Document 7Op6YNbVy207Q1e99yOJjOVKV
American Society of Heating and Ventilating Engineers Guide, 1935
Otherwise, there is little difference in the appearance of wrought-iron
steel pipe, although microscopic examination of polished and/ etched
specimens will readily disclose the difference.
/^
Cast Ferrous Pipe. There are now available several types of ca
ferrous-metal pipe made of a good grade of cast-iron with'or without additions of nickel, chromium, or other alloy. This pipe is available i sizes from \x/l in. to 6 in., and in standard lengths of 5 or 6 ft with external
and internal diameters closely approximating those of extra-stronv wrought pipe. Cast ferrous pipe may be obtained coupled, bevelled for
welding, or with ends plain or grooved for the several types of. couplings It is easily cut and threaded as wellas welded. The fact that it is readily
welded enables the manufacturers to supply the pipe in any lengths practicable for handling.
Alloy Metal Pipe. Steel pipe bearing a small alloy of copper or other alloying element, such as molybdenum or manganese, has been claimed to possess more resistance to corrosion than plain steel pipe and it is advertised and sold under various trade names.
Copper Pipe and Fittings. Owing to its inherent resistance to' cor rosion, copper and brass pipe have always been used in heating, venti lating, and water supply installations, but the cost with standard dimen sions for threaded connections has been high. The recent introduction of fittings which permit erection by soldering or sweating allows the use of pipe with thinner walls than are possible with threaded connections, thereby reducing the cost of installations.
The initial cost of brass and copper pipe installations generally runs higher than the corresponding job with steel pipe and screwed connections in spite of the use of thin-wall pipe, but the corrosive nature of the fluid conveyed or the inaccessibility of some of the piping may warrant use of a more expensive material than plain steel. The advantages of corrosionresisting pipe and fittings should be weighed against the correspondingly higher initial cost.
DIMENSIONS
The IPS dimensions of commercial pipe universally used at the present time conform to the recommendations made by a Committee of the A.S.M.E. in .1886. Pipe up to 12 in. in diameter is made in certain definite sizes designated by nominal internal diameter which is somewhat different from the actual internal diameter, depending on the wall thick ness required. There are three weights of wrought-iron and steel pipe commonly used, known as standard-weight, extra-strong, and double-extra strong. Because of the necessity of maintaining the same external dia meter in all three weights for the same nominal size, the added wall thickness is obtained by decreasing the internal diameter. The term full-weight, when applied to sizes below 8 in., means that the pipe is up to the nominal weight per foot. When applied to sizes between 8 and 12 in., inclusive, it often indicates that the pipe has the heaviest of several wall thicknesses listed. In sizes 14 in. and upward, pipe is designated by its outside diameter (O.D.) and the wall thickness is specified.
While the demands for pipe for the heating and ventilating industry are reasonably well served by the standard-weight arid extra-strong pipe,
580
Chapter 34--Pipe, Fittings, Welding
ands for pipe for higher pressures and temperatures in industry denl. . jn the USe of a multiplicity of wall thicknesses for all sizes. Even ^heating installations, the erection of piping by welding was deemed to 10 " t the use of pipe lighter than standard weight. For these reasons, ^^ectional Committee on Standardization of Wrought Iron and Wrought %uel Pipe Tubing functioning under the procedure of the American Standards Association was appointed to standardize the dimensions and
materials of pipe. The proposed pipe standard recommended by that sectional committee
- has set up several schedules of pipe including standard-weight arid extra-" trong thicknesses which are now included in Schedules 40 and 60, re flectively. The schedules approved by the Sectional Committee are jnven in Tables 1 and 3 and the corresponding weights in Tables 2 and 4.
Standard-weight pipe is generally furnished with threaded ends in random lengths of 16 to 22 ft, although when ordered with plain ends, 5 per cent may be in lengths of 12 to 16 ft. Five per cent of the total number of lengths ordered may be jointers which are two pieces coupled together. Extra-strong pipe is generally furnished with plain ends in random lengths of 12 to 22 ft, although 5 per cent may be in lengths of
6 to 12 ft.
EXPANSION AND FLEXIBILITY
The increase in temperature of a' pipe from room temperature to an operating steam or water temperature one hundred degrees or more above room temperature results in an increase in length of the pipe for which provision must be made. The amount of linear expansion (or contraction in the case of refrigeration lines) per unit length of material per degree change in temperature is termed the coefficient of linear expansion of that material, or commonly, the coefficient of expansion. This coefficient varies with the material.
The linear expansion of cast iron, steel, wrought-iron, and copper pipe, the materials most frequently used in heating and ventilating work; can be determined from Table 5.
The elongation values in Table 5 were computed from the following formula:
i` = z-[1 + a (w) +6 (w)2]
where
(1>
it = length at temperature t degrees Fahrenheit, feet. Lo = length at 32 F, feet.
t = final temperature, degrees Fahrenheit. o and b are constants as follows:.
Metal
a .6
Cast-Iron............................................ Steel.
Wrought-iron........................................... Copper.........................................................
0.005441 0.006212 0.006503 0.009278
0.001747 0.001623 0.001622 0.001244
581
1