Document 7O5KRRkG2r8omvJVpp9wbevRo
HEATING VENTILATING AIR CONDITIONING GUIDE 1943
By-pass: A pipe or duct, usually controlled by valve or damper, for short-circuiting
fluid flow.
Calorie: (large calorie or kilogram calorie) is equal to 1000 international steam-table
calories = 1/860 international kilowatthour. For practical purposes it may be con
sidered as 1/100 of the heat required to raise the temperature of 1 kilogram of water
from 0 to 100 C.
Central Fan System: A mechanical indirect system of heating, ventilating, or air
conditioning, in which the air is treated or handled by equipment located outside the
rooms served, usually at a central location, and is conveyed to and from the rooms by
means of a fan and a system of distributing ducts. (See Chapter 21.)
Chimney Effect: The tendency in a duct or other vertical air passage for air to rise
when heated, owing to its decrease in density.
Coefficient of Transmission: The amount of heat (Btu) transmitted from air to air in
one hour per square foot of the wall, floor, roof or ceiling for a difference in temperature
of 1 F between the air on the inside and that on the outside of the wall, floor, roof or ceiling.
Comfort Atr Conditioning: The process .by which simultaneously the temperature,
moisture content, movement and quality of the air in enclosed spaces intended for
human occupancy may be maintained within required limits. (See Air Conditioning.)
Comfort Line: The effective temperature at which the largest percentage of adults
feels comfortable.
Comfort Zone (Average): The range of effective temperatures over which the majority
(50 per cent or more) of adults feel comfortable. Comfort Zone (Extreme): The range of
effective temperatures over which one or more adults feel comfortable. (See Chapter 2.)
Concealed Radiator: A heating device located within, adjacent to, or exterior to the
room being heated but so covered or enclosed orconcealed that the heat transfer surface
of the device, which may be either a radiator or a convector, does not see the room.
Such a device transfers its heat to the room largely by convection air.currents.
Conductance: The amount of heat (Btu) transmitted from surface to surface in one
hour through one square foot of a material or construction, whatever its thickness, when
the temperature difference is 1 F between the two surfaces.
Conduction: The transmission of heat through and by means of matter unaccom
panied by any obvious motion of the matter.
Conductivity: The amount of heat (Btu) transmitted in one hour through one square
foot of a homogeneous material 1 in. thick for a difference in temperature of 1 F between,
the two surfaces of the material.
Conductor (Heat): A material capable of readily conducting heat. The opposite of
an insulator or insulation.
Constant Relative Humidity Line: Any. line on the psychrometric chart representing a
series of conditions which may be evaluated by .one percentage of relative humidity;
there, are also constant dry-bulb lines, wet-bulb lines, effective temperature lines, vapor
pressure lines, and lines showing other physical properties of air mixed with water vapor..
Convection: The transmission of heat by the circulation of a liquid or a gas such as
air. Convection may be natural or forced.
Convector: A heat transfer surface designed to transfer its heat to surrounding air
largely or wholly by convection. Such a surface may or may not be enclosed or concealed.
When concealed and enclosed the resulting device is sometimes referred to as a concealed
radiator. (See also definition of Radiator.) (See also. Chapter 13.)
Decibel: A unit commonly used for expressing sound or noise intensipties referred to
an arbitrary reference level. It is defined by the relation db = 10 logio -7, , where Pi is
ro
the unknown intensity, and Pa is the reference level which is commonly taken as 10-"
watts.per square centimeter.
...
Degree-Day: A unit, based upon temperature difference and time, used in specifying
the nominal heating load in winter. For any one day there exists as many degree:days
as there are degrees Fahrenheit difference in temperature between the mean temperature
for the day and 65 F.
Degree of Saturation or Per Cent Saturation: The ratio of actual humidity ratio W to
the saturation humidity ratio WB corresponding to the actual temperature and the
,' W '
..
.
observed pressure, n = (Approximately the same as but not.identical with'relative-
-i. '' s
humidity. 'See Chapter 1).
,
Dehumidification: The. condensation of water vapor from air by codling below the
dew-point.
