Document 7R1axGnaRdYe0Gn2rER0NvD2V

INC. 1 substitutes tor ras STATUS AiJD PROSPECTS introdictiou . Current consumption of PCBs by U.S. industry (1974) is as follows: Electrical Capacitors PCB lb/year 22.0 million lb Units/year h&- 100 million capacitors L; 7.. Electrical Transformers 11.2' million lb 5000 transformers ry . "" ' Investment Casting Wax .4 million lb 1.2 million lb wax t-~~n , CJWCrTORS PCBs are used in capacitors because of their unique electrical properties and qoed resistance to fire. Electrical capacitors containing PCBs are included in nearly every fluorescent light, television set, and air conditioner that is built in the United States. Larger capacitors are used in industry to assure the efficient distribution and use of electrical energy. A nunber of substitutes for PCBs have been developed and are being tested. The important properties of each of these materials ire summarized in the follow ing Tabic. Sufficient data should be available within one to three years to determine whether the use of any of these alternative fluids will be warranted bast-d on an analysis of ccnbined health and fire risks. r*--\ ,, The PC3s currently lacing used in capacitors were reformulated in 1971 to 'M` ' have suiular use properties with minirrum achievable (ecological persistence. Tne") {[, //< averse enviromental effects of PCBs are well docunentcd, and the crviroam?nud ) Icxid anticipated frcr.i continued production of PCB capacitors will be small ccm- pared to the load arising from past uses of PCBs. Hie present substitutes for l'Ci'j.i in capacitors have largely not been tested for long term health effects. KTi-t potential substitutes v^ould apparently increase the. risk of fire in consuli\n j industrial electrical equipment, llcwever, several of the substitutes are in h camjrcial use in foreign-made capacitors nod in U.S. produced eguipnvpnt for foreign wirkets. HONS 045543 relative Merits of Substitutes for PCB in Capacitors B. >w Jwj s .'f . 4f1J1l CO i F ire Resistance Short Term TOxicity fc & HHH 3 ^3 >J2U-Js '1CiV^i4J H f |1 C6V>Oi 3l V - MHSH' ' --*HQ4 ' . Mineral Oil Phthaiets eziersfft-oJ I-'cnrcnyl dichloro bic:*.2T.vl Saic=..es ,,Ki<r<e t Suc/lated ncnochloro diphenyl oxide -pctJ Synthetic hydrocarbon oils Solid plastic film 2X 1.1X 1.1X Poor Poor-fair Fair-good 1.2X 1.1X Fair Fair-good 1.1X Poor 3X Good Poor Good Good Good Good Good No Good Fair Fair Good Questionable Questionable OX Used rev in Japan Cn test in France Excel. Fair Good Excellent Questionable i Questionable TO be introduced in 1976 On test in U.S. Lab tests at present Excel. Excellent 3 to 5 years *Cnrps.tibility is the ability to use replacement capacitors in existing systems - as a function of physical/ di.7ansia-.al constraints. HONS 045544 i :/iV4i;npi n Ikc- 3 TR/yNShWiSRS Electrical transformers are used in the distribution of electricity to minimiib the losses of power between the generator and the user. Those trans formers are filled with an oil to absorb the heat which is generated inside the rfo^- tronsformer. The transformers are normally enclosed; however, in the event of a short circuit or other failure, the oil can spill. Approximately 90 per oent of all transformers are located away fran buildings and do not present a fire hazard; any fire would be limited to the transformer itself. These transformers are of filled with mineral oil whi< is completely satisfactory except for its flarnna- ^ ^ The remaining 1C per cent of all transformers are located within buildings where fires would be very hazardous. These transformers are filled with a non flammable liquid containing 60 per cent to 70 per? cent PCBs. If these trans formers had been located outside the building or provided with a fireproof vault, the initial installation cost would have been $5,000 to $50,000 higher for each transformer. Recently, silicone oils have been proposed as substitutes for PCBs in trans formers in hazardous locations. These silicone oils are flanmable, but much less so than mineral oil. The decision as to the replacement of PCB with silicones must be based on a decision as to whether the increased risk of fire offsets the reduction in toxicity achieved with the silicones. Silicone oils are currently being used in Japan ir. railusad locomotive transformers. . b- - There are no tedinologital barriers to the complete elimination of PCBs in transformer applications. However, the alternatives all incur eoonomic penalties: Alternative Action Locate transformer in safe location new installation Locate transformer in fire proof vault Use air ooolcd transformer . Use siliocne oil. - new installation Convert fran PCD to silicone oil Cost $5,000 to $50,000 $5,000 to $50,000 . 1.5 times ns expensive; noisy; not as reliable 1.2 times as expensive;' wiknown increased fire risk $450 to $15,000 MONS 045545 yer/a It Ixc 4 bwestkct.t casting " rr^-' j b Jr H.I r.( Decachlordbiphenyl ("doka") is used as a pattern wax filler in investment . I casting. About 400,003 lb is imported annually by one wax manufacturer; and I about 1,200,000 lb/vear of was containing deka wax is produced (unit price about J $0.70/lb; yearly sales approximately 0.8 to 1.0 million dollars). Details of t/rc" production process are not known. The manufacturer of the deka wax also produces other pattern waxes which presumably contain chlorinated terphenyls (fCTS) as fillers. Substitutes for the deka PCBs can be either a replacement filler material or an unfilled wax. Properties required for a filler are: melting point over 300'C, high heat transfer coefficient, lew thermal coefficient of linear expansion, and minimis ("zero") ash. Isopthalic acid is a premising filler candidate and has been used to a limited extent, but the grade used-did leave an ash residue. A new grade, cnly recently comaercialized, exhibits much lower ash and metal con tents. Its costs is $0.35/lb, which is comparable to or lover than PCB. Prior to the use of PCBs or PCTs as fillers, unfilled waxes were used. Industry claims that reverting to the use of unfilled waxes would increase pro duction oosts by about 10 per cent. However, new types of unfilled waxes have recently entered the market, and it is claimed that their properties are equiva lent to the filled wax and their cost is slightly lower ($0.60 to $0.65/lb). Al though the exact formulation of these waxes is not knavn, t)iey reportedly contain no chlorinated additives. In simmary, technically adequate substitutes appear to be available for decechlorebiphenyl filler in pattern waxes. Maximum increases in costs would be about 10 per cent. The cnly producer of wax containing PCBs could probably change to other types with very little technical difficulty or ccononic impact. HONS 045546 ' u. toxtcitv of retnirriAi. siusttivits Very little information appears to be available concerning effects of long-term exposure to most of the potential substitutes mentioned. Mineral oil and silicone oil would appear to be the least likely to cause toxic effects, but mineral oil^somatimes contains aromatic compounds and little is Inown about the degradation products of silicor.es. Phthalic acid and phthalatcs have apparently not been studied in depth. In addition, little is known about the long-term toxicity of decachlorcbipheny1. HONS 5.0 SUBSTITUTES TOR PCBs IN THE ELECTRICAL EQUIPMENT INDUSTRY V ' Polychlorinated biphenyls (PCBs) were first manufactured ccmer- cially in 1929. In the United States, PCBs have been manufactured by a single producer, the Monsanto Industrial Qiemicals Company in recent years. In 1970, Monsanto announoed a program that, since 1972, has led to ./`t total restriction on sales of PCBs for all uses except the manufacture of sealed electrical equipment, specifically capacitors and transformers. 