Document 70p5RV4k4jqxnbZ4QZ8DEQKyR
PYROCLOR FOR TRANSFORMERS
TOWOLDMON0024085 WATER_PCB-00008554
PYROCLOR
j
FOR TRANSFORMERS
MONSANTO NOOSE, 10-11 VICTORIA STREET, LONDON SW1
HONS 0733-.0
^
TOWOLDMON0024087 WATER_PCB-00008556
CONTENTS
INTRODUCTION Advantages of Pyroclor Transformers Applications of Pyroclor Transformers
PROPERTIES Composition Physical Properties:
viscosity Solubility of Water Vapour Pressure Air Absorption Chemical Properties: Fire Resistance Thermal Stability and Effect of Arcing Resistance to Oxidation Stability to Hydrolj'sis Dielectric Properties: Dielectric Strength Permittivity Power Factor DC ReBtstlvtty
DEMON OF PYROCLOR TRANSFORMERS Compatibility of Materials Reduction In Volume Soaled Transformers Unsealed Transformers Tap Chauffer Terminals Tank and Lifting Lugs
FILLINO PYROCLOR TRANSFORMERS
MAINTENANCE Sealed Transformers Unsealed Transformers
TOXICITY AND HANDLING PRECAUTIONS
APPENDIX
3 3 4
s 0 6 ti 0 6 a 6 6 6 7 7 7 7 8 8 8
n 17 17 17 18 18 18 18
10
is 19 19
21
22
MONS 073341
|
TOWOLDMON0024088 WATER_PCB-00008557
INTRODUCTION
Pyroclor is the transformer aekarel made by Monsanto. (Aakax-ela are non-flammable insulating liquids which, if decomposed tiy an electric arc, evolve only non-explosive gaseous mixtures). Monsanto has been producing askarels In the U.S. since 1932, and in the U.K. since 1951 under the name Pyroclor.
This booklet describes the characteristics of askarels, particularly how they differ from mineral oil, and gives information on the design and operation of askarei transformers. This information Is baaed on facts gathered by Monsanto from the knowledge and experience of transformer manufacturers and users over three decades.
MvMtagtB
Pyratriat Tptllfsfaif* For siting indoors, Pyroclor transformers have considerable advan
tages over other types of transformer.
1 Pyroclor transformers provide the cheapest way of obtaining a flroproof Installation. The use of Are Aghting equipment. Are walls, and pebble drains is unnecessary.
2 Pyroclor transformers are particularly suitable in many applica tions where fire risk is great and space 1b limited, such as near furnaceo. and, as in the United States and on the Continent, in coal mines.
3 Pyroclor transformers can be used In dusty and dirty atmospheres without extra protection or frequent outages for maintenance.
4 Pyroclor transformers can be used in installations where over voltages due to lightening or switching surges are prevalent.
5 Pyroclor transformers are quiet in operation.
0 Since Pyroclor transformers can be Installed at the load centre, ex pensive low voltage cable runs are reduced and voltage regulation is improved.
7 The stability of Pyroclor means that it can last at least as long as 30 years even If overloads cause the rated temperature lo be exceeded.
MQNS 073342
:j
TOWOLDMON0024089 WATER_PCB-00008558
8 Pyroclor transformer installations permit the Are insurance pre miums to be reduced in some coimcries.
9 Pyroclor transformers can operate at voltages as high as 120 kV.
Applloatlon of Pyrooior Transformers Pyroclor transformers have been used In a very wide range of appli cations and recent examples include installations In steel works, glass factories, public buildings, storas, and offices. The tendency now for buildings to be taller favours the positioning of aub-Btations on the top storeys of buildings, and in a recent example Pyroclor transformers were installed on the 42nd floor of a building In Montreal.
The mining industry employs ask&rel transformers in America and in France, and elsewhere they have been Installed at the load centre In mine winding gear, which Is situated over the mine shaft itself.
Askarel transformers are also widely used on electrified railways. On some U.S. railways, where aekarel transformers have been used satisfactorily since 1933, the transformers are located below the floor on the Multiple-unit cars. Underground railways in a number of cities have also installed askarel transformers In their distribution system.
Other recommended applications Include electric furnaces, Infra red ovens, oil refineries and ships.
Monsanto itself has some 10 Pyroclor transformers Installed at its various plants. These have so far given satisfactory service for vari ous periods up to 6 years.
