FROM (LOCATION) C.R. COLEMAN - RUABON.
DATE : 10th June, 1971.
SUBJECT : Aroclor 1016 Specifications.
REFERENCE
:
TO :
CRC/bj o'g.
R.H. MUNCH - TECHNOLOGY DEPT., SOUTH 2ND ST. LOUIS.
CC: J\R, W.R. Richard, St. Louis.' R. McCutchan - WOK. D.R. Cova, St. Louis. . O. DeGarmo, St. Louis. P.G. Benignus, St. Louis. J. Fallon, St. Louis. R. Kuster, St. Louis. R.A. Baxter/H.A. Vodden, Ruaber A.F. Regan, Newport. ' F. MacDonald, Newport. P.J.A. Marsh, Brussels. J. Durland, Tokyo. D. Danna, St. Louis.
With regard to your nemo of 1st June on this subject, I would like to see the following additional properties specified:-
1) Density at 20C. 2) Viscosity at 20C (in centistokes). 3) Refractive index at 20C.
The first two of these properties are those usually specified in Europe for the less viscous askarels, and the third follows IEC_ __ recommendations for refractive index.
For Aroclor 1242 made at Newport the appropriate values are:-
Property 1) Density at 20C(kg/m3) ' 2) Viscosity at 20C (cSt) 3) Refractive Index at 20C
Value I38O to 1390 ' 55 to 71 1.6250 to 1.6270
Method ISO R649 and ASTM D1810
ASTM D445 ASTM DI8O7
In addition, it will be necessary for us in Europe to specify dielectric constant (or relative permittivity) and power (or dissipation) factor at 50Hz instead of 60Hz, since 50Hz is the commercial frequency in Europe. The value of the dielectric constant will remain unchanged by this change in frequency, but for a given sample we might expect the dissipation factor to be 1.2 times higher. In practice, however, this, difference could easily be swamped by sampling and testing errors.
In conclusion, I would like to point out that the IEC has recommended that permittivity, dissipation factor and resistivity be measured at a temperature of 90C instead of 100C which is current practice in the USA and UK. The values set by the IEC for Capacitor Askarel Type ClA (our Aroclor 1242) are as follows:
DSW 329243
STLCOPCB4075951
)
-2
Property. Volume resistivity at 90C (TO cm) Dissipation factor at 90C, 50-GOHz Permittivity at 90C, 50-6QHz
Value 1 (minimum) 0.02 (maximum) 4.8 to 5.1
The agreed test methods for these electrical properties are still to be finalized.
- At the present time, I believe that in Europe we should retain the temperature of 100C for measuring resistivity and dissipation factor whilst attaining the values given above, a slightly harder task. We should also keep 100C for the measurement of permittivity and apply a correction factor if customers insist on this value at 90C. I have taken this different attitude for the electrical properties compared with that for the physical properties because there is a fairly equal division between 90C and 100C among our customers whereas there is an overwhelming preference for 20C for measuring.the density and viscosity of Aroclor 1242 and the transformer askarels.
COLIN R. COLEMAN.