7s a result, there are currently about 25-30 direct customers who are using PCBs to manufacture "Closed Electrical Systems" or are in tue course of servicing these systems. Newly obtained information from industry sources indicates that near term replacement of PCBs in most closed electrical service is not techni cally feasible since there appear to be no substitutes which could provide the safety, reliability and economics of PCBs. The development of satisfactory substitutes for PCBs in these applications mist be based on a thorough under standing of the requirements of the electrical services and of the properties of PCBs which make them uniquely desirable. 5.1 Capacitor Dielectric Fluids ' In order to set the proper framework in which to describe the re quired properties of the materials that are used in the construction of capaci tors, and therefore the nature of the substitutes that might be used in place of PCDo, it is appropriate to briefly discuss the nature of capacitors, the rensens they are used, and the resulting electrical characteristics of such a device. 5,1.1 Industrial Uses of Capacitors Oil filled capacitors are used in electrical equipnant to compensate for inductive loads imposed by other circuit components (power factor correction) and to provide a shift in Die phase relationships between voltage and current in motor starting circuits. MQNS 045548 2. 5,1.1.1 Pcwer Factor Correction. Hie largest use of oil filled (PCB) capacitors is to increase tlie efficiency of electrical pcwer distribution by correcting for the power factor of inductive machinery such as industrial motors and fluorescent light transformers (ballasts). In general, the load imposed on a power line by these electrical devices is not purely resistive, but is also partly inductive. Hie voltage drop across such an inductor is proportional to the rate of change of current through the device; hence where the negative sign expresses the reaction of the inductance to a change in current through the inductance. If the current is expressed in the form l = i e^wt o . where j i^T , e^ut * (cos ut - j ut), u 2if, f = frequency. Hien V = juiL i = Zi where Z is the inductive reactance given by tL = juL . (i) On the other hand, for a capacitance C, the potential difference Henae, the enpneitiv: reactance Zc is given by (2) In the eveht that a scries circuit, containing inductive (L), capacitance (c), and resistive (R) elements, lias a potential difference v = voe-)"t i HONS 045549 3. across it, the relation between current and applied potential difference is given by Laif + Ki + |/ idt Voeju)t . ' (3) A solution of this equation is in the form i . 1 ej (tut + o) o where a expresses tiie possibility of there being a phase difference between the applied potential difference and the resulting series circuit current. On substitution of the assumed solution into the.differential equation (3), one finds . (juL + E + ) i - v which is in the general (Ohrr.'s Law) form where where and r = R + jl&L ~ ~ ) = |z| Jr* + ( l - -- )* 3 OC ' Un-> (S^) and, in order to satisfy I3q. (3 *), 0 - - O') (4) (4') (4") MOMS 045550 Several cosis may be considered: X i. (A) (iiL - --tuc 5 o circuit is purely resistive then, frem (41) and M) 2 - R , 4> o . (B) wl so, . < " tan"1 ( "55= > = < 55c ' 2 = \/r' + -MraC (C) UC S O , . 2 - yn* + .w'l* (f_ tan"1 ) . The power dissipated in a series P , L, C circuit is given by */ VI dt (there T is the period s j which, on integration, yields P IoVq oos (5) v , where if is the phase angle given by 4' . MONS 045551 ](:r/ar lye She ijrporUnce oi.' the phase angle is best described by noting that electrical pewer is generated in such a manner that the voltage and current arc in phfee, i.e. uo3 ^generation = ' Hence Power generated - power consumed Pcwer losses in VoIc. - VoIo cos 8 *> VoIo (1 - cos 8) = pcwer loss due . to unfavorable phase angle Since the voltage is fixed and oos 8 < 1, the transmission line current must be increased in order to supply the load when there is a lagging phase angle. However, the resistive losses in the transmission lines are pro portional to the square of the current transmitted, theretore, efficient trans mission of electrical energy requires that the- net phase angle, or power factor, of the load be as clcse to unity as possible. This power factor correction is achieved by the introduction of a capacitor in series with the inductive load at the load end of the line. Hie use of capacitors for pcwer factor correction is a major use of PCB filled units. Since these capacitors are normally built into electrical equipment such as fluorescent light ballasts and industrial motors, they must be non-flamrable anc' able to operate at relatively high temperatures. 5.1.1.2 Motor Starting Circuits. Electric motors for residential use are designed to operate on single phase current. A number of different methods are used to develop the rotating magnetic field that is required to start the motor, anci these methods differ in the amount of torque that is developed at low speeds. Certain applications, particularly oorpressors in air conditioning units, require a very high starting torque. This is achieved in a single phase motor through the use of a capacitive starting circuit. In a capacitor motor stator windings are connected, at start, as shewn below: ,v HONS 045552 Inc. I Uiere the starting f.eld is connected to the supply through a capacitor, the result is a starting winding current which leads the applied voltage. Hence, at standstill, the rotor sees fields nearly 90 apart in time as well as 90' apart in space. The resulting, effectively rotating, field results in high starting torque and a high power factor (important during the period when the back snf due to rotor notion is low so that the starting current is significantly higher than the running current). Onoe the rotor is up to speed, the starting winding is disconnected by the oentrifugal switch. In some applications, two capacitors are used in startup, one being removed when rotor is up to speed. The remaining capacitor helps adjust the power faster during run. . 5.1.2 Constructioa.of Industrial Capacitors 5.1.2.1 Function of the Dielectric Material Wien a material mediae is placed within an electric field there is a tendency for the charges associated with the constituent molecules to move in the direction of the field (the positive charges move in the direction of the applied field, the negative charges in tire opposite direction). In the event that the material ista conductor, the mobile chargee, usually electrons, will move freely under the influence of the field and a current is said to flow in the conductor. On the other hand, if the material is a non-conductor, the effect of tlie applied electric iicld is to cause a spa^i.tl displacement of the charge centers of the constituent molecules with the result that tlierc will be induced surface charges on the material, liic charge on opposite faces will be opposite in sign and will be so arranged as to generate an electric field within the material opposing the applied field. Such a MQNS 045553 ixc. material is known os o dielectric and is characterized by a parameter defined as the ratio ofj the electric field that would exist in that space if the medium were replaced by vacuum to that actually found within the dielectric - this parameter is referred to as the dielectric constant. In