered to a mixing box provided in each space served. Each mixing unit has a control valve which proportions hot and cold air from the two pipes
to satisfy the demand of the room thermostat. Any desired temperature within the limits of the capacity of the equip ment can be quickly obtained and maintained with this ar rangement regardless of load variations in adjacent spaces. The air mixing units incorporate self-contained regulators which maintain a constant volume of total air delivery to each space regardless of adjustments in the air supplied to rooms down the line.
Some of the advantages of this arrangement are:
1. All conditioning equipment is centrally located, simplifying maintenance and operation. . 2. Hie system can heat and cool adjacent spaces simultane ously without cycle changeover and a minimum of automatic controls.
3. Since only air is distributed from fans rooms, there is a com plete absence of water and steam piping, electrical equipment or airing to conditioned spaces.
4. With all conditioning equipment centrally located, direct expansion cooling using haiocarbon refrigerants ts possible, elimi nating all intermediary water chilling equipment.
The application of high velocity air distribution which is now possible as a result of advanced techniques in noise at tenuation offers many advantages to the naval architect, shipbuilder and ship owner. The use of unitary central air handling equipment and a flexible system of small diameter prefabricated piping, damps, and fittings facilitates the in stallation for both new construction and conversions. Sub stantial space saving is possible as compared to the conven tional low velocity sheet metal duct system. Maintenance is also reduced.
AIR DISTRIBUTION METHODS
Good air distribution in staterooms and public spaces is particularly difficult because of low ceiling heights and com pact space arrangements. Consideration in design should be given to the following conditions: room dimensions, ceiling height, volume of air handled, air temperature difference be tween supply and room air, location of berths and allowable noise level. On important installations mock-up tests are often used to establish the exacting design criteria required for satisfactory performance.
Supply Outlets
Because of low ceiling heights and small spaces prevalent on ships, the selection of the proper supply outlet requires^care ful attention to prevent objectionable drafts. Before the ad vent of high induction type diffusers, it was the practice to limit the terminal temperature differential to 20 F deg. The difference between the supply air temperature and that of room (dry bulb) is referred to as terminal temperature dif ferential. High induction type diffusers, however, permit terminal temperature differentials of 30 F deg and even