Document 6w9nDeNarvqV04OaBgpENa8vE
DOW CHEMICAL U.S.A.
50883 __________________________________________ _
TEXAS FREEPORT, TEXAS 77541
ENVIRONMENTAL HEALTH REPORT
AIRBORNE ASBESTOS SURVEY
TOOL ROOM BUILDING A-702
PILE NO. A/-J.J3U
nATF January 9, 1978 AUTHOR E. E. Bosche1________
rumrttpn niTr^iti. Ji
Summary
A survey of A-702 Tool Room was made and the asbestos levels were in the 0.02 fiber per cubic centimeter range. This should not present any health hazard to the Tool Room personnel.
cn
H O
o
cn
or FO
bbs
Distribution
Sarah Champagne B-108 P. C. Gay B-101 M. G. Trevino B-108 R. C. Walker, Sr. B-108 G. T. Wommack B-108 ^File
AN OPERATING UNIT OP THE OOW CHEMICAL COMPANY
File A7-1350
I
* '' ^ 1 -2 January 9, 197S
INTRODUCTION
At the request of the Maintenance Department supervision, a survey of the A-702 tool room for airborne asbestos was made on December 15, 1977.
METHODOLOGY
Bendix Micronair personal sampling pumps (Environmental Services, Baltimore, Md.) were placed in the tool room work and office areas as well as on the perimeter adjacent to the Chlorine Cell Manufacturing area. Air was drawn by these pumps through open faced Millipore cassette filters (Millipore Corp., Bedford; Mass.) catalog no. MAWG 037AO. These filters were cleared and fibers ^5 micrometers were counted by phase contrast microscope by Dow Central Laboratory Department.
The pumps were allowed to run for a specific length of time and the air flow was calibrated before and after this sample period. If the air flow was not still the same after the sample period, the starting and ending flow rates were averaged and this was then taken as the constant flow for the entire time.
The reported value from Central Laboratory is fibers per square of grid on the filter disc. This value is multiplied by 90 (the number of available squares on a disc) and related mathe matically to the total air sample volume.
RESULTS
No samples showed a fiber count giving more than 0.02 fibers per milliliter of air. Table I shows asbestos quantities found.
DISCUSSION
The OSHA limit for asbestos fiber is 2.0 fibers - 5 micrometers per milliliter of air. This survey showed a 100 fold safety margin in the Tool Room of A-702 compared to this regulatory limit.
ST00I56U7
EHS EEB/bbs 1-9-78
TABLE I ASBESTOS DETERMINATIONS IN A-702 TOOL ROOM
LOCATION
ASBESTOS FIBERS - 5 un FIBER/ML
Compressor Maintenance Shop
< 0.02
Work area just outside of office
< 0.02
At fence nearest Cell Services area
0.02
At fence at Drum Storage
< 0.02
In office
0.01
ST001561*8