general, at least at low frequencies, the dielectric constant of mast materials is greater than unity. Since the effect of an applied electric field on a dielectric medium is the generation of a surface charge, it is clear that work must be done in the separation of these charges. Clearly, the larger the applied electric field, the larger the surface charge, and conversely, when the electric field is removed, the surface charge is zero. The energy that is required to establish the necessary surface charge is then said to be stored within the dielectric and can, in most cases be recovered without loss by removing the external electric field. ' . In practice, the external electric field is established by applying electrical chirges co a pair of metal plates placed on the opposite surfaces of the dielectric to ferm a device called a capacitor. The capacitance of the re sulting structure is defined as the ratio of the charge on either of the conducting plates to the electric potential existing betwen the plates. Alternatively, the capacitance may be defined in terms of the energy stored within the dielectric as <iere C is the capacitance, W is the stored energy and V is the applied voltage. Although the geometry of the conductor-dielectric sandwich can take a wide variety of forms, the specific geometry that is of most interest is that in which the conductors are parallel plates separated by the dielectric. In this case the capacitance of the device is given as CS eA "a (2) l where e is tile dielectric constant, A the area of each plate and d the spacing (the thickness of the dielectric). . As is 3tatcd above, the magnitude of the surface charges that are formed on the dielectric inci-onsou as the applied electric field increases. Eventual) MONS 045554 l4;/iA' 'fxc. 0. the external electric f:icld -Toy become sufficiently strong as to rupture the bonds that holdyfocjctJjcr the charges on the individual constituent molecules with the result that the dielectric breaks down; i.e., conducts current. The critical field strength, or rather the critical voltage, where Vc Ecd(3> is defined as the maximum potential gradient (voltage) that the dielectric can sustain without rupture. C)early, the dielectric constant and the critical voltage, or dielectric strength, are essentially unrelated. When several capacitors, say and are connected in parallel, then the voltage across each is the same, V, while the charge on the capacitors is Q. C,V and Q, = C,V, hence the capacitance of the parallel carbination is given as Cj + C^. On the other hand, if the two capacitors were connected in series, then the charge, Q, would be the same for each. In this case, the respective potentials would be given as Q/C^ and = Q/Cj, with the result that the total capacitance is given as VCt " i/cx + i/c2(5) Frcm the above considerations it can be seen that the effect of even a snail hole through the dielectric will be to produce a very small reduction in the overall capacitance, since the resulting structure may be considered as two capacitors, one with the nor.nSl dielectric, the other with air dielectric, in parallel, On the other hand, the'breakdown strength of air is considerably less than that of most practical dielectric materials, so that the effect of such a discontinuity in the dielectric will primarily be in reducing the critical voltage of the resulting structure. . On 'Jjr other hand, the effect of a gap between the dielectric and the plates is more serious in that the resulting structure will act as if it were made up of several capacitors in series. From Eq. 5 above, it con be seen that the snallest capacitor in a series circuit will determine the total capacitance of the structure. Thus, a gap between the plates and the dielectric will have the effect of reducing the capacitar.pe without a reduction in the dielectric strength. In most, practical devices, the assimption that the 60lc effect of the dielectric is tire reduction of the internal electric field by the induction of surface charges is not entirely correct. In all ouch practical cases, there is a MQNS 045555 leakage current that Hews through the dielectric. The effect of this leakage current is the production of Joule heat within the dielectric. Useful dielectrics are such that this lc.ikage is very small but the heating effect is not a]ways negligible as will be discussed below. 5.3.2.2 Practical Capacitors As pointed out above, in its simpliest form, a capacitor is a pair of metal plates separated by a suitable dielectric. Depending on the application, a great variety of structures have been used ranging frem parallel plate-mica or glass dielectrics for very snail capacitors, through tantaltkit-tantalum oxide-tantalum structures which have very l arge capacitances with very low operating voltage ratings. The capacitors that are of interest in this study have capacitance values in the range of a few tenths to tens of microfarads and are usually spiral wound of two thin alumimm foils and twA paper spacers. To illustrate the utility of spiral winding a 0.5 mfd capacitor made of two layers of aluninum foil 2.5 inches wide by 0.0005 in thick and alternate layers cf paper (dielectric constant 2) 0.001 in thick, would have a diameter of only 0.9 in; whereas, in the plane parallel configuration, the structure would be 2.5' in by 220 in. Incidently, taking the dielectric strength of the paper to be of the; order of 500. kv/an, the voltage rating of the above example capacitor would be about 1250 volts. There are. several pitfalls in the manufacture of such spiral wound metnl/paper capacitors associated with the necessity of avoiding the presence of small inperfections in the Faper dielectric and the necessity of insuring conplete and reliable matching of (die metal foils to the surfaces of the paper dielectric. As an alternative to the jneuirement of very high quality control of the paper and of the forming process, iu Iras been found to be cost effective to evacuate the spaces with the wound capacitor ar.0 tc> subsequently fill the voids with a suitable liquid di rice hr: material prior to sealing the completed unit. 5.1.2.3. Returned Properties of Dielccti'ic Liquid Hie properties that are essential for the liquid dielectric can be enumerated in terms of the functions that tire liquid must fulfill as lollows: ' A. # , Electrical Properties - Slxauld have a dielectric constant at least as largo as that of the dielectric and a dielectric strength at least as high as that of the dielectric. HONS 045556 l4/i n /,vc. . . Physical Projorties - Must be liquid at a suitable ten;vraluro to allow processing of the device. Further, the filler should be liquid over the operating temperature range of the resulting device with a sufficiently email expansion coefficient so as to fulfill its function over the entire temperature range. . Must have a boiling point sufficiently elevated as to insure that the vapor pressure over the temperature range of the device does not cause rupture of the closure. . Chemical Properties - Must be chemically compatible with the dielectric material and with the metal plates. Specifically the dielectric liquid must wet both the plates and the diclectri: without altering either chemically or physically over the entire* temperature range of the device. The material must also be chemically stable at elevated temperatures so that its properties do not change over time. . Flonnwbility - Should be of such a chemical structure as to be hon-flarrmable and as to produce no flanmable breakdown pro ducts in the event that electrical breakdown does occur within the device. . Cost and Availability - Should be cheap and readily available With 'veil defined and standarized properties. . Tcxicity - Sliould be non-toxic and its possible breakdov.