Properly designed and installed askarel transformers will give trouble-free service for a minimum of 30 years. Since their introduc tion in 1932, the manufacturers report finding the overall failure rate to be less than 0.5 per cent for all units under test and service condi tions. The Edison Electrical Institute's report on thelrraember utili ties publishes the failure rate for askarel transformers as 0.13 per hundred banks per year. Even the raro reports of failure are invari ably found to be due to Improper sealing, which allows moisture to enter.
Askarel transformers working at 120 kV have been made, but most work in the region of 11 kV. Units are in service with ratings up to 30 MVA, although since they are normally employed only indoors, the majority are found in the range between 50 KVA and 1.5 MVA.
4
MCWS 073343
^
TOWOLDMON0024090 WATER_PCB-00008559
PROPERTIES
Pyroclor was developed for normal operation under class A condi tions. An alternative askarel, Pyroclor ETR, has been developed for operation under class B conditions.
The most important properties of Pyroclor and Pyroclor ETR are shown In the table.
OtmpMltion Pyroclor is composed of 40% trichlorobenzene and 50% hexachiorodiphenyl by weight, with 0.125% of gras scavenger. Pyroclor ETR is entirely tetrachlorodlphenyl with the same concentration of gas scavenger.
Typical properties of Pyrcelsr asp Pyrtoler ETR
(TJieM value) do not constitute a specification)
Property
Pyroclor
Pyroclor ETR
Description
Viscosity at V0*C (efl) Pour Polnt<*C) Relative Density at 16.5/15.6*0 Coefficient ofexpanslon/der C SpeolAo Heat et78*C (Jlg dee C) Thermal Conductivity at 75'C (W/mdef C) Evaporation toaa (per osnt)
Fire Point Refreotlve index n" Inorganic chlorides (ppm) Acid number tmg KOH/j) Watercontent (ppm) Dielectric Strength at X'C by B.S. 148:1968UV) DC Resistivity at 100*0 aad 500V/mm after l minute electrification (o cm) Lose tangent 100`Cand 50 c/e Permittivity at lOQ'C and SO c/a
Liquid which, at room temperature, may contain crystals 2.9 --32 or lower 1.564 oooorr 1.3
coloured, viscous liquid
5.8 -7 1 481 0.00070 1 18
0.107 3.6 (6 hat 100*0 None l 8148 0.1 max. o.oi max. 20 max
0.1003 0.07 (2 hat 126*0 None 1.6296 o.l max. 0.01 max. 30 max.
40 min.
40 min.
i.Ox iu,amin. 0.03 max. 3.9
1.0s I0"mln. 0 03 max. 4.6
5
MOISS 073344
TOWOLDMON0024091 WATER_PCB-00008560
Physical properties Viscosity The ratio of trichlorobenzene to hcxachlorodlphejiyi In Pyroclor has been selected to matcli the viscosity-temperature characteristic of mineral oil. Figure 1 illustrates the similarity.
Solubility of Water Figure 2 shows that water is slightly more soluble in clean Pyroclor than in mineral oil. but there is very little change in the solubility between new and used Pyroclor, as can be seen from the graph.
Vapour Pressure The variation of the vapour pressure of Pyroclor and Pyroclor ETR with temperature is 3hown in Figure 3.
Air Absorption The amount of gas dissolved in a liquid may be ex pressed as a Bunsen coefficient, that is, the volume of gas at NTP dissolved in unit volume of a liquid at a partial pressure of 760 torr. The Bunsen coefficients for the solution of air in Pyroclor and Pyro clor ETR are shown in Figure 4.
GtltlRlOAl properties The chemical Inertness of Pyroclor is outstanding and in particular it has excellent fire resistance, thermal stability and resistance to oxidation and hydrolysis.
Fire Resistance Although Pyroclor will be shown to have a flash point when examined by the usual laboratory tests, this flash burns with a 'cold' flame and no fire is carried back to the liquid phase, therefore there Is no corresponding fire point. The autogenous ignition tomperature of Pyroclor has been measured by dropping small quanti ties of the liquid on to the floor of a ceramic lined muffle furnace. The liquid did not take Are until the surface was a dull red heat, approxi mately 700C. Once the liquid, however, leaves such a hot surface it ceases to burn and it is therefore impossible to convey Are by moving streams of liquid. The laboratory of the National Board of Under writers (U.S.A.)have carried out stringent tests on the Are resistance Of this type of liquid and have concluded that It Is essentially non flammable.
