478 CHAPTER 32 1960 Guide The application of insulation to air-conditioning ducts is accomplished in a variety of ways depending largely on am bient conditions and temperature differentials between the air in the room and conditioned air. Boards or blankets are normally used in a single layer 1 in. thick. Boards are fastened to the duct surfaces with spot or solid application of adhesive, and further reinforced with wires, bands, spindle anchors, or sheet-metal screws. Although, where the service is cot too severe, it is permissible merely to point the joints with a muffin compound, in most cases the insulations should be protected against water-vapor permeation. Where blankets are used the insulation can be wrapped around the duct, and held in place with tape over all joints or with spirally wrapped twine. Again in most cases the insulation should be provided with an outer vapor barrier protection. UNDERGROUND PIPE INSULATION The installation of insulated piping underground is much more of a problem than protection of above-ground piping from weather. Ground water conditions including chemical or electrolytic contribution by the soil, plus existence of water head, call for very special design to protect insulated piping from corrosion. Design must take into account the fact that even during installation, weather conditions can result in wetting of the insulation in flooded trenches. Therefore, it is necessary to provide for adequate drying out of the insu lation before covering and sealing. Underground piping systems are installed in a variety of protective structures which include tunnels and metallic and ceramic conduit systems, as well as integral protected pipe and insulation systems. Adequate design of such systems to meet the conditions of underground installation requires compliance with manufacturers instructions. Detailed data on commonly used forms of tunnels, conduit, and other sys tems, together with underground insulation specifications, have been published by the National District Heating Asso ciation in the District Heating Handbook* Piping in large tunnels is covered with sectional insulation to provide optimum thermal performance and is finished with good mechanical protection in the form of metal or waterproofing jackets. In instances where actual submersion of hot piping may occur, experience has shown that water will enter the insulation as water and boll at the pipe surface. It has been found that a few sectional insulations properly secured with corrosion resistant metal banding can withstand the boiling action and release the steam without damage. In some instances an open-weave wire-inserted asbestos fabric, or equivalent, jacket is applied for additional mechanical protection. Conduit systems are in more general use than tunnels. The use of sectional insulation with the conduit sired to provide space between the conduit wall and insulation provides for drainage and adequate drying of the insulation on heated piping in the event of accidental flooding. The thickness of insulation for underground piping is not determined on the same basis as for above-ground piping. Further information on this subject will be found in Refer ences 5, 6, and 7. REFERENCES 1 Clifford Strode: Handbook of Air Conditioning, Heating and Ventilating (The Industrial Press, New York, 1959, p. 4-167 and 170). * Technical Data Sheet (Johns-Manville Corp, August 1955). * U. W. Smith: Rapid method of determining the economical thickness of pipe insulation (ASHVE Journal Ssction, Heating, Piping and Air Conditioning, October 1947, p. 118). 'District Heating Handbook (National District Heating As sociation, 1951, 3rd ed., pp. 193-194). ' D. D'Eustachio: Criteria for thermal insulation for use on underground piping (Symposium on Thermal Conductivity Measurements and Applications of Thermal Insulation, ASTM Special Technical Publication No. 217, 1957). * Underground Insulated Piping Systems (Federal Construc tion Council, Technical Report No. 27,1957). T Underground Heat Distribution Systems (Federal Construc tion Council, Technical Report No. 30, 1958). BIBLIOGRAPHY F. C. Houghten and Carl Gutberlet: Heat emission from iron and copper pipe (ASHVE Transactions, Vol. 39, 1938, p. 97). Heat Transmission from Surfaces (Philip Carey Mfg. Co, Bulletin 102-A). R. H. Heilman: Surface heat transmision (Sec. 1, Mechanical Engineering, May 1929, p. 355). S. Crocker: Piping Handbook (McGraw-Hill Book Co, New York, 1945, 4th ed.). P. Swain: Insulation handbook (Power, Vol. 94, Nos. 2, 3, 5, 7, and 9, 1950). U. W. Smith: How to insulate equipment (Plant Engineering, Vol. 1, December 1947, p. 32). T. S. Nickerson and G. M. Dusinberre: Heat transfer through thick insulation on cylindrical enclosures (ASMS Transactions, Vol. 70,1948, p. 903). H. J. Stoever: Applied Heat Transmission (McGraw-Hill Book Co, New York, 1941). CHAPTER 33 FUELS AND COMBUSTION Solid Fuels: Analysis, Classification of Coals, Classification of Cokes, Combustion of Solid Fuels, Firing Methods for Solid Fuels, Secondary Air, Draft Requirements and Regulations, Furnace Volume; Fuel Oils: Oassrficafion, Air Required; Fuel Gases: Classification, Heat Value, Combustion; General Combustion Principles; Air Required; fffiaency from Flue Gas Analysis; Heat Balance,Condensation and Corrosion; Soot; Air Supply to Furnace Rooms FUELS may be classified according to their physical when required in testing