-n products should be non-toxic. " . Environmental Persistence - Should be environmentally degradable arxj non-bioaccumulating. , Legislative Acceptability - Sliould be acceptable under the laws of the . .S. and of all other countries to which capacitors arc exported. 5.1.3 Hie'Vsz cf PCJls in Capacitors . The rcnvre*rcial mixture of PCDs that is vised in capacitors is l:nown as Arcelor 1016. Thisurdtorinl is the standard against which the properties of any other proposed capacitor dielectric fluid must be compared. HONS 04555? /er/ar Inc. 11. 5.1.3.1 Properties of PCB Capacitor Fluid V. The relevant properties of Aroclor 1016 are as follows: Electrical Properties dielectric constant (ASTW D-149-44) dielectric strength (ASTM D-149-44) Resistivity (ASTW D--257--4G) . Physical Properties 5.85 (25C) >35 KV >500 x 109 . ' irelting point (pour point) -19*C boiling point 325-36GC coefficient of thermal expansion .00008 cc/cc/C . Chemical Properties corrosiveness: liquid - nonconosive - breakdown products - corrosive solvency: high, but satisfactory materials have . been developed stability (max. service temp.) 85* . Flammability liquid (Cleveland open cup flf.sh point) 141C breakdown products (primarily MCI): nonflammable -Cost and Availability .. Oost Availability - no problem . .40/lb. . Toxicity liquid: short term: lav long term: carcinogenic and embryotoxic breakdavn products (fran fire) short term: toxic (UCl) MONS 045558 /.vc . Persistence environmental - very S bioacomujating - very . Legislative Acceptability banned in Japan 5.1.3.2 Advantages an! Disadvantages of PCDs in Capacitors The only major problem arises frcm the extreme environ mental persistence ar.d long term carcinogenic properties of PCDs. In addition, the restrictions on the use of PCDs in electrical equipment exported to Japan will require., that suitable alternatives be available. 5.1.4 Alternates to the Use of PCBs in Capacitors ' As a guide to the evaluation of a candidate substitute for the PCBs in capacitor applications, there are two main approached that might be adopted: (a) a straightforward substitute that would require minimal alternation of the present production techniques; and (b) the introduction of new production techniques designe: to obviate the need for a filler. In either case, the prime requirement, and indeed the basis for this exercise, would have to be that the alternative solution be signifi cantly less environmentally distressing. 5.1.4.1 Substitutes for PCBs examine the first approach, it is noted that so long as the present method of construction is used, the filler is required and must necessarily satisfy requirements a, b erd d at least as well as is the case for the PCBs. The only alternative to these requirements is a more or less severe restriction on the operating temperature range of the oonpleted device and is probably not desirable. Or. the otiler hand, seme sacrifice in the requirements on the range of dielectric constant and dielectric strength seers possible by increasing tlie dimensions of the devices. It would appear that in many applications this increased size would be troublesome but not so serious as to be: impractical. Further, there are applications in which the extreme non-flann^bility of the filler and of its possible breahdcxvn products could lie somewhat relaxed. Finally, the oost factor could be considerably relaxed. MONS 045559 YerJar pc 4.J. A number ol coupounds arc being developed as replacements for rCDs in capacitor 5. The following list of compounds must all be considered as possible substitutes for rCDs. Mineral Oil: In standar'd use in capacitors until replaced by PCBs in the early l')30'r. lias a lower dielectric constant than PCD-225 vs 2.85, resulting in a required 2501 increase in capacitor area. The resulting capacitors will be 35% to 200% larger than the PCB capacitors. Mineral oil is flammable as are its breakdown prcducts. Flash point is 145"C. Castor Oil: Used in DC capacitors. Breaks derm in AC field. Dibutyl Sebacate: Unstable in contact with paper. Used in parallel plate capacitor:. Should be similar to mineral oil inflammability. Phthalate esters: Dioctyl" phthalate is used in capacitors in Japan, and by one U.S. manufacturer in capacitors built for export to Japan. Limited to 85C, vs SS'C fra PCB capacitors. Di-nonyl phthalate has been developed and proposed by Exxon under the trade name of BU 2065. There is some concern that these compounds may to carcinogenic. 'Isopropyl dichlorobiphenyl: Similar to PCB in properties. Being developed in Frrnce by Prodotec for electrical equipment manufacturers. Claimed to be less bioconcentrated than PCB (1016) and to degrade more rapidly. Present costs are higher than PCB, resulting in a -5 to 10% increase in the cost of capacitors. Siliconesi Being developed in U.S.' by Dew Coming and in Japan. Premised 1976 introduction. Butyl Monochloro diphenyl oxide: (Dow Chemical XFS-41G92). . All short term tests loo); cood, but there is a possibility of conversion dioxins which are very toxic. Presently undergoing service tests by McGraw Edison. Dielectric constant equal to PCB - direct substitution possible. Persistance is measured by degradation to CO? caused by digestion with sewage sludge microorganisms. Tire ixan-butylated and monobuty component of the mixture degrade 1400 and 45 times faster (respectively) than PCBs (Aroclor 101G! but the dibutyl compound degrades at only 3.5 times the PCU rate. Hie latter compound oaiyrn'ist's ;ilx>ut 20-25 percent of the mixture. Therefore the mixture is expected to degrade ever three times faster in the environment than PCB3. Hie chemical rcactiv.il; and the pliot.o decomposition data are not available currently. MONS 045560 ]h{f\R IAC . Blocencentration by fish was measured by the ratio o equilibrium concentrations of the fluid components in trout muscle vs ambient water. 'il5e ratio is about 00 for the most concentration component (dibutyl), about 300 for the least concentrated component (mono- and tri-butyl) but about 10,000 for 2,2',1,4' tutrachloro biphenyl (a PCD). Therefore the bioconcentration is over ten times less than PCPs. Acute toxicity (oral administration to rats) of both DPD and PCBs is very lew: greater than 10 grt/kg has been cited for DPO and greater than 1.6 pn/kg for PCBs. The toxicity (CbC 50) to fathead minnows is 15.4 mg/1 for DPO and 0.76 mg/1 for Aroclor 1016. A 7 hour rate inhalation study showed no effect for either PCB or DPO vapors, iThe two classes of chemicals have about the same vapor pressure). Neither class thawed any rabbit skin absorption. DPOs do not irritate rabbit skin or cause a chlctracne reaction, whereas PCB does cause moderate rabbit skin irritation and the impurities in some PCB preparations (dioxins and furans) cause chloracne. The Dew Chemical fluid is not mutagenic in the /mes test. A 90-day rat feeding study shewed that the fat accumulation, measured by the ratio of concentration in fat ecupared to diet concentration, is 22 tines greater for PCBs (Aroclor 1016) than for the Dow Chemical fluid. The rate of disappearance (clearance) after the 90-dny feeding period is much lower for Aroclor 1016 (60 days) than for Dew Chemical fluid (7 days). . Ionci Term Toxicity - no further results are currently available from the 90-day study. Thuse"results are necessary in ordep to evaluate the potential of chronic effects in people. Birth defect studies and reproductive function studies have not been conducted. Fince this is a new proprietary compound, Dow Chemical is the only source of data. Synthetic hydrocarbon oils - being developed by Monsanto as direct replacements for TCB. Dielectric constants equal or higher than that of PCB. Not fire resistant. 