Thermal Stability and Effect of Arcing Pyroclor undergoes no thermal decomposition whatsoever at temperatures below 176aC. If Pyroclor Is raised above this temperature by, for example, local over-heating or transient arcing, small quantities of hydrogen chloride are pro duced. The gas scavenger, absorbs this hydrogen chloride and pre vents attack on the iron core or the cellulosic insulation.
If a major Internal fault occurs in a Pyroclor transformer which results In a sustained arc below the Pyroclor surface, then the high temperature of the arc will decompose the Pyroclor. The main de
G *ONS 073345
TOWOLDMON0024092 WATER_PCB-00008561
composition products are carbon and hydrogen chloride. Hydrogen chJoride Is non-flammable and will not form exploeive mixtures wi tii air, but la an unpleasant and Irritating1 gas r.o breathe. However, it is easily detected in the atmosphere and exposure to low concentra tions would produce no lasting 111-effects. Since It Is very readily soluble in water, it is likely to bo removed rapidly from thu atmo sphere under most normal circumstances. Hydrogen chloride does not quench the arc that produces it, and consequently the circuit breakers should be capable of Interrupting the probable fault cur rent, For the same reason, Pyroelor Is unsuitable for switchgear. The amount of gas that Is produced by an arc in Pyroelor will vary according to the circumstances, but a figure quoted is 135 cm' per kWs.
Laboratory tests and practical experience have shown that phosgene ami chlorine are not formed as decomposition products ofasharcl.
Resistance to Oxidation Pyroelor has exceptionally good resistance to attack by oxygen. When subjected to a bomb test at lio C in oxygen at a pressure of 250 pslg. (17 kg/cm*; there was no evidence of oxidation aa Judged by development of acidity or the formation of sludge. Hot mineral oiJ in the presence of oxygen undergoes a aeries of complex chemical reactions, producing by stages, peroxides, acids, water and other condensation products which eventually form a sludge.
Stability to Hydrolysis Pyroelor is resistant to attack by water, although water will dissolve In Pyroelor and the presence of this mixture will naturally affect the electrical properties. In an experi ment, Pyroelor was refluxed with water and oxygen was passed through the mixture and at the end of the experiment no free clilorides wore generated, even after extending the time over a con siderable period. A further experiment was conducted whereby the liquid was scaled in a gloss capsulo with water and boated for many hours at 150"C, and once again no chloride formation could be detected.
DltltOtrle properties Although a transformer liquid is principally a coolant. It must also act a8 an insulation in and between the windings of the transformer, and the dielectric properties are therefore of great importance.
Dielectric Strength The dielectric strength of Pyroelor is equal to the best quality mineral oil and has the dielectric qualities required for the voltage stresses encountered In transformers over the entire temperature range of operation. Figure 5 shows the variation of tho dielectric strength of Pyroelor (measured according to 3.S. 148:1959) with temperature.
7
HONS 073346
^
TOWOLDMON0024093 WATER_PCB-00008562
At low temperatures the gas scavenger has a tendency to crystallise and exhaustive teats have shown that even with samples of Pyroclor containing large quantities of suspended crystals, the dielectric strength of the liquid is not affected and there Is no alignment of the crystals between the electrodes.
Permittivity The permittivity of Pyroclor Is much closer to the per mittivity of cellulose and this leads to a greater uniformity of stress in impregnated press board. The variation in the permittivity of Pyroclor at 50 c/s Is shown in Figure 6.
Loss Tangent The variation of the loss tangent at 50 c/a of new Py roclor with temperature is shown In Figure 7. Satisfactory Pyroclor in a transformer may be oxpoobod bo have considerably higher low tangent than new material. In the range 0.2 to 0.8 at 100 C.
D.C. Resistivity The variation of the d.c. resistivity of now Pyroclor with temperature la shown in Figure 8. These readings were made one minute after tho application of a stress of 500 V.'mm. Satis factory Pyroclor sampled from a transformer may have a d.c. resistivity as low as 2.5 x 10'*n cm. at 100 C.
D.O. Resistivity of Pyroclor ia thus seen to be much lower than that of mineral oil by comparison. This inevitably leads to lower insula tion resistance on finished transformers filled with Pyroclor than on their counterparts filled with oil. This is. however, quite normal and is an accepted characteristic of Pyroclor transformers.
MChS 073347
TOWOLDMON0024094 WATER_PCB-00008563
KINEMATIC VISCOSITY ( c l)
TOWOLDMON0024095 WATER_PCB-00008564
Finn 2 Till salability at watar In Pyralar and na* mlnaral all.
10
NGNS 073349
|
l
TOWOLDMON0024096 WATER_PCB-00008565
Finn I Till aarlatlaa af tha vapaar praalura with tamparatura of Fjraclor an* Ppraalar ETR.
