Document 7RD5BgGQ6oMvk6GxOpr69jzLV
AW
LAPORTE
\AA/
For More Information Call: Jim Ponciroli. Plant Manager
ta> Phone No. 314-544-1400
Company Information:
Laporte Pigments, Inc. (formerly Mapico, Inc.) owns and operates a manufacturing facility in St. Louis, Missouri that produces iron oxide pigments of various types and colors from inorganic raw materials. Iron oxide pigments are the largest volume color pigments used. They are commonly found in paints, and colored concrete products as well as colored plastics, paper, inks and cosmetics. More specialized properties are required for applications such as toners for copiers, printers, photographic chemicals and catalysts. The facility, which is located at 303 East Hoffmeister Avenue in south St. Louis County, has been producing pigments at this location for more than 34 years. There are 100 full time employees, many of whom are also residents ofthe surrounding south St. Louis community.
Risk Management Planning (RMP)
The Environmental Protection Agency (EPA) created a regulation called Risk Management Program (RMP) as an amendment to the Clean Air Act. The RMP rule requires facilities with certain quantities of chemicals and other regulated substances that are on a specific EPA list to disclose information on accidental releases of the listed materials. Specifically, facilities are to provide the following information: a five-year history of accidental releases for their listed materials, "worst case" and "alternative case" scenarios related to potential releases of the listed materials, their plans to prevent and minimize the effect of incidents, and their emergency response programs for dealing with an accidental release should one occur.
Anhydrous ammonia and aqueous ammonia are two of the chemicals listed in the EPA's RMP rule. Laporte Pigments uses these two chemicals in amounts that exceed the EPA-designated threshold quantities and is, therefore, subject to requirements ofthe RMP rule.
According to the RMP rule, the accidental release history must include all accidental releases from covered processes that resulted in death, injuries, significant property damage, evacuations, shelter-in-place or environmental damage. The following is the five-year accident history for covered RMP-listed materials at this site:
Year:
1994 1995 1996 - 1997 1998
Number of RMP Accidental Releases:
00000
Management's policy for safety in the work place is to integrate safety into all ofthe facility's day-to-day operations and to continuously seek and implement safety improvements. Our success in this regard can be best demonstrated by our historical record of injury and illnesses cases that are reported annually to the Occupational Safety and Health Administration (OSHA). The average for the past five years has been approximately 3.5 cases per 100 full time employees (FTEs), including only 1.7 cases per 100 FTEs in 1998. For the most recent OSHA year of record (1997), these values compare to 6.5 cases per 100 FTEs for the pigment industry and for the overall chemical industry of 4.8 cases per 100 FTEs. Laporte Pigments has one of the best safety records in our industry and is proud of it.
Since anhydrous and aqueous ammonia are both toxic materials, the RMP requires Laporte Pigments to develop a worst-case scenario for one of these two chemicals and a separate alternative-case scenario for each of the two chemicals. The table on the back side of this sheet provides information on these worst-case and altemative-case scenarios. The table also provides information about each chemical and the measures that Laporte Pigments has in place to prevent accidental releases and, should one occur, to effectively respond by implementing planned emergency procedures designed to reduce the effect of the accidental release.
DSW 138131 STLCOPCB4038088
Hxample RMP accidental release scenarios for (lie Laporte Pigments, Inc. St. Louis facility.
I'hc RM11 rule defines ihe worst ease release as the hypothetical and entire release of the largest quantity container of the RMl'-lislcd material within 10 minutes. It assumes weather conditions that would maximize its
impact, complete failure of all safely controls and systems, and no emergency response. Deeause the worst-ease accidental release scenarios are extremely unlikely, the RMP rule also provides for development of an
alternative release scenario Alternative release scenarios depict a more credible release of an RMl'-listed material and consider safety systems that are in place.
i
i
Chemical
About the Chemical
Accident Prevention Measures
Example Event
Scenario
RMP
Emergency Response Measures
Designated Laporte Pigments has in place
In-Place
Distance of Concern'0
Anhydrous > Ammonia is a colorless > Anhydrous ammnonia is
Worsl-Casc > Instantaneous failure of
3. 6 miles r Remotely controlled
Ammonia
gas lltal is a strong alkali
stored in industry-standard Release
storage vessel wall.
emergency shut-off valves
and has an extremely
slecl storage tanks equipped Example'"1 > Total release of the entire
> Trained emergency
pungent odor. It is
w ith automatic ov erfill
contents (124,000 pounds) in
responders.
flammable at
protection with alarms.
10 minutes.
r In-plant emergency
concentrations of 16 lo
> Tanks arc filled lo no more
> Worst possible weather
notification system.
25% in air. It is stored as
than 80% of capacity.
conditions.
> Procedures for
a liquid by compression. > Personnel are trained to
> No mitigating measures in
communication with off-site
> Laporte Pigments uses
safely handle anhydrous'
effect.
responders and residents.
nulls droits ammonia for
ammonia.
r Response drills.
pH control in its
processes.
Anltv droits r Description is the same
> Measures arc the same as
Alternative > Failure of gasket on a system 0.1 miles > All emergency measures
Ammonia
as given above for worst-
slated above for worst-case Case
component.
same as listed above for worst
case scenario
scenario
Release
> Release of 212 pounds in 10
case scenario
,
Example
minutes.
> Assumes no mitigating
measures arc in effect.
Aqueous > Aqueous ammonia is a
r Aqueous ammonia is stored Alternative > Failure of pump packing.
0.1 miles r Containment dike with a
Ammonia
clear, colorless solution
in an industry-standard
Case
> Release of 295 pounds of
capacity that is 30% greater
of water and no more
steel tank equipped w ilh
Release
aqueous ammonia in 10
than that of the aqueous
than 44% ammonia that
automatic overfill
Example
minutes.
ammonia storage lank.
has a s cry pungent odor.
protection with alarms.
> Assumes no mitigating
> All other emergency measures
> Laporte Pigments mixes > Tank is filled to no more
measures arc in effect.
same as listed above for
part of its anhydrous
than 75% of capacity.
anhydrous ammonia
ammonia with water to
> Personnel arc trained lo
make a 28% solution of
safely handle aqueous
aqueous ammonia for use
ammonia.
as a process reactant.
(1) The distance a toxic v apor cloud, lire, or explosion from an accidental release is predicted to travel before dissipating to the point that serious injuries from slmrl-lerm exposures will no longer occur. Data
developed bv HI'A or HPA-approved computer models were used to simulate conditions and predict the reported distances.
(2) I or RMP. a toxic chemical is one defined by MPA as acutely toxic, meaning it can cause serious health effects or death from short-term exposure.
USW 1 3 8 1 3 2
I he sharing of this information Is intended to improve community understanding of local industries and promote an informed dialogue on their chemical accident prevention practices. Ibis not a prediction of the probability that any scenarios discussed w ill es er occur. The information is based upon the Risk Management Plan being prepared by the Laporte Pigments, Inc. St. Louis facility. Descriptions in the final Risk Management Plan submitted in June, 1999 may differ from these descriptions due to reslsions.____________________________________________________________________ '______________________