5.1.4.2 Elimination of Dielectric Liquids in Capacitors In view of the complex and strongly interacting nature of the requirements on's filler material, there is considerable interest in the development of alternative production teclmiques. The rather advanced tcclmology involved in the production of very thin plastic films of vary high physical integrity, such as .is required in many food packaging applications, has oixnqd the way for the l MONS 045561 15. 'Inc. . .i production of plastic films of suitable dielectric constant and dielectric strength for capacitor opplicetions. The parallel development of methods for the deposition of thin, carefully controlled metallic films on non-conducting surfaces, such as is widely practiced in the semiconductor industry, suggests that all of the problems that the filler is designed to obviate, could be circumvented by metallic films de posited onto suitable plastic substrates and the resulting structure spirally wound into useful capacitors. The essential problem associated with this approach, aside from the development of suitable high speed processing equipment, lies in the selection of a plastic substrate that is tractable but also stable at sufficiently high operatic temperatures. An additional problem with this approach lies in the nature of the polymers that have been studied, nearly all of the suitable materials are themselves flarmable and so arc the probable breakdown products. The technology for metallized polypropylene film capacitors comes frem Pye TTE of England which is partially csvned by Philips. Representatives of this canpany have approached most major U.S. manufacturers. Currently, this technology has been [urchased by one U.S. manufacturer at a cost of four percent on their capacitor sales for the life of the technology usage. The failure rate of the dry film capacitors is reported to be 20 times that of PCD filled capacitors. Present efforts on diy film type capacitors are directed teward the development of a suitable capacitor design. The projected availability of this substitute is in 3-5 years time. . ' Aerovox reports that dry type metallized polypropylene capacitors could bz used in fluorescent ballast application, and that this substitute is good for industrial applications up to 370 volts. Application of these units up to 440 volts is considered a possibility. This substitute, when available, could replace 50 per cent of the industrial capacitor market. It will increase the cost of industrial capacitors by 20 par cent as conparod to a comparable PCB unit but will double the cost of ballasts (two separate units will be required for purposes of start and storage.) The film used in these capacitors and metallizing equipment arc nunufacturod in Uuropo and have to be imported. The use of this technology will require major radegign of the parent products, specifically when used in fluorcc loup and room size air conditioner applications. MGNS 045562 ihlJtR iXC. 1G. totalized polyester film and metulizod nolycai l.onnte film capacitors are nahufacturcd by G.E. for electronic applications, but are not available in sizes ccr|e([it:ve with the PCD filled capacitors. 5.1.''`1.3 Iiimlnation of Capacitors Through Use of Active Circuits 1 "synthetic" capacitor for power factor correction can be constructed by use of a .* ynchronous motor running without a mechanical load resulting in a leading current. This device is known as a "synchronous capacitor". 5.1.5 Smeary - Substitutes for PCBs in Capacitors 5.1.5.1 Hectrical Properties Axoclor 1016 and its decomposition by-products are non flammable. Therefore, its v.se in capacitor application greatly reduces fire and explosion hazards. This dxraeteristic permits more economic designs of capacitors where safety codes require ;ireproof enclosures for capacitors containing flammable liquids. 1 he single most important property of a liquid to be used in a capacitor is its dielec trie constant (the ratio of its ability relative to air to store electrostatic eneryy). The dielectric constant of capacitor-grade PCD is 5.85 while that of mineral c-il is 2.25. Doubling the dielectric constant of the fluid used allows a reduction by half in the area of capacitor electrodes. As a result, significant savings can be realized in the costs of construction and install ation of these units. Additionally, the dielectric constant of askaxels matches closely that of the cellulora paper used in the capacitors (6.6 for cellulose and 5.85 for askarel). Decause of the close natch it is possible to stress askarelinpregnated paper to CO-- 50C volts/mil. Mule the stresses that can be applied to comparable papor-minel-al oil capacitors are limited to 300-350 volts/mil. tCB has good chemical stability, low vapor pressure and are considered adequata with regards to dissipation factor and dielectric strength. Its breakdown products, mainly MCI, have the advantage of being non-flanmable, but are highly corrosive. This requires the use of corrosion resistant materials inside the capacitors. ,u HONS 045563 /f.hJmi INC. .I 5.1.5.2 Toxicity l'~ The major disadvantage ot the PCB is its apparent toxicity. As mentioned, capacitors arc closed electrical systems and in normal circumst.mces FCBs used in the capacitor co not reach the environment. However, during electrical failure, these capacitors can leak and are ordinarily discarded when they fail 7he major disadvantage of the proposed substitutes is the lack of information. Leak of information on long term effects such as carcino genicity plus their fate in the environment, prevent their being proposed as iimediate substitute? ;o the- PCBs. Many studies are underway to determine dironic effects but until data are rvailable we should not act precipitiously. 5.1.5.3 relative Merits of Substitute Capacitor Fluids as " Compared to PCB . The relative merits for the various substitutes that have been proposed are susmarizac in Table 5.1.5.3-1. 5.1.5.4 Conclusions lCSs have been used almost exclusively in liquid filled capacitors in the U.;:. for Ihe past 40 years. Therefore, it is very difficult to estimate the risk costs of switching to a flammable fluid. Approximately 100,000,000 capacitors containing PCBs ue manufactured each year and are used almost universally in air conditioners, fluore;cent lights, and television sets as well as in industrial applications. Therefore, e'efi a small increase in the rislc of fires could have substantial effects on the safety of the public, . Tlie PCBs currently being used in capacitors have been reformulated (since (.971) t( have similar use properties with minimus ecological parsistance. Although these toxic properties of reus are fairly well documented, the environmental lo,id from continued production of PCD capacitors will be small confused to past uses of TOls. The alternative to the use of PCBs is to use a fluid having unltncwn and untasted long term health hazards and to increase the risk of fire from capacitors in ansimer ajid industrial electrical equipment. . .v t " There are a masher of alternatives to rCD presently being tested. Sufficient data thouId bo available within one of three years to determine whether the use of any of these alternative fluids will be warranted based on an analysis of combined health and fire risks. HONS 04556*. > .