Document 7O3mk4pM1Q60x13ZgvYqyNwE
STEPS
STANDARD OPERATING PROCEDURE
CHECK
KEY POINTS
was done.
a phase stating so. An example of this is "operator checked at alarm time. . . " .
Every effort is to be made to check the alarm as soon as possible. If for some reason we are unable to do so it should be noted as such and a reason given.
The remainder of the response
should clearly state what was
found and what corrective action
was taken. Examples of this are:
"...found a sample coil fitting
leak and tightened it up and leak
stopped",
"...found nothing",
and "...found a leaking flange,
cleared the piping to stop the
leak and wrote it up in the maint.
log to be repaired".
8. If the response in the log book is incomplete or missing the VC_ lead man is responsible for tracking down the answers.
Write notes in the appropriate logbooks if necessary.
9. Put the completed report on the desk of the supervisor in charge of the air monitor report fiie.
r 10. The VCM-I air monitor alarms also print at VCM-II. VCM-II is responsible for checking out points 9-12 in the same manner as described above.
The findings must be noted in the storage logbook and must be communicated back to the VC-I control room to be logged onto their air monitor report.
Points: 1-8 VC loading rack 9 S-1,2 transfer pumps 10 Day tank transfer pumps 11 Piperack south of maint. 12 S-1,2 tank car ldg pumps
shop
When points 1-8 alarm, VCM-II must call the VC rack to verify their acknowledgment. On backshifts, when shipping is not loading, it is VCM-II's responsibility to check the alarm and report the findings to VC-I control room to be logged onto their air monitor report.
\v
REVISION DATE: 10/8/87
INITIALS: MJF
PAGE 2
SL 090275
VCM AIR MONITOR
STEPS
STANDARD OPERATING PROCEDURE
CHECK
KEY POINTS
1. When an air monitor alarm is received, the appropriate operator or lead operator is to go out and investigate the leak immediately.
2. Corrective action is to be taken to stop the leak if one is found.
3. The following information is to be noted in the logbook for each alarm.
a. The alarm was acknowledged and check when received or at what time it was checked out.
b. What was found.
c. What corrective action was taken to stop the leak.
4. Repeated alarms at the same point are not acceptable.
5. If the system appears to be malfunctioning contact the shift supervisor to call out the analyzer group to repair the system.
6. Pull the air monitor report after it prints out at 7am.
VC lead man la responsible.
7. Transfer the responses the alarms for each point the logbooks to the air monitor report.
to from
a. Responses are to be made in such a manner as to leave no doubt or confusion about what
1. It is yo u r respo nsi bility to inv est igate t <:orrec t. and report on any alar ms that occ ur. Our amb ien t air monitor ing records are re viewe d by the La . DEQ. To con vin ce th e m that we are handling VCM CO rrect 1 Y , our rec ords must be com pie te .
Even if nothing was found, write "nothing found".
Use the TIP or HNU to locate the leak .
If for some reason it is lost, pull the alarm point data logger for the 24 hour period 7am-7am. Alarms will appear in columns <R3 and >R3. The <R2 column is not for alarms.
Since the alarm is to be checked immediately, the response on the air monitor report should contain
REVISION DATE: 10/8/87 PAGE 1
INITIALS: MJF
SL 090276