11 MOMS 073350 i
TOWOLDMON0024097 WATER_PCB-00008566
>0 NSf N COIFFICiCNT
Figura 4 ffca air abaarptlon of Pyraolor and Pyrovfor ETR. 12
. MCNS 033351
TOWOLDMON0024098 WATER_PCB-00008567
DIELECTRIC STRENGTH (kV )
w
Figaro 9 IN nriatliB of tho dlolootrlo strength of Pyroolor with tomporaturo. HONS Q7335Z
13
TOWOLDMON0024099 WATER_PCB-00008568
PCIM ITTIVITY
Hurt I Tit rariatloa tf tin parmittlrity if Prraelar wltl tamparatara. 14
MOMS 073353
^
TOWOLDMON0024100 WATER_PCB-00008569
Flfuro T Tho nrlatlm of the low tangent of oaw Pyroslor witli tomoorotoro. HONS 073354
15
^
TOWOLDMON0024101 WATER_PCB-00008570
ISO-
I
Figure Thu variation af tho d.e. realithrlty of now Pyrooltr with tamporetare. MCNS 073355
TOWOLDMON0024102 WATER_PCB-00008571
DESIGN OF PYROCLOR TRANSFORMERS
Compatibility of materials Since Pyroclor is a mixture of chlorinated hydrocarbons, it is a plasticizer for a variety of resins and plastics normally used in l lie construction of mineral oil transformers. If any of these materials are polar, they ionise to a greater extent in Pyroclor than in mineral oil because of the greater permittivity of Pyroclor and so Increase the dielectric losses more. For these reasons special attention must be given to the selection of materials which will be suitable for use with Pyroclor.
Pyroclor is a more searching liquid than mineral oil. so we do not reemnwcjid that the oil filling of existing transformers be replaced by Pyroclor as this would be very likely to cause extensive leaking and. in ninny cases, a breakdown due to the attack on insulating materials.
A very large number of materials has been examined for their anil ability for use with Pyroolor. and lists of tested materials art) avail able. Further information can be obtained from Monsanto.
Reduotlaa in valume For successful transformer design using Pyroclor it is desirable to keep the liquid volume to a minimum because it is more costly than oil. Even without radical re-design, useful economies can be made by rounding the corners of the tank or by using tanks with cruciform shape. Considerable economy can be made by Ailing dead space with wood or even glass marbleB. The wood, however, must be of low resin content and must be thoroughly dried. In addition, cooling tubes having oval or star-shaped cross-sections can be used to cut the volume.
Bald transformers Transformers using Pyroclor are normally hermetically sealed. since a* Pyroclor transformers do not require any maintenance, possible Ingress of moisture is eliminated. Welded tank designs have become popular with Pyroclor transformers. Another special fea ture with hermetically sealed Pyroclor transformers 1b the so-called `top hat' type of construction with an air or nitrogen tilled spru e
MOMS 073356
^
TOWOLDMON0024103 WATER_PCB-00008572
which Is used to allow for expansion of the fluid. The sealing- ia fre quently so arranged that the gas is under a slight negative pressure when cold. With hermetically sealed units it is customary to maite provision for a rupturable relief diaphragm which can be vented in the outside atmosphere
Unsealed transformers Pyroclor transformers fitted with breathers are also made. The breather should be fitted with a silica gel moisture trap to prevent ingress of moisture with expansion and contraction following heat cycles of the transformer. The conservator is recommended with breather designs, since at maximum operating temperatures the trichlorobonzene present has a relatively high vapour pressure ami the conservator will prevent losses by evaporation. An alternative is to fit the breather on to the end of a section of vertical tube which will act as an air condenser for the Pyroclor vapour. If a Bucholz relay U fitted, it should be suitable for use with Pyroclor.
Tap ohangar Since Pyroclor is unsuitable for switchgear, on-load tap changing below the liquid surface is not adopted. It is usual to incorporate soma form of interlock to prevent this.
Tirminall Because water floatB on the surface of Pyroclor, the terminal con nections should preferably be brought through the side walls of flutank, below the surface. If connections have to pass through the liquid surface, they should be encased in suitable sleeving to preven i; tho possibility of a flashover arising from surface moisture.
Tank and lifting luga Since Pyroclor is nearly twice as dense os mineral oil. these items must be sufficiently robust.