- .'Mineral Oil Phthalats esters Isopropyl dichloro biphenyl Silicones Butyiated mcmochloru ciphenyl oxide Synthetic hydrocarbon oils Solid plastic film Table 5.1.5.3-1 Relative Merits of Substitutes for PCB in Capecitors System Cost vs PCB Short Term Toxicity Long Term Toxicity and Environmental Effects A v a ila b ility i'*4 00H11 a . . V)_ --- - a>f~ . u* 2X 1.1X 1.1X t Poor Poor-fair Fair-good Poor Good Good 1.2X 1.1X Fair Fair-good Good Good 1.1X 3X Poor / Good Good No Good Fair Fair Good Questionable Questionable Excel. Fair Good Excellent Questionable i Questionable Excel. Excellent OK Used now in Japan On test in France To be introduced in 1976 On test in U.S. Lab tests at present 3 to 5 years `Compatibility is the ability to use replacement capacitors in existing systems - as a function of physical/ dimensional constraints. HONS 045565 ](:i;Jar IXC * . 5.2 PCBs iji TracCurmers Polychlorinated biphenyls are used as liquid coolants in electrical transformer*. PCBs have <ti advantage over the other major liquid transformer coolant (mineral oir.) in tliat they ore nonflamnable. Gaseous coolants are also nonflammable, hut gas cooled transformers haw disadvantages which are considered belorf. Alternative liquid coolants are probably available, but to date none have been found which have all "die advantages of PCBs. The following analysis includes a suimary of the purposes of transformers in electrical circuits, heat generation in transformers, currently-used cooling techniques, and materials being investigated - as substitutes for PCBs. .~ 5.2.1 Heat Generation in Electrical Circuits In direct current electrical circuits, the power, P, delivered at a load consisting of a pure :-esistance (e.g., a light bulb) is the product of the electrical current, i, mov.ng through the load and the voltage, v, across the load, P - (v) (i) But since current in proportional to voltage for a given resistance (that is, v = (i) (R) where R, the resistance, If: the constant of proportionality), it follows that power delivered to the load, resistance is the product of voltage, v, and the square of the current, i; . ~ P = i2R , Since tide Wire!: that carry electrical power from tlie site of generation ' (be it o battery or uj elec trical generator) to the load resistance also offer resistance to the flow of electrical current, a portion of the power generated is lost through heating of the wires connecting the load to the electric power source. However, in irony circuits (e.g., an automobile electrical system), the power lost .in the transmitting wires is small in comparison to the power delivered at the load (such os the headlights). For a given wire diameter, electrical resistance is proportional to the length of the wire.- Thus, in transmitting electrical pewor over long distances, the resistance or tho wires could cause tie dissipation of a significant portion of tlie energy intended for the load. MONS 045566 VerJmi pc 20. In alternating current circuits, the paver dissipated in a resistance (either in the load or in t ie wires carrying the power to the load) is also given by P " i^R. (The relation, P = (v)(i), always applies to paver dissipated in d.c. circuits, but in a.c. circuits Die expression only applies when'the voltage and current are in phase with Each other, which isn't always the case, though in most practical instances involving purely resistive loads it is a fairly accurate scans by which to calculate the [awer dissipated.) 2 The expression, P = i R, it not influenced by the phase relation between voltage and current rnd thus applies to both alternating and direct current circuits. It is apparent from this opression that the energy dissipated in a transmission wire having resistance R le proportional to the seoond power of the current; thus, if the current being delivered to the load were to be doubled, the energy losses in the transmission wire weald be quadrupled. * Ccrrmercial elec trical power is often generated many miles from where it is to be used. There are hundreds of thousands of miles of power transmission lines in this country, and it is not unusual for tie electrical power generated in one place to be used hundreds cf miles away, which means that a goodly amount of electri cal resistance must be over come in transmitting electrical energy to the user. The method usee to minimize energy losses in transmission lines is to roduoe tlie current, i, and thus minimize the iZR losses (also known as Joule heating losses) in the trrr smission wire. But in order to deliver maximum paver to the laid, the transmiseiprt'voltoge, v, must be increased since the paver delivered is (as with d.c. circuits) effectively given by P = (v)(i). Thus, if the trans mitted current, i, in reduced by a factor of 2 - which reduces the Joule heating losses of Die transmissicn line by a factor of 4 - the voltage of the transmitted paver must be increased hr1 a factor of 2. In practice, however, the electric paver which we use in our lianas at 110 volts is transmitted at voltages ranging up to more than 700,000 volts - roughly GOOD times greater than cornon wall-socket voltage, which further neons that Joule heating losses are (G500) 2 or more than 40 million times less than if tJie paver were transnu-ttpd at 110 volts. MONS 045567 5.2.2 The Notnre and Purpose of Transformers Tne purpose of a transformer in an electrical circuit is to transform electrical power ton its high-current lav-voltage cluractcri sties at the goner..Ling '/eh/ar hrc. 21. facility to the low-current high-voltage diaracteristics needed for efficient transmission; and then, at or near the .site of use, transformers perform the opposite transformation, bringing the pcwer back into its lew-volt.jge (typically llOv or 220v) high-current form. There are two types of transformers used in the electrical power industry: power transformers (used for "stepping up" the voltage at the plant) and distribution transformers (used for "stepping down" the voltage at or near the site of power ui;e). Power and distribution transformers operate on the sane principle the one merely operates in a reversed fashion to the other. Using this simple CORE (IRON) schematic diagram, the principle of operation of a transformer can be stormed up by' saying that the turns ration, N^/N^, is equal to the voltage ratio, V^/Vj. The details of the interaction between the windings and the ferrcmagnetic oore of tie transformer need not; be considered here except to say that the magnetic field pro duced in the core as a result of tire current flowing in the windings on the input side (called the primary aide) of the transformer induces a current in the output (secondary) side of the transformer. (If the transformer is being used for stepping ip voltage, then the primary side is the one having fewer turns; for stepping clown, the primary side is the. cnc having most turns.) The lengths of wire in the windings offer resistance to the flew of electricity, the result being tile production of heat in the windings. Heat is also produced by currents induced in the transformer core as a result of the sa-na mechanisms that induce currents in tlx: secondary windings. Since the electrical resistance of most conducting materials increases with temperature, the efficiency of tile tr.ancfonvor (i.e., the ratio of the output power to the input per.'nr) is MONS 045568 maximized if the tr.