February 8, 1972 THERMINOL SYSTEM CHANGEOUT PROBLEMS
Mr. D. E. Roush General Offices B-2-S
COMPANY CONFIDENTiAL
G. A. Hlppe A. E. Leisy J. R. Savage - B2SL D. J. Schllllnger
In the Spring of last year, all of the Therminol systems at WOK were changed out from Aroclor to T-66 or T-55.
In many of these units, we followed the recommendations of Marketing and we drained the Aroclor as best we could. We refilled with the substitute fluid without cleaning the system.
About two weeks ago, we discovered the vent line plugged on our heating unit in Dept. 248. Amount of pressure .
buildup was unknown but substantial. Apparent cause was breakdown of Aroclor forming HC1. The HC1 reacted with the steel system forming ferrous chloride. The ferrous chloride sublimed plugging the vent.
-
In Dept. 239, which was given a t-66 rinse, we found the vent nearly plugged. Other systems are being checked.
We have analysed the T-66 in all of our heating systems for Aroclor. Results are:
Dept.
Aroclor 1248
-
245
248 273 255 239
8.1# (T-66 changed out once)
12.5# 4.2#
<-0.5# (system solvent washed) being analyzed T 7o
270
275 258
23.4# Units transferred
8.9# f to Edwin Cooper 26.4#''
Based on our experience, I strongly recommend that any Thermi nol system, customer or Monsanto, be thoroughly washed and cleaned when changing from Aroclor to another fluid. Not only is there a potential safety hazard but there is also a con tinued potential for PCB pollution losses.