FILLING PYROCLOR TRANSFORMERS
Pyroclor as received, either in drums or in bulk, is ready for filling the transformer directly. Care should be taken to carry out the fill ing as quickly as possible Indoors, and days when the humidity ia high should be avoided. If the drums have been exposed to low tem-
18
MCNS 073357
^
TOWOLDMON0024104 WATER_PCB-00008573
peraturea, the gras scavenger may have crystallised, but this will rydissolve when the temperature of the transformer rises, so it la only necessary to agitate the drums to ensure that the crystals are washed into the tank. Alternatively, the crystals may be re-dissolved by pre-heating the drums to approximately 50 'C.
Vacuum impregnation of transformer windings can be carried cut with Pyroclor, but unless precautions are taken the volatile tri chLorobenzene is likely to escape. This can be avoided by using a trap in the vacuum line or alternatively the viscosity of the Pyroclor can be brought back to normal after the impregnation process by addl re fresh trichlorobenzene.
A table for converting volumes to weights Is given In the Appendix,
MAINTENANCE
SMlfttf transformers A properly designed sealed Pyroclor transformer requires no maintenance.
Unfilled triMfermer! Pyroclor and oil are two different chemical substances and the condltion of Pyroclor should be Judged only on the basis of dielectric strength, appearance and water content. High loss tangent and low d.c. resistivity in used Pyroclor is to be expected: thesn values are not an indication of chemical or electrical breakdown.
New Pyroclor has a minimum dielectric strength of 40 kV at 25 C, and a maximum moisture content of30ppm. If the dielectric strength decreases significantly this Indicates moisture pick-up, arcing or both. 'When the dielectric strength has fallenbelow40kV, an analysis for water in necessary. If water is found in excess of 100 ppm. Its source should bo located and corrections made.
When the moisture content approaches 125 ppm (saturation level) the dielectric strength of Pyroclor drops below the value required for efficient insulating, The moisture content should not be allowed to rise over 70 ppm; it should be held as near as possible to 30 ppm. Maintaining a low moisture level will ensure high dielectric strength and top operating efficiency.
MONS 073358
in
TOWOLDMON0024105 WATER_PCB-00008574
The colour of used Pyrocior Is a useful guide to its condition. In a properly designed transformer lire Pyrocior retains i ts original pale straw colour throughout Its life. A blue, green, or red cast shows that extraction from the other internal materials Is occurring, but this is not necessarily a hazard unless the dielectric strength also falls, or this phenomenon is accompanied by leakage. If the Pyrocior is dark brown or black, and if black particles of carbon are Been and the dielectric strength is low, then arcing has been occurring and immediate action must be taken. The development of turbidity indicates contamination from water, insulation particles, metallic dust, or dirt. Care must be taken, however, to distinguish this from the precipitation of the scavenger that occurs at low temperatures. High dielectric strength indicates that any turbidity present is not water, and that the insulating efficiency of the Pyrocior is still excellent.
Mineral oil la soluble In Pyrocior and any contamination of the Pyrocior by oil will reduce Its fire resistance. A maximum hydro carbon oontent of 2% by volume can be tolerated, however, but it is recommended that Pyrocior transformers should never be topped up with mineral oil.
Dissolved water can be removed from Pyrocior with a (liter press. Before use, the filter paper should bo dried in an oven at 110 C for 3 to 4 hours. The Pyrocior 1b preferably circulated hot, 66 toflOC, through the filter. If water is present as a separate phase, it should be first removed by separation.
When connecting a filtration plant to a transformer, the dirty Pyro cior should be drawn off from near the top of the bank, pumped through the plant, and then returned to the transformer through the bottom drain valve.
If arcing has oocurred, as shown by the preeenco of carbon, It la often possible to restore the electrical properties of the Pyrocior by treat ment with activated alumina. Peter Spence Alumina A 300 is rocommended for this purpose. It should be activated by heating to 100"C for two hours and then added to the Pyrocior In the proportion of 0.06% by weight. (A volume to weight conversion table Is given in the appendix.) The mixture Is stirred for 2.5 hours at 50 to 60C and then filtered through either a filter press, an edge filter, or a filter with a built-up bed. Only the latter Is likely to remove colloidal carbon.
After treatment the unreacted gas scavenger content of the Pyrocior should bu tested by the method of ASTM D1701 - 59T. If neceeeary, additional gas scavenger should be added to restore the original content.
HONS 073359
TOWOLDMON0024106 WATER_PCB-00008575
TOXICITY AND HANDLING PRECAUTIONS
Aokarels made by Monsanto have been used for over 30 years without causing any toxic effects, but they must be handled with care.
