Document 6b1paJJQQ22R9mDMm296LxGw6
PUB. NO. CP--PI--1973 PUB. NO. TR-P6-1973
JANUARY 25, 1973
PROPOSED AMERICAN NATIONAL STANDARD GUIDELINES FOR HANDLING
AND DISPOSAL OF CAPACITOR- AND TRANSFORMER-GRADE ASKARELS
CONTAINING POLYCHLORINATED BIPHENYLS, C107.1- (
I
iHONS 042009
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
ISS EAST 44TH STREET. NEW TORE. N. Y. 10017
TABLE OF CONTENTS
General............................... ............................ Benefit!............................................................
.......................... ..........
Alternative*............................. .................... Interdepartmental Task Force on PCB'i
Section Page
1 1-3
11 11 11 12 12
CAPACITOR GUIDELINES......................................
Introduction....................................................... Capacltoi-grade Askarei ..................... Plant Housekeeping and Employee Safety Control of Water Effluents........................... Scrap Disposal Procedures............................. Labeling..............................................................
2 1-9
21 21 21 26 26 28
TRANSFORMER GUIDELINES
General Guidelines.... SpedAc Guidelines....
3 1-7
31 35
DISPOSAL SERVICES
4 1-2
APPENDIX--ANALYTICAL PROCEDURES AND LABORATORY SERVICE ORGANIZATIONS.
A Tentative Procedure for the Determination of Airborne-polychlorinated Biphenyls Analysis of Water and Sediment for Polychlorinated Biphenyls........................................
5 1-23
5 1-8 5 9-16
1973 by National Electrical Manufacturers Association HONS 042010
PROPOSED AMERICAN NATIONAL STANDARD GUIDELINES FOR HANDLING
AND DISPOSAL OF CAPACITOR- AND TR AN S FOR MER-CR A DE ASKARELS
CONTAINING POLYCHLORINATED BIPHENYLS, C107.1- (
)
(NEMA Official Standards Proposal 1-25-1973.)
Tills proposal was prepared by NEMA, in cooperation with die Capacitor and Transformer Working Groups of die American National Standards Institute Committee. C107, on Use and Disposal of Askarel and Askarel Soaked Materials.
These proposed standards will be periodically reviewed for any revisions necessary to keep them up to date with advancing technology. Proposed or recommended revisions should be submitted to?
Technical Director Manager. Engineering and Safety Regulations Department National Electrical Manufacturers Association 1SS East 44th Street New York, New York 10017
i HONS 042011.
o
o
GUIDELINES FOR HANDLING AND DISPOSAL OF CAPACITOR- AND TRANSFORMER-GRA DE ASKARELS
CONTAINING POLYCHLORINATED BI PHENYLS
SECTION 1 PREFACE
o
MONS 042012
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
SECTION 1 PREFACE
I. GENERAL
Askarels consisting of or containing polychlori nated biphcyuls (PCB's) have been used In many applications for over forty years, but only recently was evidence discovered that PCB's are widely dispersed in the environment. Systematic investi gations of tire biological effects of PCB's have been undertaken within the past few years to es tablish die effects of specific formulations upon specific species. Some studies have shown that PCB's may be an environmental contaminant. Simultaneously, significant steps have been taken by u.S, Industry to limit further releases of PCB's to the environment.
PC8'S have been used in three broad types of applications for the past forty years, as follows: (a) "open ended" applications, for example, in paints, specialty inks, paper coatings, plastics, etc., (b) "nominally closed" applications, for example, as the working fluid in hydraulic or heat transfer systems; and (c) "closed electrical system" applications, specifically as the insulating fluid in certain types of transformers and capaci tors. The Monsanto Company is tire sole U. S. producer of PCB's. It has discontinued supplying tite material for all type (a) and (b) applications.
Evaluations of the alternatives and risk/benefits involved in the continued use of PCB's in closed electrical systems are summarized in the following.
Askarcl-filled power and industrial capacitors are significantly smaller, more reliable, more durable, and safer than oil-filled capacitors. As a result, askarels have supplanted mineral oils in more than 90 percent of the power and industrial capacitors made today. Over the past few decades most of the equipment that Incorporates such capacitors has been designed to take particular advantage of the Size, safety and reliability benefits of askarcl ca pacitors (e.g., many types are today less than 1-4 percent of the size of equivalent oil capacitors and have a life expectancy of ten to more than twenty years).
Various federal, state and local codes, therefore, require their continued use in or adjacent to public, commercial and industrial buildings which locations present the greatest potential danger to Life and property.
111. RISKS
In the United States, medical records over a nearly forty-year period show that tite only ad verse health effects experienced by U.S. workers exposed to askarels, either during the manufacture of these liquids or of electrical equipment con taining these liquids, have been limited to oc casional cases of non-chronic chloracne or other temporary skin lesions or irritations.
