Document 6kLew310ODzXJyY5ZNerLe6
184'
CHAPTER 9
1953' Guides.
The Hot Box test value, from University of Minnesota, for tins wall,: corrected for a 15 mph wind velocity, was U = 0T50 Btu per (hr) (sq ft) (F deg). The .error between the calculated and test values would be
0.153 - 0.150 0.160
w X
100
=
2 percent.
If the effect of the tie rods Were omitted from the calculations, the over all U value would be 0.103. Although the percentage of area occupied , by
,th, e tie rod.s per square f,oo,t o,f wa,,ll area i.s --0.00--0-4-8- x 100 = 0.048 percent,
the error between the calculated and test values would be
>
0.150 - 0.103
0.150
X 100 = 31 percent.
In making the-calculations for values of U shown in Tables 6 to 19, the following conditions have been assumed:
Equilibrium or steady-state heat transfer, eliminating effects of heat Capacity. Surrounding surfaces at ambient air temperatures. Exterior wind velocity of.15 mph.
Surface emissivity of ordinary building materials = 0.83. No correction for position or direction of heat flow. (Average coefficients used). Air spaces are I in. or more in width.
Variation of conductivity with mean temperature neglected.
Corrections for framing made on basis of parallel heat flow through 2 X 4 im (nomi nal) studs, 16 in. on centers, the framing covering 15 percent of wall area.
Actual thicknesses of lumber assumed to be as follows:
Nominal
Actual Nominal
Actual
1 in. (S-2-S).............................. J4 in. 3 in. fS-2-S)..:................................. 24 in.
1$ in. (S-2-S)...............................lA in. 4 in. (S-2-S).:.................................... 3f in. 2 in. (S-2-S)................................l| in. Finish flooring, (maple or oak). . . 1A in. 2\ in. (S-2-S)................................2i in.
Coefficients for frame construction are corrected for the effect of framing where such correction would increase the coefficients, but not where the correction would decrease the coefficients.11
It should be noted that the effects of poor workmanship in construction and installation have, an increasingly greater percentage effect on heat transmission as the coefficient becomes numerically smaller. Failure to meet design estimates may be caused by lack of proper attention to exact compliance with specifications. A factor of safety may be employed as a precaution when it is judged desirable.
Roof Coefficients
Computations for wood shingle roofs applied over Wood stripping are based on 1 by 4 in. wood strips, spaced 2 in. apart. Values for roofs con taining Spanish and French clay roofing tile are assumed the same as for slate roofs. Values for pitched roofs in Table 17 apply where the roof is over a heated attic or top floor, so that the heat passes directly through the roof structure, including any interior finish material.
Combined Ceiling and Roof Coefficients
If the attic space between the ceiling and roof is unheated, the combined coefficient from room air below the ceiling to exterior air can be calculated from the following formula:
Heat Transmission Coefficients of Building. Materials
. 1- 1
St
=
-- + -yr /,. nu.
185 " (4)
and
. U = 1/Rt
where
U - combined coefficient to be used with ceiling area. Rr = total resistance of ceiling and roof.
= coefficient of transmission of ceiling. U, -- coefficient of transmission of roof. n = ratio of roof area to ceiling area.
'
- (5) ':
It should be noted that the overall coefficient U should be multiplied by the ceiling area to determine heat loss, and not by the roof area; Values of Ur and Ux should be calculated using a value of 2.2 (the reciprocal of one-half the air space resistance) rather than 1.65 for the conductances of surfaces facing the attic, since the attic is equivalent to an air space.
If the attic contains windows, dormers and vertical wall spaces, and if their area is small compared to that of the roof, they may be considered part of the roof area. For accuracy, the sum of the coefficients of each individual section, multiplied by its percentage of the total area, should be used as Ur. Where attic wall areas are large, it is preferable to estimate the attic temperature as illustrated in Chapter 12, and calculate the heat loss through the ceiling by multiplying the value of UM for the ceiling by the difference in temperature above and below the ceiling.
Basement Floor, Basement Wall and Concrete Slab Floor Coefficients
The heat transfer through basement walls and floors to the ground is dependent on the temperature difference between the air within and that . of the ground, on the material constituting the wall or floor, and on the conductivity of the surrounding earth.- The-conductivity of the earth will vary with local conditions, and is usually unknown. Tests12 at the A.S.H.V.E. Research Laboratory indicate a heat flow of approximately 2.0 Btu per (hr) (sq ft) through an uninsulated concrete basement floor, with a temperature difference of 20 F between ground temperature and the air temperature 6 in. above the floor. Based on this result a coeffi cient of 0-10 Btu per (hr) (sq ft) (Fahrenheit degree difference) is recom mended for calculation where it is desirable to allow' for the small base ment floor heat loss, e.g., for heated basements.
For basement walls the same coefficient may be used, but due to closer proximity to the surface of the ground, the temperature difference for win ter design conditions will be greater than for the floor. The test results indicate a unit area heat loss, at mid-height of the basement wall approxi mately twice that of the same floor area.
For concrete slab floors laid in contact with the ground at grade level, recent tests12 indicate that for small floor areas (equal to that of a house 25 feet square) the heat loss may be calculated as proportional to the length of exposed edge rather than total area. This amounts to 0.81 Btu per (hr) (lineal foot of exposed edge) (Fahrenheit degree difference between the inside air temperature and the average outside air temperature). It should be noted that this may be appreciably reduced by insulating under the ground slab, and also along the edges between the floor and the abut ting walls. See also sections on Basement Temperatures and Heat Loss, and on Floor Heat Loss in Basementless Houses, in Chapter 12.