844
CHAPTER 47. TERMINOLOGY
Dehydration: The removal of water vapor from air by the use of adsorbing or absorb
ing materials. Density: The weight of a unit volume, expressed in pounds per cubic foot, d = W -4- V.
Dew-Point Temperature: The temperature corresponding to saturation (100 per cent
relative humidity) for a given moisture content.
Direct-Indirect Heating Unit: A heating unit located in the room or space to be heated
and partially enclosed, the enclosed portion being used to heat air which enters from
outside the room.
Direct Radiator: Same as Radiator.
Direct-Return System (Hot Water): A hot water system in which the water, after it
has passed through a heating unit, is returned to the boiler along a direct path so that
the total distance traveled by the water is the shortest feasible, and so that there are
considerable differences in the lengths of the several circuits composing the system.
Down-Feed One-Pipe Riser (.Steam): A pipe which carries steam downward to the
heating units and into which the condensation from the heating units drain.
Down-Feed System (Steam): A steam heating system in which the supply mains are
above the level of the heating units-which they serve.
. Draft Head (Side Outlet Enclosure): The height of a gravity convector between the
bottom of the heating unit and the bottom of the air outlet opening. (Top Outlet En
closure): The height of a gravity convector between the bottom of the heating unit and
the top of the enclosure.
Drip: A pipe, or a steam trap and a pipe, consideredas a unit, which conducts con
densation from the steam side of a piping system to the water or return side of the system.
. Dry Air: In psychrometric work, dry air is defined as air without water vapor. This
state, though not obtained practically, is used as the basis of calculations.
Dry-Bulb Temperature: The temperature indicated by a standardized thermometer
after correction for radiation, etc.
Dry Return: A return pipe in a steam heating system which carries both water of
condensation and air. The dry return is above the level of the water line in the boiler
in a gravity system. (See Wet Return.)
Dust: Solid material in a finely divided state, the particles of which are large and
heavy enough to fall with increasing velocity, due to gravity in still air. . For instance,
particles of fine sand or grit, the average diameter of which is approximately 0.01 centimeter, such as are blown on a windy day, may be called dust.
Dynamic Head or Pressure: Same as Total Pressure.
Effective Temperature: An arbitrary index which combines into a single value the
effect of temperature, humidity, and movement of air on the degree of warmth or cold
felt by the human body. The numerical value is that of the temperature of still, satu
rated air which would induce an identical sensation of warmth.
Enthalpy: A thermodynamic property which serves as a measure of the quantity of thermal energy connected by a fluid in steady flow. In a non-flow process .the increase of
enthalpy equals the quantity of heat absorbed provided pressure'is constant. Enthalpy
was formerly called heat content, sometimes total heat. Specific enthalpy is the ratio of .
total enthalpy to total weight,, that is, enthalpy per unit weight of substance, Btu per pound. -
Entropy: A thermodynamic property which, for practical purposes, is-best defined by-
stating its principal functions: (1) during a reversible adiabatic change of state, entropy
is constant; (2) during a reversible isothermal change of state, the heat absorbed is equal'
to absolute temperature times change of entropy. Specific entropy is the ratio of total
entropy to total weight, that is, entropy per unit weight, Btu per degree Fahrenheit
per pound.
Equivalent Evaporation: The amount of water a boiler would evaporate, in pounds
per hour, if it received feed water at 212 F and vaporized it at the same temperature
and atmospheric pressure.
Estimated Design Load: The sum of the heat emission of the equivalent direct radia
tion to be installed plus the allowance for heat loss of the connecting piping plus the
heat requirements of any auxiliary apparatus connected with the system.
Estimated Maximum Load: The load stated -in Btu per hour or equivalent direct
radiation that has been estimated to be the greatest or maximum load that the boiler
will be called upon to carry.
..
Extended Heating Surface: See Heating Surface.
Extended Surface Heating Unit: A heating unit having a relatively large amount of
extended surface which may be integral with the core containing the heating medium or
assembled over such a core, making good thermal contact by pressure or by being
845