Document 7O8bpOoO1groMZXO1EOMQ7k1g
'4%8
CHAPTER 21
1955 Guide
Steam Heating Systems
489
Two-Pipe High Pressure Systems
Two-pipe high pressure systems operate at' pressures above 15 psig, usually from 30 to 150 psig. They are usually used .in large industrial type buildings, which are equipped with unit heaters or large built-up fan units, or in which high pressure steam is required for process work.
Fig. 8 illustrates a typical high pressure system. Because of the high pressures and the great differential between steam and return mains, it is possible tb locate returns above the heating units and lift the condensate to these returns.
The condensate can be flashed into steam in low pressure mains if any are available, or passed through an economizer heater before being dis charged to a vented receiver. It is, of course, necessary to provide for the elimination of air from high pressure systems, the same as in low pressure systems.
Fig. 6. Ttpical Up-Feed Gravity One-Pipe Air-Vent System
or vapor at sub-atmospheric pressures, and at consequent lower tempera tures. Systems which use vacuum valves are known as vapor or vacuum one-pipe systems. The vapor or vacuum systems will maintain a more uniform temperature condition than the pressure systems.
Each heating unit in a one-pipe system may also be provided with a valve on the connection to the unit, although this is not essential except to shut the unit off in case it is. not desired for. heating. Valves on onepipe systems must be either fully opened or fully closed; No-throttling or modulating.position can be, maintained since, if a valve is partially closed, condensate will not drain from the unit. This:condition is dan gerous because it may create a low water;condition .in the boiler with con sequent burning or cracking of the boiler, or create a hazard due to the freezing of the water-logged, heating unit itself.
TWO-PIPE SYSTEMS Two-pipe systems, as previously defined, are systems in which steam and condensate flow in separate'pipes. Two-pipe systems may operate under high pressure,'low pressure, vapor, or vacuum conditions. Either the up-flow or the; down-flow arrangement of mains may be employed-
Fig. 7. Typical Steam Runout where Risers are Dripped
. Return traps used on high pressure systems, are usually of the bucket,
uiverted bucket, float or impulse type.
Two-Pipe Low Pressure Systems
Low pressure systems operate at pressures of 0 to 15 psig. The piping
arrangement of both up-feed and down-feed low pressure systems is idenical with those of two-pipe vapor systems described in the following secuon. The only difference between the two systems is in the type of air
^e.used. The air valves used in low pressure systems usually do not ntam the check discs and hence, the system cannot operate under a acuum. The low pressure systems are not as popular as the vapor sysr because they have the disadvantage of not holding heat when the te of steam generation is diminishing. They also have .the disadvantage corroding to a greater extent than vapor systems, due to the continued presence of new air in the system.
denW Pressure systems have the advantage, however, of returning con-
Dos w6
boiler readily and not retaining it in the piping, as may be
sible in vapor systems when the system pressure exceeds the operating