Document 6bgv6GDrYnzD9ejB03Y6kVdyg

Preliminary Dust Survey for Asbestos Textile Institute, Juno, 19U7 , 13. of veeks, the eyetem operation vill suffer. Apparently, some of the. older commercial flat hag type of collectors All. exhibit that difficulty. Modifi cations In the design of such units have, however, been Incorporated In acre recent models end those difficulties nay have been eliminated. Ttro plants employ commercial collectors of the flat bag or envelope type. Another plant usee & doth tube conoerelal collector and also one whose filtering element Is of paper, vhich la replaced at Intervale of several -weeks, A. study of operating details of these conoerelal collectors la indicated in this study,, inolndlng coneldexatloua of original coat end operating cost. Beclrculatd.cn Several plants return air from the duet collectors to the vorkrooo to conserve heat In the cold veather. Ve are not prepared at this point- either to condone or to condemn this practice except In cases vhere there is obvious ly leakage of dust through the filter and consequent recantaminatian of the air inside the plant. The practice Is generally frowned upon vhere dusts that axe hazardous to health axe being handled. Ve believe there are certain circumstances vhere the practice might be permissible provided adequate safe guards are Incorporated In operating procedures. The large volumes-of air Involved In dust control represent a tremendous problem as to heat loss and boiler capacity vhich cannot be passed over lightly.