of heating devices. Typical ulti state as solid, liquid, or gaseous. The principal fuels mate analyses of the various kinds of coal are shown in used for domestic heating are coal, oil, and gas. However, Table 1* coke, wood, kerosine, sawdust, briquettes, and other sub Other important qualities of coals are the screen sizes, stances are used for heating in special applications or in ash fusion temperature, friability, caking tendency, and the localities where an adequate supply is available. Experiments qualities of the volatile matter. In considering these factors are in progress in the use of a colloidal suspension of coal the following points are of interest. The volatile products particles in fuel oil, but this fuel has not attained wide given off by coals when they are heated differ materially spread usage as yet. The choice of fuel is usually based on in the ratios by weight of the gases to the oils and tars. dependability, cleanliness, availability, economy, operating No heavy oils or tars are given off by anthracite, and very requirements, and control. small quantities are given off by semi-anthracite. As the SOUD FUELS volatile matter in the coal increases to as much as 40 per cent of ash and moisture-free coal, increasing amounts of Analysis of Fuels oils and tars are released. For coals of higher volatile con tent, the relative quantity of oils and tars decreases and is Coal has a complex composition that mays classification therefore low in the sub-bituminous coals and in lignite. The into clear-cut types difficult. Chemically it consists of carbon, percentage of ash and its fusion temperature do not indicate hydrogen, oxygen, nitrogen, sulfur, and a mineral residue the composition or distribution of the constituents. called ash. A chemical analysis provides some indication.of the quality of a coal, but does not define its burning char Classification of Coals acteristics'sufficiently. The coal user is interested princi pally in the available heat per pound of coal, the handling and storing properties, the amount of ash and dust produced, and the burning characteristics. A description of the qualities of coals and their characteristics can best be obtained from publications of the U. S. Bureau of Mines. A treatment A classification of coals is given in Table 2, and a brief description of the kinds of fuel is given in the following paragraphs, but it should be recognized that there are no distinct lines of demarcation between the kinds, and that they graduate into each other. applicable to heating boilers is given in a U. S. Bureau of Mines bulletin.1 There are two types of coal analyses, namely, the proxi mate analysis and tire ultimate analysis. In the proximate analysis the proportions of moisture, volatile matter, fixed Anthracite is a clean, dense, hard coal which creates little dust in handling. It is comparatively hard to ignite, but it bums freely when well started. It is non-caking, it bums uniformly and smokelessly with a short flame, and it re quires no attention to the fuel bed between firings* Standard anthracite sizing specifications are shown in Table 3. carbon, sulfur, and ash are determined. This analysis is quite easily made and is satisfactory for indicating most of the characteristics which are of interest to the user. For the proximate analysis the moisture is determined by observing the loss of weight of a sample of coal when dried at about 220 F. To determine the volatile matter, the dried sample is heated to about 1750 F in a closed crucible, and the loss of weight is noted. The remaining sample is then burned in an open crucible, and the accompanying loss of weight represents the fixed carbon. The unburned residue is ash. Although determined separately, the sulfur content is frequently reported with the proximate analysis because the usefulness of a coal for certain purposes depends on its sulfur content. In the ultimate analysis, which is difficult to make, the percentages of carbon, hydrogen, oxygen, nitrogen, sulfur, and ash in the coal sample are determined. It is used for detailed studies of fuels, and in computing a heat balance Semi-anthracite has a higher volatile content than anthracite. It is not so hard, and ignites somewhat more easily. Other wise their properties are similar. Semi-bituminous coal is soft and friable, and fines and dust are created by handling it. It ignites somewhat slowly and bums with a medium length of flame. Its caking properties increase as the volatile matter increases, but the coke formed is relatively weak. Having only half the volatile matter con- tent of the bituminous coals, it can be burned with less production of smoke, and is sometimes called a smokeless coal. Bituminous coal is a term covering a large range of coals and includes many types having distinctly different composi tion, properties, and burning characteristics. The range from the high-grade bituminous coals of the East to the poorer coals of the West. Their caking properties range from coals which melt completely, to those from which the volatiles and tars are distilled without change of form, so that they axe classed as non-caking or free-burning. Most bitu minous coals are strong and non-friable enough to permit the screened sizes being delivered free from fines. In general, they ignite easily ana bum freely. The length of flame varies with different coals, but it is long. Much smoke and . ' 479