Document 72rrB3wMq9mqwZR113nNZM7g
214
CHAPTER 15
1959 Guide
method of rating is subject to error from differences in types and calibration of instruments, grille design, and the care with which the rating test is conducted. Because of this, the standard air rating is used by manufacturers to rate unit ventilators.
Table 1 shows the air delivery capacities by the two methods of rating and the approximate room heating equiv alent in square feet of direct radiation (EDR) of an inter mediate size of beating element. Heating elements are avail able for higher and lower capacities.
Heating Capacity Requirements for Unit Ven tilators
Since a unit ventilator has the dual function of introducing outdoor air for ventilation and maintaining a specified room temperature, the heat required by the unit may be similarly divided into (1) heat required for ventilation H. and (2) surplus heat H,. The surplus heat is available for main taining room temperature. If auxiliary radiation is installed, the surplus heat requirement may be reduced by a corre sponding amount. The sum of H, and H. is the total heat Hi to be supplied by the-unit ventilator.
These quantities of heat are related by the following equations:
H, = 0.24 W (t - f.) H, = 0.24 W , - t.)
(1) (2)
H, - H,~ J7. = 0.24 IF 01, - 0
(3)'
W - d60Q H, - H, + 0.24 d 60 Q (t - t.)
(4) (5)
Fig. 3 .... Typical Ceiling-Mounted Unit Ventilator
where
d = density of air, pounds per cubic foot (0.075 lb per cu ft for Standard Air by definition).
H, *= surplus heat, Btu per hour. H, = heat required to warm air for ventilation, Btu per
hour. H, = total .'heat requirements for both heating and ven
tilation, Btu per hour. Q TM volume of air handled by the ventilating equipment,
cubic feet per minute. . I " temperature to be maintained in the room, Fahren-
' heit t, -- outdoor temperature, Fahrenheit. .1/ " temperature of the air leaving the unit, Fahrenheit. W " weight of air circulated, pounds per hour. 0.24 -- specific heat of air at constant pressure (approximate
value).
Example 1: The heat los of a certain room is 24,000 Btu'per hour, and the ventilating requirements are 1000 cfm. If the ropm temperature is to be 70 F and all air is taken from the outdoors at OF, what will be the total heat demand on the unit if it is required to provide for both the heating and venti lating requirements (combined system)?
Solution: Since the surplus heat is available to replace the heat loss of the room,
H, * 24,000 Btu per hour.
Substituting in Equation 5:
H, = 24,000 + 0.24 X 0.075 X 60 X 1000 (70 - 0)
= 09,600 Btu per hour
__________ 24^00 .
b
+ 70 0.24 X 0.075 X 60 X 1000
92.2 F
Fig. 2____Typical Floor-Mounted Unit Ventilator-- Blow-Through Type
Horizontal Position
Unit Ventilators and Unit Heaters
215
Table 1 ....Typical Capacities of Unit Ventilators for an Entering Air Temperature of 0 F
Cubic feet of oir per minute
Anemom
eter roting
Standard air rating
750 500
1000 1260 1560
750 . 1000
1250
total capacity in square foot,
equivalent direct radiation
214 320 427 534
Capacity available
for booting the Final oir
room, tqoore foot temperature
equivalent diroot
F
radiation
56 95 84 95 112 95 141 95
If iq Example 1 & 1000 cfm (Standard Air) unit were required, but only 25 percent of the air introduced were outdoor air, the solution is:
H, =. 24,000 + 0.24 X 0.075 X 60 X 0.25 X 1000 (70 - 0)
---- * _--- + , :24 00
= 42,900 0,^.2
0.24 X 0.075 X 60 X 1000
The only difference from Example 1 is that theyentilation load has been reduced.
Heating Capacity Ratings
Heating capacity ratings for steam unit ventilators are obtained in accordance with the ASHAE Standard Code for Testing and Rating Steam Unit Ventilators.' Under this code the capacities are established for varying air entering temperatures in addition, to .the standard rating. Capacity ratings include the entering air temperature, the total heat ing capacity, the surplus or heating capacity, and .the final air temperature.
Hot water unit ventilators have heating capacity ratingsbased on various entering water temperatures, flow rates or temperature drops, and entering air temperatures.
Gas-fired unit ventilators have beating capacity ratings obtained in accordance with regulations established by the American Gas Association. Heating capacities include the total heat input and the total heat output, in Btu per hour, for various entering air temperatures.
Electric unit ventilators have heating capacity ratings based on the heat input to the electric heating element, in kilowatts or Btu per hour.
The air capacities of hot water, gas-fired, and electric unit ventilators are obtained in accordance with the ASHAE Standard Code for Testing and Rating Steam Unit Venti lators.1
Applications of Unit Ventilators
Items to be considered in the application of unit venti-.
lators are: (1) unit air capacity, (2) percent minimum out
door air, (3) heating capacity, (4) cycle of control, and '
(5) location of unit.
The primary considerations in the selection of the unit air
capacity are the mild weather cooling capacity and the
number of occupants in the space. Other factors to be con
sidered are state and local code requirements, volume of the
room, density of occupancy, and the usage of the room. A
safe rule for determining unit air capacity is to allow a total
air quantity of 30 cfm per person, or six to nine room air
changes, per hour, whichever is greater. With this quantity of
air handled, it is posable to obtain satisfactory cooling in mild weather. Table 2 gives.recommended room volume cir culation rates for different types of spaces served. For rooms facing East, South or West, higher values should be used.
The minimum amount of outdoor air for ventilation is determined after the total air capacity has been established. It may be governed by state or local codes or may be cal culated by the engineer to meet the ventilating air needs, of the particular application.
The heating capacity of a unit to meet the beating require ment can be determined from manufacturers tables. Selec' tion of heating capacity should always be made after deter mining the basic size of unit by selecting the unit air capacity.
Automatic Control of Unit Ventilators
Many different cycles of control are available. The principle'difference in the various cycles pertains to the amount of outdoor air delivered to the room during normal periods of occupancy. Usually a room thermostat controls both a valve to regulate the heat supply and a damper to regulate the' supply of outdoor air. An air-stream thermostat in the unit prevents the discharge of air below the desired minimum temperature. Unit ventilator control cycles provide the proper sequence for the following stages:
Warm-up Stage. Ail control cycles function to provide rapid warm-up by having the units provide full heat with the outdoor damper closed. Thus 100 percent room air is recirculated and heated , until the room temperature ap proaches the desired temperature level.
Heating and Ventilating Stage. As the room temperature rises into the operating range of the thermostat, ventilation is accomplished by the partial or complete opening of the outdoor air damper according to the cycle used. Auxiliary heating equipment is shut off. As the room temperature continues to rise the unit ventilator heat supply is throttled.
Cooling and Ventilating Stage. When the room temper ature rises above the normal level, cool air is discharged into the room. The room thermostat accomplishes this by throt tling the heat supply, finally shutting it off, and opening the outdoor air damper to prevent overheating of the room. The air stream thermostat frequently takes control during this stage to prevent the discharge temperature from falling below a set level.
The three basic cycles of control commonly used are as follows:
Cycle X. 100 percent of outdoor air is admitted at all times except during the warm-up stage.
Table 2.... Recommended Outdoor Air Capacities for Mild Weather Cooling
For North Exposure
Type of tpace
J .. ^
Recommended ootdoor air delivery--room
volume* per hour
Classrooms Laboratories, Forge Shops MetaJ Working Shops Offices Card Rooms, Lodges Private Offices Cafeterias & Kitchens
6-9 1 6-8 ' 6-8
6-8 6-9 6-9 4H-7