These precautions should be observed: 1 Avoid skin contact. Protect the hands, preferably by
oil-resistant gloves or, for short contact, by using a barrier cream.
2 If skin contaot should occur, wash off with soap and water.
3 If hot aakarel must be handled In a closed or confined area, provide exhaust ventilation or wear an approved respirator.
4 If aakarel gets In the eyss, hush with large amounts of water. In the event that irritation persists, refer the patient to a physician.
5 Infreouent exposure to aakarel vapours will not cause any Ill-effects, but prolonged exposure to a high vapour concentration should be avoided.
Neglect of these precautions may cause acne and may lead to liver damage.
HONS 073360
^
TOWOLDMON0024107 WATER_PCB-00008576
APPENDIX
Packaging Pyroclcir is, at present, packaged in steel drams containing GOOlb. (272 kg) by weight, or 38.3 UKgal (174 litres) at 15.5 C by volume. Pyroolor ETR is similarly packaged, but these drums contain a volume of 41.0 UKgal (186 litres) at l5.5rC.
Velum* to weight conversion tables Pyreeler These tables are based on the density of Pyroclor at 15.5 C:
15.67 lb/UKgal 1.563 kg/Htre Weight In pounds
UKgal
0
20 40 60
80
0_
313 627 940 1254
100
1567
I860
2193
2507
2821
200
3134
3447
3761
4074
4388
300
4701
5014
5328
5641
5965
400
6268
6581
6896
7208
7522
500
7535
8148
B462
8776
9089
600
9402
9715
10029
10342
10656
700
10969
11282
11596
11909
12223
800
12536
12849
13163
13476
13790
900
14103
14416
14730
15043
15357
Weight in kilogrammes
Litres
0
100 200 300 400
D 1000 2000 3000 4000
Litres
1563 3126 4669 6252
500
156 1719 3282 4845 6408
600
313 1876 3439 5002 6665
700
469 2032 3595 5158 6721
800
626 2188 3751 5314 6877
900
0 1000 2000 3000 4000
782 2345 3908 5471 7004
938 2501 4064 5627 7190
1094 2657 4220 5783 7340
1260 2813 4376 5939 7502
1407 25)70 4533 6096 7059
HONS 073361
^
TOWOLDMON0024108 WATER_PCB-00008577
Pyrtoler ITU These tables are based on the density of Pyroclor ETR at IS.5 C: 14.63 lb/UKgal 1.4QO kg/litre
Weight in pounds
UKgal
0
20 40 GO 00
0_
203
100
1463
1756
200
9226
3219
300
4389
4662
400
6862
6145
600
7315
7608
900
8778
9071
700 10241 10634
HOT
11704
11997
900
13167
13460
Weight In Kilogrammes
Litres
0
10U
586 2048 3511 4674 6437 7900 9363 10826 12289 13752
200
878 2341 3804 5267 6730 8193 9660 11119 12682 14045
1170 2033 1096 5559 7022 8485 9948 11411 12874 14337
300 400
0 1000 2000 3000 4000
Litres
0 1000 2000 3000 4000
1460 2920 4380 5840 500
730 2190 3650 5110 6570
143 1606 3066 4526 5986 600
876 2336 3796 5256 6710
292 1752 3212 4672 6132
700
1022 2482 3942 5402 G862
438 1898 3358 4818 5278
800
1168 2628 4088 5548 7000
584 2044 3504 49<tt 6424 ooo
1314 2774 4234 5694 715-1
23
HONS 073362
TOWOLDMON0024109 WATER_PCB-00008578
TtohRlctl 4nlc
The technical service staff of Monsanto is always ready to provide additional Informa tion on the use of the materials Indicated In this report, and to assist manufacturers In the solution of particular problems ensuing from their application.
front cover illustration A 600 KVA, 3 phase, 50 cycle, ground mounting transformer with a voltage ratio of 11.000/415 volts. This Pyroclor Ailed transformer was ordered for installation In tho Royal Palace at Baghdad.
Every effort, has been made to ensure Ui.u ; h.* Information In t tils publication is reliable. bin as the conditions under which it m.n applied arc beyond our control, iw ann.ii accept- responsibility for any result s . u u.-t .
Form* No. P.B. 073-EI-S6D2 Puellshodby Monsanto Chemicals Limttori Printed In Enirland by -l. D. Garrod Ltd.. l.oruJon, 3 hi.id
HONS 073363
^
TOWOLDMON0024110 WATER_PCB-00008579