LOSS PREVENTION SURVEY
CONFIDENTIAL This report should be made available only to authorized persona.
veniew
B. F. GOODRICH COMPANY TIDAL ROAD 3/4 MILE NORTH OF HWY. 225 DEER PARK, HARRIS, CO., TX 77536
BY: A.K. Godso
DATE: Dec. 13, 1989
LOC.ID: 800083/860854 HRS: 7
CONFERRED WITH: Mr. B. DesJardins, Safety
Engineer
RECOMMENDATION
NEW*: None
UPDATE
COMPLETED: None
(89-0)
RECOMMENDATIONS
85-1
FIRE PUMPS: Provide two automatic horizontal centrifugal fire pumps, diesel engine driven each rated at 2,500 gpm at a pressure of 125 psi, and arranged in accordance with NFPA Standard No. 20 to take suction from reservoir containing 1,200,000 gallons. The pumps should be provided with control panels and the following additional features: (No plans to comply. Oxychem is upgrading its water supply system by replacing the 40 plus year old firemain) RSVP* PLANS**
a. A detached noncombustible pump house heated to maintain it above 40 deg. F and equipped with emergency lighting.
b. A standard pump test header equipped with 8 hose valves in accordance with NFPA Standard No. 20.
c. The reservoir should be split into two equal sections and arranged so that either pump can take suction from either side.
d. Eight "Underwriters" playpipes with 1-1/8 in. and 1-3/4 in. tips for test purposes.
85-2
PROTECTIVE SIGNALING: Extend the proprietary signaling system to include deluge system waterflow and halon extinguishing system trips. (To comply. Project has been approved and is in early engineering stage. Presently, alarms go to a panel in the Operations Building which isn't constantly attended.) RSVP* PLANS**
85-3
PCB TRANSFORMER: Replace the unit(s) located along the east side of the Main Substation with equipment that meets or exceeds the requirements of the
BFG50838
RMPRQT
PEP
ws
8 8 9 5P
SUPR FD
2F 2G
HPS
00
PCB
3010
%AS
52
%ASN
5
CNST1 CNST2
18 82
_____
CNST3 CNST4
00
occ
This survey is made for properly insurance purposes only and is based upon conditions and practices observed and information made available ai the time ofthis review. It does not purport to list all hazards
nor to indicate that other hazards do not exist. No responsibility is assumed for the control or correction ofconditions or practices existing at the insured premises IHI specifically disclaims any warranty or
representation that compliance with any advice contained herein will make arvypremistt or operations stiff nr healthful, or in compliance with any law. rule, or regulation Ifthere are any questions cencernmf the recommendations or you hare alternate solutions, please contact us.
B. F. GOODRICH COMPANY
2
800083/860854
85-3
(Continued)
National Electrical Code for installations of Less-Flammable Liquid-Insulated Transformers. (To comply by second quarter of 1990)
85-7
FIREPROOFING: (Revised 5/2/88) Provide fireproofing for the pipe rack supports in the following areas using material having a 2 1/2 hour fire resistance rating per UL 1709. The protection should extend to Include the vertical and horizontal members of the first level of pipe racks. Details of the installation should be determined in consultation with the local IRI District Office. (No plans to comply)
d. Along the east and south sides of the VCM charge pumps which are located south of the reclaimed VCM bullets.
IN LIEU OF THE ABOVE
AUTOMATIC SPRINKLERS: Provide a deluge system to protect all levels of pipe rack supports designed to provide 0.25 gpm/ft* (10.2 L/mim/nr) over the protected area. RSVP* PLANS**
AND
FIREPROOFING: Provide fireproofing for the areas mentioned in items a through d using material having a 1 1/2 hour fire resistance rating by UL 1709. The protection should extend to include the vertical and horizontal members of the first level of pipe racks. Details of the installation should be determined in consultation with the local IRI District Office.
87-1
YARD MAINS: Perform a hydrostatic test of the fire protection mains at a pressure of 150 psi (10.35 bars) for two hours. (To do by second quarter of 1990)
SIGNIFICANT CHANGES
The Occidental Petroleum facility (920053/860854), currently supplying the fire water supply to the insured, has begun a three phase project to provide an independent fire water system. The existing process/fire water system will be used solely as process water system after the independent fire water system is installed. So far, approximately 4000 ft (1220 m) of new mains have been installed at Occidental with a tie-in to 8.F. Goodrich's system expected the first quarter of 1990.
A new blowdown tank will be installed north of the reactor structure in 1990. No details were available.
The corroding sprinkler system in the cooling tower was replaced with a new system identical to the previously existing system.
MMW/2223V
BFG50839 -412003
B. F. GOODRICH COMPANY
3
800083/860854
COMMENTS
RSVP*:
The completion of this recommendation will involve an impairment of your fire protection. Please notify the IRI's Houston Office, 1225 North Loop West, Suite 927, Houston, TX 77008, (713) 868-5814 at least 48 hours before starting this work.
PLANS**:
Completion of this recommendation requires the review and acceptance of detailed working drawings and necessary supporting calculations. All fire protection equipment should be listed by a recognized testing laboratory. All installations should be designed in accordance with
applicable NFPA Standards unless modified by an IRI interpretation guide. Duplicate sets of drawings and specifications should be sent to IRI's Houston Office, 1225 North Loop West, Suite 927, Houston, TX 77008 for review. IRI's acceptance should be secured
before construction or installation begins.
Mr. Richard Kitchen has been requested to submit information regarding various boiler & machinery objects. Due to limited manpower, this information was not available during this survey; instead, It will be available by the first quarter of 1990.
MMW/2223V
BFG50840 26412004
RISK; B.F. Goodrich Company
LOC ID: 800083/860854
VJATER SUPPLIES & TEST RESULTS
SUPPLY DESCRIPTIONSGPM
FLOW LQC
STAT RESD
RESD LQC
DATE
1-10" conn to 1-10" private main at east side of Pit
6326
The VCM sphere deluge system, the VCM reel aim tanks deluge system and four 2-1/2" off hydrants 1 & 57
62
55
VCM deluge valve
6/16/87 DL
1-14" conn to 1-14" private main at NW side of Pit
1061* Monitors north 55 43 of reactor structure
Deluge valve 11/14/88 for East Reactor
1-14" conn to 1-14" private main at SW side of Pit
3973
VCM sphere & 100 reclaim tank deluge systems & monitors in the area
65
Hydt. off PIV No. 151
1-6" conn to 1-10" private main at Office Building
Note:
Private mains connect to the Occidental combination service/fire protection water system. 4 Electric service pumps (approximately 4000 gpm, 70 psi) with a 200,000 gal. reservoir.
*No pumps kicked on.
7/13/89 DL
PUMP RATING
AUTO/
CHURN
DISC
SUCT
GPM/PSI
DRIVE MAN SUCTION SOURCE PSI GPM PSI RPM PSI COND
DATF
2500/100 2500/100
2500/100
1500/100
# 4 Die. Auto 1,000,000 gal. #3 Die. Auto Abvgrd tank
#2 El ec. Auto #1 Die. Man
200,000 gal. Abvgrd. tank
ic
125 2500 100 125 2500 100
109 3820 80 ?
15 -3
108 1269 92 1800 2
Good Good
Good
Fair
9/87 PDF & DVJ
7/21/87 DL
12/2/79 JRD
These pumps are the Occidental fire protection system
N20C Rev. 8/82
MMW/2223V
BFG50841