Document 6bG73jRky3wy3EEeeLDGzpa59
HEATINC VENTILATING AIR CONDITIONING GUIDE 1943
the heat capacity of water is approximately unity, this slope is the ratio of the water to the air rate. Equation 3 indicates that the potential for energy transfer at any section is the difference between the enthalpy of saturated air at the main-body water temperature at that section and the enthalpy of the air stream in contact with that water. This potential is the difference in the ordinates of the saturation and operating lines for the water temperature at the plane in the tower which is under con sideration.
Combination of Equations 2 and 3 results in the expression:
Gdh = Ka (ft" - Aa). d V
(4)
Integrating this equation over the length of the exchanger:
J2P G dh ** Kah'-K
V
' {5)
Conditions 1
Water flow
l Lb per hr
Energy exchange LcdUGdh
dV
Air 41 ^ G flow Lb per hr
Conditions 2 Fig. 4. Section of Typical Counter-Flow Tower
The integration of the left side of Equation 5 determines the tower volume required to achieve the desired energy exchange- This summation is readily accomplished for counter and parallel flow arrangements. G and Ka are usually independent of the tower volume and Equation 5 then becomes:
NTU- f1** = ^
y2 ^ --
G
(6)
J^k.ere
*s defined as the Number of Transfer Units and is a measure of the
difficulty of the cooling process.
v
. The integration is made numerically or graphically. In the'graphical
integration
^ is evaluated as a function of Aa. This determination
involves the use oi the energy balance equation integrated from one section to the section in question. The area under the curve between any two abscissae is the number of transfer units required to change the air state from. Aj to Ai.
An approximate value for the number of transfer units can also be determined by a simple graphical method of direct construction on the
548
CHAPTER 27. SPRAY EQUIPMENT
temperature enthalpy diagram7. This method cannot be applied very sati^actorily to cooling towers as the operating range is small' and the
value of the NTU is near unity.
When the relationship between the enthalpy of the saturated air and the temperature is linear over the range of water temperatures involved, it can be shown8 that the logarithmic mean of the terminal potentials, Aim, is the correct driving force: This is true to a good approximation when the water cooling does not exceed 15 F. The approximation to linearity may be determined by inspection of Table 6, Chapter 1, or the temperature enthalpy diagram of Fig. 5. If the logarithmic mean is a
valid potential, Equation 6 may be written:
to -- to _ KaV
Atom
G
n\
Fig. 5. Temperature Enthalpy Diagram for Air Water Vapor Mixture __ Showing the Operating Line for Example 1
and the need for the numerical integration for the determination of the tower volume is eliminated.
The overall rate coefficient,Ifo, must be known if the tower volume is to be determined. Experiments conducted on towers containing different packing construction have yielded some. magnitudes of this coefficient, evaluated on an overall basis. These data are presented in Fig. 6,as a. function of the gas mass velocity through the packing, and apply only to the particular packing structure for which they were obtained. The overall rate coefficient (Ka) 'may also be a function of the water rate, since a reduction of the water rate may reduce the wetted area within the exchanger9. The results included in Fig. 6 probably represent magnitudes
'Graphical Method of Determining Number Transfer Units, by T. Baker (/ndustrial and Engineering Chemistry, August, 1935, Vol. 27, p. 977).
Loc. Cit. Note 4, p. 79, *Loc. Cit. Note 5.
549