CHAPTER 20
1946 Guide
into Btu per hour by multiplying the square inches of leader area by 111. 167 and 200 for first, second and third floor respectively.
Example 4 What would be the total gas consumption over a full heating season of a gas-fired gravity warm air furnace designed according to the Code*, and with four 12 in. and two 8 in. round leaders to the first floor and six 10 in. leaders to the second floor, if the gas has a heating value of 500 Btu per cubic foot, the plant operates at a 70 per cent seasonal efficiency and is designed to maintain an average inside temperature of 65 F when it' is 10 F outside in a city where the average outside temperature is 45 F and the heating season is 5088 hr long?
Solution. The area of the round leaders is: 12 in., 113 sq in.; 10 in., 79 sq in.; and 8 in., 50 sq in. The total Btu transmitted is:
First Floor: [(4 X 113) + (2 X 50)1 X 111 = 61,272 Btu per hour.
Second Floor: (6 X 79) X 167
= 79,158 Btu per hour.
Total 140,430 Btu per hour.
Substituting this total heat loss value as H in Equation 1 gives:
F
140,430 (65 - 45) 5088 0.70 (70 - 10) 500 = 680,483 cu ft gas.
DEGREE-DAY METHOD
This method is based on consumption data which have been taken from buildings in operation, and the results computed on a degree-day basis. While this method may not be as theoretically correct as the Calculated Heat Loss Method, it is considered by many to be of more value for practical use.
The amount of heat required by a building depends upon the outdoor temperature, if other variables are eliminated. Theoretically it is pro portional to the difference between the outdoor and indoor temperatures. The American Gas Association * determined from experiment in the heating of residences that the gas consumption varied directly as the dif ference between 65 F and the mean outside temperature. In other words, on a day when the temperature was 20 deg below 65 F, twice as much gas was consumed as on a day when the temperature was 10 deg below 65 F. For any one day, when the mean temperature is less than 65 F, there are as many degree-days as there are degrees difference in temperature between the mean temperature for the day and 65 F. Degree-days may be calculated on other than the 65 F base but are seldom used and are of little value except where the inside'temperature to be maintained as, for example, in warehouses, differs greatly from the usual inside temperature range of 68 F to 72 F.
The normal or average number of degree-days, on a 65 F basis, which have occurred over a long period of years, by months, oh a 65 F basis are given for various United States and Canadian and Newfoundland cities in Table 1. .The United States values were computed from daily mean temperatures recorded by the Weather Bureau over a 43-year period 4 from 1899 to 1941. The number of degree-days for a calendar day of a given year was obtained by taking the difference between 65 F and the mean temperature determined from a reading of the maximum and minimum thermometers for a particular locality. The daily normal was established by taking an average of the 43 daily degree-day figures. These daily values were then added to obtain a monthly normal, and the yearly or seasonal degree-day figure was established by taking a summation of the monthly values. In general, attempts to apply the degree-day
Estimating Fuel Consumption for Space'Heating
379
method to fuel consumption over a period of less than a month are of
questionable value.
1
If the degree-days occurring each day are totaled for a reasonably long
period, the fuel consumption during that period as compared with another
period will be in direct proportion to the number of degree-days in the
two periods. Consequently, for a given installation, the fuel consumption
can be calculated in terms of fuel used per degree-day for any sufficiently long, period and compared with similar ratios for other periods to deter
mine the relative operating efficiencies with the outside temperature
variable eliminated.
Studies made by the National District Heating Association5 of the
metered steam consumption of 163 buildings located in 22 different cities
and served with steam from a district heating company substantiate the fact that the 65 F base originally chosen by the gas industry is approxi
mately correct.
Formula for Degree-Day Method
The general equation for calculating the probable fuel consumption by
the degree-day method is:
.
F= UX NXD
(4)
where
F -- fuel consumption for the estimate period.
U = unit fuel consumption, or quantity of fuel used per (degree-day) {building load unit).
N = number of building load units (when available use calculated heat loss instead of actual amount of radiation installed).
D = number of degree-days for the estimate period. ,
Values of N depend on the particular building for which the estimate is
being prepared and must be found by surveying plans, by observation, or
by measurement of the building. Values of U for use in this equation are
the unit fuel consumptions per degree-day and are obtained as a result
of the collection of operating information. Certain of this information is
presented later but before referring to these data attention is directed to
the nature of the unit.
Unit Fuel Consumptions per Degree-Day
The quantity of fuel used per degree-day in a given heating plant can be reduced to a unit basis in terms of quantity of fuel or steam per degreeday per square foot of radiation, per cubic foot of heated building space, or per thousand Btu hourly heat loss at design conditions. A less fre quently used basis is quantity of fuel per (degree-day) (square foot of floor area).. In fact any convenient unit can be used to relate the consumption to the degree-day and to the building.
The choice of these units requires explanation and some discrimination and judgment. If the volume basis is used, the net heated space is pref erable to the gross building cubage since gross cubage includes outer walls and certain portions of attic arid basement space which are usually unheated: In the absence of data on net heated volume a figure of 80 per cent of the gross volume may be used to obtain the estimated net heated volume: Regardless of which volume figure is used, this unit basis is not considered accurate-for estimating fuel consumption due to differences in types of construction, exposure and ratio of exposed area to cubic contents.