Document 6bgRaw842vYLpJ75G5OBkO7GR
774
____________
CHAPTER 42
________'1946 Guide.
Grille Selection
''
In practice the allowable total sound and the required air flow are usually known, and it is desired to determine the maximum allowable velocity. In comparing sound ratings of various grilles several_ factors must be known if the information is to be properly applied:
1. The threshold intensity on which" the decibel ratings are based.
' 2. The distance from the grille at which data were taken.
3. If stated as loudness level versus velocity for a given grille, the core area (not nominal area) must be known.
4. The sound absorbing characteristics of the test room. 5. Whether or. not corrected for test room loudness level: if not; the room level (without grille noise) must be known.6. Methods used for recording data. (Characteristics of sound meter).
Since total loudness and air flow are both functionsof velocity and area, the solution of the problem implies a trial and error method. It has been found possible to present these data with sufficient practical accuracy as a family of uniform curves, as illustrated in Fig. 5, which are based on
these assumptions:
1. Threshold intensity = 10~'" watts per square centimeter1.,
2. Microphone location 5 ft from lower edge of supply opening on a line downward at ' 45 deg and in a plane bisecting the supply opening perpendicularly.
- 3. Where data are given as loudness level versus velocity, the rating is per square foot of core area.
4. The room is assumed to have 100 sabines absorption.
5. Plotted data are loudness levels of supply openings only,, correction having been
made for test room level.
-
6. Data taken with a direct reading sound-level meter with frequency weighing network intended to approximate the response of the human ear.
If the published ratings are in terms of decibels per square foot, cor
rection must be made for area to secure the total sound level of supply openings of more or less than one square foot area from Equation 11.
Decibel Addition = 10 logioA
(11)
where A -- core area, square feet.
'
With Fig. 5 it is possible to find directly the velocity in feet per minute
which will give a predetermined total loudness at a predetermined rate of
flow expressed in cubic feet per minute. The values used are arbitrarily
chosen for,the purpose of discussion and do not necessarily represent data
referring to any particular design of air supply opening. A correction
chart is shown in Fig. 6 for a room having a sound absorption other than
100 sabines.
,
Example 3. Determine the core area (see Chapter 40) of an air supply grille which will maintain a noise level of not more than 40 db in a room having 100 sabines of sound absorption, if an air volume of 2400 cfm is required to maintain the proper air con-.
ditioning. -
Solution. Assuming a grille noise rating of at least 5 db below the noise level of the room. Fig. 5 shows that the limiting grille velocity for a total loudness of 35 db is about 725 fpm and the core area becomes fixed at 2400.4- 725 or 3.31 sq-ft.
If the room absorption had been greater,- the previously selected velocity of 725 fpm would be safe, since the loudness reduces. If the room absorption had been 200 sabines a correction of plus 1.3 should be made by reference to Fig. 6, and the permissible velocity -. becomes that corresponding to a total loudness of 36.3 or approximately 800 fpm.
If the room had been highly reflective with an absorption of less than 100, the cor- -
Sound Control
775
rection would be much more important. For instance, for a room of 35 sabines a cor rection of minus 3 db should be made'and the maximum velocity corresponding to the' 32 db total loudness would be approximately 600 fpm.
Where more than one supply opening must be considered, the problem; is more complicated., If a similar supply opening is added in a far corner of a highly absorbent room, the change in noise level at the 5 ft station at the first supply opening is small; however, if the room is small, or highly reverberant or both, the intensity at the 5 ft station may be almost doubled and the noise level increased nearly 3 db thereby. The simplest method of handling this problem is to treat the room as though all the air were being supplied by one supply opening. Thus, if two outlets, each supplying 1000 cfm are used, the value 2000 cfm should be used with
Fig. 5. Although this method may place an unwarranted limit on.velocity when used in a large, room, it is seldom that such a room has a noise level low enough to justify a more complicated though more exact procedure.
In general, return grilles are selected for velocities about half the supply velocity, and when this is done, they may be neglected in sound computa tions. However, if supply and return grilles are the same size, resulting in the same face velocity, they must be treated as two supply openings. That is,, if 1000 cfm are supplied and exhausted, through grilles of the same area, 2000 cfm must be used in the. solution with Fig. 5.
CROSS TRANSMISSION BETWEEN ROOMS
Ducts serving more than one room permit cross talk between the'rooms and should be lined with acoustical .material; Where the rooms are close together and the ducts short, the ducts should be sub-divided to provide