-j.tfomcr is kept at a lc1.: cycraLij.y temperature. Therefore, all transformers used in the electrical industry have provision for cooling, based on either gaseous or Liquid coolant. ^ the coo."aits in camion use today are: . mineral oil KBs air) gas dry type Host po.vtt transformers (i.e., step up transformers) are situated in . remote locations where fire and explosions are not a threat to people or property. Mineral oils are oormanly used in power transformers. Distribution transformers, on the other hand, <re often located in buildings and near population areas. Such transformers must bn either of the dry type on they must be cooled with non-flimuable 1i . FCB-type fluids. . PCB-oooL.ed transformers account for about 5 to 10 percent of all trans formers in service. KBs are, of oourse, at issue here, and certain substitutes have been suggested end are being studied. The relative merit of the currently used cooling method:' and of the suggested substitutes is considered below. 5.2.3 r.1ne Properties of PCB-Ctaoled Transformers Liquid (octants in transformers have better heat transfer and heat capacity characters: tics than gaseous coolants. PCBs have the furtlier advantage of being the most re n-flammable of currently used transformer coolants. The other advantages of KBs <ire their high dielectric strength, their outstanding chemical stability, and their lew viscosity. Disadvantages, in addition to the environmental threat, are the highly corrosive 1IC1 they produce when arcing takes place and their cost, which is about seven times as mudh as mineral oil, on a volume basis. ' The volume of liquid coolant used in various transformers ranges from 40 to 1500 gallons (500 to 20,000 lbs, for PCBs), with an average of about 230 gallons (3000 lbs). One transformer producer, General Electric, estimates Urns number of PCB-filled transformers put in service in the U.S. since 1932 to be 135,000, and virtually all are still* in service. Typical lifetime is often greater than 30 years, and units th:t do fail are usually rebuilt and returned to service. The current MONS 045569 YEll[\ H ixc. 23. production rale for niB-filled units is about 5,000 per year, requiring sane 19 million pounds of PCDs. V pCB-fillcd trirsformers are located mostly inside public, oomrcrcinl, or industrial buildings, oi on the roof tops of such buildings. No special en closures or vaults are rcqiired except as are necessary to prevent occidental electrical or mechanical ccntact of persons with the equipment. However, the National Electrical Gxfc dees specify vaults for the indoor installation of FCBfilled transformers rated rore than 35,000 volts. PCB-filled transformers are limited by the dielectric itrength of the material to ratings below 69,000 volts. 5.2.3.? Oil-Type Transformers rCB-ao/ taining transformers cost about 1.3 times as much as oil-filled units of the sae capacity, and thus most users prefer the oil-type where possible. If safety were not a consideration, there is no reason why oilfilled transformers could rot be used in all applications. Physical size would be unchanged; weight ard oost would be less. However, fire underwriters do not approve of tire use of oils end of* r flammable liquids for indoor applications; and where oil-filled transformers arr not specifically prohibited as on-site replacements for PCB-filled units, the Naticnal Electrical Code imposes certain restrictions upon their mode of installation. All oil-filled transformers rated over 600 volts re quire vaults if the units' ire to be located in or near buildings; alternative fire protection arrangements art permitted for units rated less than 600 volts. Assuming space were available In ex:.sting buildings to accomodate these special auxiliary safety provisions, seconding to General Electric the cost of vault construction would range from $5,000 to $50,000 per transformer. Detailed cost data on vault construction is being gathered. Oil-filled units can be installed outdoors if they are suitably isolated from flammable structures or if these structures Eure suitably safeguarded against fires. When transformers are located outside of the building they service, however, the low-voltage paver must be brought into the building via cables or insulated buses, the cost of wliich could also range from $5,000 to $50,000 per installation. Also, jjutdeor tiansfomers lave to be rated slightly higher than indoor ones because of .loule heating losses in the cable and bus runs. HONS 045570 vfmJar pc. 24. 5.2,3.2 Dry-Type Transformers Dry-tile transformers cost about 1.5 times as much as oil transformers. They could )e used indoors for some applications, but they have limitations that should lie considered. For instance, dry-type transformers are not ns efficient or relliible as conparably rated liquid-filled units. Dry units are more prone to damage tlur to surges and they have loss overload capacity tlian liquid-filled units. (An i:dison Electric Institute survey of failures in network transformers stored e: 7 pe:-cent per year failure rate for dry units arc compared to 0.2 percent for liquld- 'illcd units. General Electric reports that many liquidfilled transformers can curtain a 100 percent overload for 2 hours, which means that liquid-filled transformers are more likely to sustain operation during periods of temporary malfunction of related equipment.) Dry-tyje transformers are 10 to 30 percent larger in linear dimension than comparably rated liquid-cooled units, which puts a space constraint on their use as direct replacements for PCB-cooled units already in service. The extra noise of dry transfer iters - typically 5 to 10 db louder - is also a considera tion for indoor installations. Outdoor installations of dry-type transformers is ' a problem, too, because of their sensitivity to moisture and airborne pollutants. 5.2.4 Requlrid Properties for Transformer Oils (Heat Transfer Liquids) A suitable substitute for PCBs in transformer applications would have all of the properties of Pile, plus 1cm toxicity and, especially, lew environmental persistar.ee. The pmpertJ.cs desired of a transformer coolant are: 1. 1cm vlscoa.ty (for heat transfer properties); high heat capacity; liigh heat of vaporization . 2. Non-flammability, required primarily for indoor applica tions' ' 3. Clienical stability at high temperatures; low vapor pressure 4. Nigh dielectric strength, for reliability and small size 5. Chemical^and physical compatibility with other materials in the transformer 6. Inert degradation products, to assure minimum damage to other transformer parts in (lie event of clemical .breakdown HONS 045571 JjXC. . 7. High electrical resistivity 8. Low toxicity of the fluid and its decomposition products 9. Lew cost 5,2,5 Substitutes for I'CBs in Transformers 5,2,5.1 Fluorocarbons Certain fluorocarbon compounds have properties similar to the PCBs, and sene study is being carried out in this area. However, fluoro carbons are hiyWy volatile in cenparison to PCBs, and they are about six tines as expensive at this tine - tlrough, of course, higher production volunes would lower their cost, 'l S.2.S 2 Silicones Lew V. scosity silicone fluids (on the order of 50 centistokes) are also possible replacanents for PCBs. Silicones are currently produced by four companies: General Electric, Dew-Coming, Union Carbide and Stauffer. The silicone fluid recommended by one producer is polydimethyl siloxane, which has this molecular structure: 2H, CH.. I I3 at | H,C -- Si -- 0(--Si--0--) Si --at 3T I "I 3 ch3 ch3 ch3 " Physical Properties Silicone fluids have the special advantage of a relatively teirperature-indepc:r)de.nt viscosity, and generally they have liigh flash points and low pour points. The silicone fluids have somewiiat poorer teat transfer charac teristics than mineral oil, but can be substituted directly for mineral oils in existing transformers. 