American Society of Heating and Ventilating Engineers Guide, 1932
Table 12. Coefficients of Transmission (V) of Hollow Tile Walls with Stucco Exterior Finish *>-<1
Note.--These coefficients are expressed in Btu per hour per square foot per 1 deg fahr
DIFFERENCE IN TEMPERATURE BETWEEN THE AIR ON THE TWO SIDES AND ARB BASED ON AN OUTSIDE WIND EXPOSURE OF 15 MILES PER HOUR.
The values of U inthisTable are basedon thefollowinq
Internal Conductivities or Conductances which are
expressedm
per Wr perSq.Ft. per TF
Stucco WollowTile 8"0.4<1 IO* 0-44
Cement Mortar
Raster board Raster (Gypsum)
WoodLath ^Plaster Corkboard
Riqid Insulation (Boardform)
8.00 perl"
\2"=0.*l iG?0.25 8.00 perl" 3.73 perl* 1.11 per?
2.00 osapplied
0.30 perl"
0.33 perf
Cellular Gypsum (18*) Flaked GypsumDry(24*)
aSSpert'
0.48perT
Y- Thickness of Insulation where specified
_0LQ 0
Interior
Construction
'Z
l Plain Walls - No Interior Finish
Thickness of WollowTile--X
Y 8"
A
io" \T \<o BCD
Q3I7 a 304 0.241 aiq5
2 T Plaster on WollowTile 3 % Plaster on Metal Lath -- Furred A j Plaster on Wood Lath -Furred
Q 216 0.285 Q22q 0.188 0.Z28 0.221 0.186 0158 o.ziq 0.213 0.180 0.153
5 -j Plaster on & Plasterboard - Furred 4 Plasteron Wood Lath on 2* Furrmq
6 Strips -- Cellular Gypsum Fill c 4 Plasteron Wood Lath on 2" Furrmq
7 Strips -- Flaked Gypsum Fill
GZ20 0.213 a
ai5fo 0.153
0.180 0.153 0.135 0.120
a >r 0.141
o.m 0.124 o.m
8 2 Plasteron Giqid Insulation --
(Board form) Furred S
i" 2
0.172
0-16.8 0.147 o.i2q
r 0.137 0.134 0.120 0.108
lO ^ Raster on Cork board set in ^ Cement Mortar
II
auq 0.117 0-106 o.oq6 2 aoqq o.oqs o.oqo 0.083
Based on 1% in., the actual thickness of 2 in. furring strips. bFigures on this page can be used with sufficient accuracy for hollow tile walls without stucco finish. cThe coefficient used for cellular gypsum. 0.59 is for 18 lb. weight--weights as low as 12 lb. may be used. dThe 8 in. and 10 in. tile figures are based on two cells in the direction of heat flow. The 12 in. tile is based on three cells in the direction of heat flow. The 16 in. tile consists of one 10 in. tile and one 6 in. -tile, each having two cells in the direction of heat flow.
44
Chapter 3--Heat Transfer Through Materials and Constructions-
Table 13. Coefficients of Transmission (/) of Limestone or Sandstone Walls
Note.--These coefficients are expressed in Btu per hour per square foot per- 1 deg fahr
DIFFERENCE IN TEMPERATURE BETWEEN THE AIR ON THE TWO SIDES AND ARB BASED ON AN OUTSIDE WIND EXPOSURE OF 15 MILES PER HOUR.
Thevalues of Uin this Table are based on thefollowinq
Internal Conductivities or Conductances which are
expressed in B.tu. per Ur perSq.Ft.per l*F
Stone
10.00 per l"
Cement Mortar Plasterboard
8.00 per 1* 3.73 per
Plaster (Gypsum)
2.32 peri"
Wood Lath t Plaster
2.oo as applied
Cork board
0.30 per l"
Riqid Insulation (Boardform)0.33 perl*
Cellular Gypsum (18*) Flaked Gypsum, Dry (24*)
O.sq perl" 048 perl"
l.
yi
----
Y* Thickness of Insulation where specified
b .O Interior
1 Construction
z
l Plain Walls -No Interior Finish
Y 8" A
Thickness of Stone -X
IO* 12." \G>~ 20`
& c DE
24"
F
0.556 0.502 0.457 Q385 0334 0.245
z 4 Plaster on Stone
0.4*17 0.452 0.415 0.356 0.311 can
3 i Plasteron Metal Lath -- Furred
0.330 0.310 0.242 0.261 0.236 0.216
4 4. Plaster on Wood Lath - Furred
5 \ Plasteron Plaster board-Furred
0.312 0.244 0-277 0250 0.227 0.208 0.314 0.245 0.274 0.251 0.228 0.204
4 2"Raster on Wood Lath on Furrmq 6 Strips-Cellular Gypsum Fill b
a
r 0.148 0.141 0.1&4 0.01 0.160 0.150
4 Raster on Wood Lath on 2" Furrmq 7 Strips -- Flaked Gypsum Fill
a
\*V8 0.175 0.164 0.163 0.153 0.145 0437
8 "Z Raster on Rtqtd Insulation
(Board form) Furred
4
to 4 Plasteron Corkboard set
Cement Mortar ii
2l" 0.225 0.216 0.207 0.141 0.177 0.166 r 0.168 0.163 0.157 a 148 0.140 0.132
a 141 0:138 0.134 0.127 0.121 0.115 2." 0.114 0.112 0.104 0.105 0101 0.048
Based on 1% in., the actual thickness of 2 in. furring strips. bThe coefficient used for cellular gypsum. 0.59 is for 18 lb. weight--^weights as low as 12 lb. may be used.
45