822 CHAPTER 41 1949 Guide 6. Calculate the losses for the duct offering the greatest resistance to the flow of air, using the A.S.H.V.E. Friction Chart, Fig. 1, and the other data given in this chapter. Recommended Design Velocities The air velocities given in Table 4 have been found to give satisfactory results in engineering practice. Where the higher velocities are used, the ducts should be cross-braced to prevent breathing, buckling or vibra tion, and should be constructed of heavier gage metal. At the higher velocities it is particularly important to design the ducts for minimum resistance. As high velocities at one point offset the effect of proper design in all other parts of the system, emphasis should be placed on the impor tance of air velocities, elbow design, location of dampers, fan connections, grille and register approach connections, and similar details. For industrial Table 4. Recommended and Maximum Duct Velocities Recommended Velocities, fpm Maximum Velocities, fpm. Designation Outside Air Intakes* Heating Coils* Air Washers Suction Connections Fan Outlets Branch Risers Residences Schools, Theaters, Public Buildings Industrial Buildings Residences Schools, Theaters, Public. Buildings -Industrial Buildings 700 800 1000 800 900 1200 250 300 350 300 350 350 450 500 600 500 600 700 500 500 500 500 700 800 1000 900 1000-1600 1300-2000 1600-2400 1700 500 500 1000 1400 1500-2200 1700-2800 700-900 1000-1300 1200-1800 800-1200 1100-1600 1300-2200 600 600-900 800-1000 700-1000 800-1300 1000-1800 500 600-700 800 650-800 800-1200 1000-1600 * These velocities are for total face area,.not the net free area. buildings, noise is seldom given much consideration, and main duct veloci ties as high as 2800. or 3000 fpm are sometimes used, but when these veloci ties are used due consideration should be given to duct design,, resistance pressure, fan efficiencies and motor horsepower. . For department stores and similar buildings, 2000 to 2200 fpm are sometimes used in main, ducts where noise is not objectionable and space conditions wa.rrant.it. ... Where high velocity diffusing outlets are used, the duct velocity should be, if possible, equal or somewhat lower than the throat (neck) velocity of the diffuser, in onier to utilize the effect of higher static pressure in the duct for equalization of air discharge. The velocities in main ducts, and particularly in branch ducts and branch risers should be correlated to the throat (neck) velocity of the air outlets and manufacturers data should be consulted for permissible throat velocity' for the particular type of application. If it is necessary to use a duct velocity that is twice the velocity for an outlet mounted on the side of the duct, a collar with directing vanes should be used to straighten the flow of air from the outlet. Sometimes it is desirable to mount the outlet flush with the side of the duct in which case ;the duct velocity should be kept below twice-that of the outlet velocity, and even then an outlet larger than normally required should be used, as Air. Duct Design 823. the entire outlet area will not be effective. Manufacturer's selection tables base sizing of outlets on required volume of air, temperature differential, and distance of throw or radius of diffusion. In following their recom mendations, maxima should be avoided. See: Chapter 40 for a discussion of air outlets. DESIGN METHODS The design of the air transmission system is generally the last step, in the design of the heating,'ventilating or air conditioning system, but it should always be kept in mind that the type of air transmission used will, to some extent, depend on the type of equipment used as well as on the purpose of the system. Zoning and zone control and other-factors and their influence on the transmission and air distribution;system are briefly discussed in Chapter .43 (Central Systems for Air Conditioning) The methods used for the design of duct systems reflect, to some degree;' certain developments in the arts of heating,'ventilating and air conditioning and it took a long time before empirical methods gave way to more refined and scientific calculations. . Some engineers prefer speed and simplicity to scientific exactness, but experience is then needed and proper judgment must-be exerted to prevent' mistakes'. Both the Velocity Reduction Method and the Equal Friction Method take no account of the static regain resulting from the difference between the velocity of fan discharge and velocities of pipe discharge, and are therefore; to some degree, approximate methods' However, they are more easily applied than the static regain method which is based on scientific reasoning but is subject to an assumption regarding the efficiency of conversion from kinetic energy to. static- regain; This efficiency for ordinary expansion sections is usually.taken as 50 per cent; 1. Velocity Reduction Method When this method is used, arbitrary velocities for the various sections of the ducts are selected, with the highest velocity at the fan outlet and lower velocities down the run as various branch ducts are taken off the main duct. As the quantities of air that are to be delivered through each section of the duct are known, the area of each duct section can be easily deter mined by using the formula: ~. where A = duct area in square-feet. Q = air quantity in cubic feet per minute. Vm = air velocity in feet per minute. To find the total static pressure against which the fan must operate the static pressure loss of each section is calculated separately' and the total loss found by adding the individual losses of the sections of the duct which has the highest resistance. This may be the duct with the longest run, but not necessarily iso. The velocity method has the advantage that the duct area can be deter mined very easily. It should be used only for simple layouts. The air velocities given earlier in this chapter are helpful in choosing proper velocities. Balancingis obtained by use of dampers.