0455^ V Elarmnbi li ty Polydi:methyl siloxane has a higher flash point them conven tional, non-PCB transformer coolants: 280,'C versus 14G"C (PCBs have no me flash 26. joint.). lie heat of combustion of 50-ccntistokc polydiinothyl siloxane is lower than that of mineral oil - 7.67 keal/gm versus 11.0 keal/gm - and since the sili cones bu^n marc s)a>ly, they are considered poor fuel. On the Underwriters Laboratories fire-hazard classification (in which water is rated an 0 and ether as 100) polydimethyl siloxane is classified as 4 to 5, wliich is slightly higher than the 2 to 3 rating given to FCDs, but it is considerably less than the mineral oil rating of 10 to 20. Bcolog.ical Persistence These compounds do not biodegrade-, measured by sewage sludge breakdown to GOj. However- there is evidence that they partly depolymerize to low nolecular weight compounds upon contact with soil and water. Since ultra violet light-decomposes methyl silicones, sunlight exposure nay be the mechanism for environmental degradation. ploaccimulation . Mo tendency for bioaccumulation or bioccncentration has occurred in experiments. In mammals, the compound is not absorbed by the gastrointestinal tract or by skin. . Toxicity The PCD substitute developed by Dow-Corning for power trans formers is called 02-1090. IT--is a particular lot of the DC-200 series of fluids, vhich are polydinetiyl siloxanes of various chain lengths. The literature on en vironmental and hea th characteristics of these fluids refers to at least six other fluids, most of which are probably DC-200 fluids but some of which could be other mixtures with certain additives. By necessity, the following comments are all based cm the assumption tint all of these confounds have identical persistanco, bioaccimulation, and toxicity properties. liie acute toxicity of siloxanes is very low in guinea pigs, rats, and rabbits; -P gnvOcg/duy for an extended period produces no toxic effect in guinea pigs. Hie IDtO^in rats is greater than 20 gm/kg. They ore not fatiguing, irritating or sensitizing to skin. FDA allows them as food additives up to a con centration of 10 P)xn. In mallard ducklings and bobwhite quail, 5,000 ppm for 5 MQNS 045573 r Yl'.lj'llt '/.A'C. .. 27. diys in diet cuir.es no eDict. Hie human gut absorbs a negligible amount of 0 oonponnds. In 28-day orni rat studies, amounts of up to 20 gm/kg/day produced no effect, but in 9f-day feeding experiments, the no-effect level was 190 mg/kg/diy. In beagle" dogs, 300 mg/kg/cay for 120 days produced no effects. In mice 3 percent in the diet for 00 weeks [.reduced no effects. A 2-year rat study at 3 gm/kg/days produced no effects. Adverse effects were seen in two experiments: a) a teratology study with rats and rabbit.; showed an excess incidence of adverse effects; b) rats injected with the fluid sir-wed seme positive pathological findings. The latter bra einx-rinents run by di ifcrc-a t investigators have produced no effects, but should bo reported. All these classes are extremely non-toxic to rodents. In fish, (e.g. fathead minnows) tho siloxanes have no effect, the diphenyl oxides (DPOs)are intermediate and the PCBs ere 2U times more toxic than DPOs. With respect to skin and eye sensitivity all an negative except PCBs, which produce moderate rabbit skin irratation. In subacute studies, DPO results are still pending, but indications arc that it concentrates in fat tissue only 1/20 the extent of PCB accumulation, and it cleans tissue after cessat: on of exposure 10 times faster than PCBs. The siloxanc mixtures produce no effect; in feeding studies of rats, mice, beagle dogs with high exposures over 17 weeks to two years. With injection seme adverse effects have been seen, but tlie experiment Blould be repeated. Siloxanes could produce birth defects but results ore not clear. The ma; or deficiency in our knowledge of the silicones appears to be in their fate in the -environment and the toxicity of their breakdown products, as much as FCUs. Cost The silicone transformer fluids currently cost up to 1.5 times Avail n! dlity Daw-Coining is currently completing evaluation of polydimethyl siloxane ns a high voltage insulating fluid. They report, tlxxigh, that a near term 100 percent replacement o` PCBs in transformers by this fluid is not possible. If a transformer market" were to develop for polydimotiiyl siloxanc, the present domestic capacity could only be adequate to supply new transformers. Tho time lag for a 100 j-orcent replacement of I'Cite in transformers by polydinethyl siloxane will be on the order of 5 to 10 years. MONS 045574 mfiii jw. Substituted Pi cblorobi.|,i ;onyl Another possible PCD substitute is a dichlorobipbcnyl with a branched--hydtrocarbon :-hair., such as: iCrCT' Tire efiect of tire substitution should be to increase the bio degradability of the compoind relative to PCB but to decrease its fire resistance. 5.2.6 Summary - Substitute for PCBs in Transformers Most transformers use mineral oil as a coolant; only the 5 to 10 per cent of all transformers which must have exceptional resistance to fire currently use PCBs as a coolant. Hie singlp most, important property of any liquid considered as a re placement for PCBs it its fire resistance. Other alternatives to eliminating the use of PCB transformers include the use of mineral oil transformers in vaults, the relocation of the transformer to a safe location, or the use of dry transformers. Each of these alternatives has major economic disadvantages which must be weighed against the environmental risk of oontinued use of PCB or the increased fire risk accompanying the use of other alternatives such as silicone liquids. 5.2.6.] Relative Merits of Substitutes for PCBs in ' Transformers ' * lire relative merits of tlie various alternatives that have been proposed are sumarized in Table 5.2.6.1-1. 6.2.6.2 Conclusions Bcoha.iic factors totally govern the use of PCSs or their re placement by other materials in transformer applications. PCBs ore presently used where tie money saved by locating the transformer in a hazardous location offsets the lugher cost of PCB relative to mineral oil. The alternatives to the use of 103 include tlie relocation of tlie transformer to a safe location or the use of a fireproof vault around the transform--r. HONS 045575 TABLE 5.2.6.1-1 . Helath'e Marits of Alternatives to the Ubu of PCB Transformer Fluids 29. R eliability vs PCB C o n v e rtib ility c F re se n t Trans fo r er Cost/ transform F ire Risk l ( Mineral oil in vault ewel excel $5000 to $50,000 good usually no Relocate transformer excel excel '$5000 to $50,000 good usually no Use dry transformer ext el excel 1.5x poor usually no Silicone heat transfer oil . Substituted PCB heat transfer oil excel poor/fair fair/good fair/good 1.3x new $500 to 7500 per conversation ?' good good yes yes MONS 045576 \?a< substitution of any other heal Lrannforr.er fluid for PCB in existing transformers will increase the risk of fires. Silicone oils are less flamsublc tlian mineral oil, and are presently being used in railroad loco motive tiansformers in Japan. Tlvs increased risk of fire is felt to be more than offset by the reduction in the probability of toxic spills in this application. The use of silicones, or nay other flantnoble liquids, to replace PCBs in existing transformers in the U.S. will be a function of the probable cost of fire risk tii.it is incurred as reflected in insurance rates and building codes. I ^ HONS 045577