Document 7pVqagKxrpB1bx9QNV0RMev6
750
CHAPTER 70
1962 Guide And Data Boole
Sow is through a solenoid valve which is operated by a low
pressure Boat switch responsive to the liquid level in the evaporator.
The pilot operated low pressure float control (Fig. 24) is
widely used for flooded systems using Refrigerants 12, 22 and
500. Direct acting low pressure float valves are impractical
for these refrigerants except for very small tonnages.
The high pressurefloat valve is so named because the float
chamber is connected to the high pressure tide of the system.
It is actually a float trap, whose function is to
all liquid
refrigerant and no gas. Liquid is fed to the evaporator as fast
as it is condensed. High-tide float valves are usually prac
tical only in systems having one evaporator because of dis
tribution problems if multiple evaporators are used. It is
necessary to charge the system carefully to provide a liquid
level that will flood the evaporator, and yet not cause slopover at full load.
Float chambers should be located as near the liquid con
nection on the cooler as possible since a long length of liquid
line, even though insulated, can pick up room heat and give
an artificial liquid level in the float chamber. Equalizer lines
must be amply sized to minimize the effect of beat transmis
sion toward creating false liquid levels in the chamber. The
float chamber and its equalizing lines must be iT*glt*4
Some sources indicate that a discharge line oil separator
must be used on each flooded cooler system to keep the
oil concentration low in the evaporator. In spite of the hazards
accompanying the use of oil separators, this appears to be
good practice. The use of this device minimizes the amount
of bleed-off that must be taken to keep the oil concentration
down in the cooler and the lower oil concentration insures
maximum cooler efficiency. Oil separators are not 100 percent
efficient. Therefore, it is still necessary to design for oil return
from the cooler whether a seprator is used or not.
Direct Expansion Fluid Chillers
The dry expansion chiller has the refrigerant flow through the tubes while (he water, or liquid to be.cooled, flows trans versely over the outside of the tubes and is guided by ver tical baffles. These coolers may be tingle circuit or multi circuit with each circuit fed by a thermal expansion valve or pilot operated thermal expansion valve. Multi-circuit coolers
are usually used on systems where the compressor capacitv can be reduced below 50 percent since oil cannot be prop^b returned and good thermal valve control may not be expected below this minimum loading per circuit. In addition, at figg loadings the liquid distribution may become poor, resultti* in unequal feeding of the tubes because of separation in cooler heads of flash gas from the liquid. The high gas velocity through the cooler coupled with the thermal valve control enables this type of evaporator to return oil to the com. pressors when due regard is given to the minimum Inading per circuit and the design of tire suction line. A discharge line oil separator is generally not required since the oil return from the low tide will normally be in balance with the oil coming from the high tide. .
It is usually recommended that the minimum capacity on a single circuit should not be less than 50 percent of its full capacity. For example, on a system containing a compressor which can be reduced to 25 percent capacity, a two circuit cooler is often used so that when the compressor reduces in capacity below 50 percent, the refrigerant solenoid vaJve feeding one of the circuits closes.
Liquid-suction inten:hangers (superheaters) are sometimes used with these coolers to prevent slop-over to the compressor with any cycling of the thermal valve, although they are usually not necessary.
Fig. 25 shows typical piping connections for a multi-circuit dry expansion chiller. Each circuit contains its own thermal valve and solenoid valve. One of the solenoid valves shouldbe wired to close at reduced system capacity. The thermal valve bulbs should be located between the cooler arid the liquidsuction interchangers, if used. Locating the bulb downstream from the interch&nger will cause bad cycling of the thermal
Fig..26 .... Typical Piping Arrangement in Liquid duffing Package Using Direct Expansion Chiller*
flrigerant Piping Systems for Refrigerants 12, 22 and 500
751
since the high pressure liquid flow through the inters^ntrer ceases when the thermal valve closes; consequently, bo source of heat is available from the high pressure liquid itil.the cooler must starve Itself to obtain the necessary jnperheat to open the valve. Then when the valve does open,
superheat will cause it to overfeed until the bulb ^oses liquid downstream from the interchanger. Therefore,
remote bulb should always be located between the cooler jj&ftbe interchanger. "fig- 26 shows a typical piping arrangement that has been ^^ successfully in packaged water chillers having direct ex pansion chillers. ^*Any suction risers must be sized to return oil at minimum ppaahte loading in that riser. Care must be given in designing b system to prevent any oil traps in the suction gas passage of bu'L-S interchanger, if used. When the suction gas flows uouod theannularspac^through an interchanger, the suction connection going to the compressor should be made at the bottom to avoid a trap in the interchanger where the oil may Accumulate.
Note in Figs. 25 and 27, that the water or liquid to be cooled Alters the cooler on the suction gas leaving end. This is de sirable to obtain the maximum superheat on the suction gas leaving the chiller.
On larger systems it may become necessary, due to the limited size of thermal valves, to use a pilot operated liquid' valve controlled by a small thermal expansion valve. Fig. 27 shows the proper arrangement. The small thermal valve pilots the main liquid control valve. The equalizing connection and the thermal bulb of the pilot thermal valve should be treated is the same manner as that of a direct acting thermal ex pansion valve. A large liquid line solenoid valve is not re quired to shut off the high side from the low during shut down as a small solenoid valve in the pilot line will serve this
Semi-Flooded Evaporators
A typical example of thLg type of evaporator is the floor mounted, forced circulation, air cooler, with a prime surface (no fins) type coil, used for product refrigeration.
These evaporators are usually primarily designed for flooded operation, and are therefore built with the marin^m amount of circuits for the minimum possible pressure drop. For instance, a type commonly used has large horizontal headers at top and bottom, with individual serpentine pipe coils 6 to 10 rows high in direction of air flow connecting the two headers.
If refrigerant is fed to the top header of these coils with
Fig. 27 .... Dry Expansion Cooler wiJh Pilot Operated Control Valve*
thermal expansion valves, very poor liquid distribution would result in the large header. This would seriously reduce the unit capacity. Therefore, best results are obtained by bottom-feeding the coil. This will result in a semi-flooded condition which tends to more evenly feed all circuits (Fig.
28). Because of the large volume and number of circuits in prime
surface coils designed for flooded operation, the suction gas velocity up through the coil is not sufficient to entrain oil when bottom-feeding the coil from an expansion valve. Thus the coil can form a trap for any lubricating oil which is in circulation through the system. If this is allowed to happen the concentration of oil in the refrigerant-oil mixture,which constitutes the coil operating charge, can become so great as to impair tire heat transfer performance of the coil and cause lubrication failure of the compressor.
To keep the oil concentration in the coil at a mimmnm, it is actually necessary to overflow this liquid refrigerant-oil mix ture from the top of the coil in sufficient quantity to contin uously return to tbe suction line the same amount of oil that enters the coiL Once this oil-rich liquid refrigerant enters the suction line, proper design of this line will carry the oil back
to the compressor. The oil-rich liquid refrigerant slopped over from the top of the prime surface coil must be rectified by means of a liquidsuction heat interchanger which will evaporate the refrigerant and permit the oil only to be returned in liquid form, by en trainment or gravity, to the compressor.
To realize this slop-over of oil-rich refrigerant from the top of the coil, tbe valve should operate at a low superheat setting and the thermal bulb should be located at a point where the necessary superheat can be obtained to operate the valve while the required slop-over is taking place.
Direct Expansion Air Coils
Direct expansion air coils arc usually composed of a finnedtube bundle into which refrigerant is fed by means of an ex pansion valve, usually the thermostatic type, and over which air is passed by forced convection means. This type of evap-