11, BENEFITS
Aikarel- tilled transformers do not burn or sustain fire under conditions of internal electrical arcing.
Askarcl-filled transformers and capacitors arc delivered to customers as scaled units from winch there is no escape of askarel under normal oper ation. While certain types of equipment failures can permit loss of some askarel to the environ-
Section 1 Page 1
MONS 042013
O
o o
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
mem, transformer failures are limited to approx imately 0.02 percent of the units in service per year. Willi icspect to capacitors, such losses are limited to approximately 0.02 percent of the askarel put into service per year. In addition, limited amounts of PCB's can get into the en vironment during the manufacture, delivery, improper use, maintenance, repair and disposal of transformers and capacitors.
Specific control measures have been instituted by Individual manufacturers and are supplemented and strengthened by national standards and procedures such as this Guide which provides information to prevent die inadvertent loss of PCB's to the environ ment at all stages from initial askarel manufacture through ultimate disposaL
iV. ALTERNATIVES
For technical and local and national code rea sons. it would be impossible to replace most askarelfilled transformers now in service with oil-filled units of equivalent ratings, without major construction changes that would be required to compensate for the fire resistance of the askarel-filled units. For certain applications and locations, dry-type trans formers may replace askarel-filled transformers.
For new installations, while many of the lim itations noted above would still apply, building and installation design provisions could be made to accommodate the use of oil-filled, open drytype, or scaled dry-type transformers provided nccctta y technical, code, physical size, and cost considerations are properly evaluated.
Section 1 Page 2
The principal alternative to askarels for capac itors is mineral oiL but such replacement would return capacitor technology to its pre-1932 level and would necessitate the redesign and replace ment of such widely used equipment as fluores cent light fixtures and racks for power and in duction heating capacitors, which could not now accommodate the increased size of oil capacitors while maintaining their present ratings.
The cost of askarel liquids is about five to ten times more than mineral oil. Thus, long before there were any environmental concerns about PCB's. there was a strong economic In centive to find other less expensive insulating liquids with the desirable characteristics of askarels. Since the 1930's at least ten major chemical or electrical companies have invested large amounts of time and money in this search, all with no success. While potential substitutes that are most costly than askarels have also re ceived some consideration (e.g., fluorinated liquids), little is known about either their elec trical performance or possible ill effects upon the environment. There are today no fluids that tcan be used as a direct replacement for askarels.
V. INTERDEPARTMENTAL TASK FORCE ON PCB'S
An in-depth study of PCB's has recently been completed by five Executive Branch Departments of the federal government. This Interdepartmental Task Force on PCB's issued tbeir report entitled, "Polychlorinated Biphenyls and the Environment," in May, 1972. * See Section 1 Page 3 for die conclusion quoted from page 4 of this report.
# Distributed by the National Technical Infor mation Service, U.S. Department of Commerce, Springfield, Virginia 22151. Price S6.00.
MONS 042014
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
"The use of PCB's should not be banned entirely. Their continued use for transformers and capacitors in the near future is considered necessary because of the significantly Increased risk of fire and explosion and the disruption of electrical service which would result from a ban on PCD use. Also, continued use of PCB`s In transformers and capacitors presents a minimal risk of environmental contamination. The Monsanto Company, the sole domestic producer, has reported voluntarily eliminating Its distribution of PCB'l to all except manu facturers of electrical transformers and capacitors." Reference should be made to the Interdepartmental Task Force Report for additional information and conclusions.
MGNS 04^015
Section 1 Page 3
o
o
GUIDELINES FOR HANDLING AND DISPOSAL OF CAPACITOR- AND TR AN S FO RM ER-G R A DE ASKARELS
CONTAINING POLYCHLORINATED DIPHENYLS
SECTION 2 CAPACITOR GUIDELINES
o
{
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA.
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
SECTION 2 CAPACITOR GUIDELINES
I, INTRODUCTION
The environmental effects of askarcls are under In* depth study by governmental and other agencies. Askarcls have been considered relatively harmless to humans based on about forty years uf safe industrial usage. There has been no known instance of human Injury when they were used under the normally ac cepted precautions and conditions of handling in botit manufacturing and user applications.
Traces of askarcls are being found in the en vironment and in fish and blrdlifc. The lung-term genetic and ecological effects are not yet com pletely understood. For tltese reasons, care should be taken to contain askarels and minimize their entry into the environment
There are two general classes of askarels used by tlie electrical industry. The higher chlorinated grades are the more persistent in nature. Because of their high degree of nonflammability, they are used in transformers where personnel safety is of paramount importance.
Capacitor-grade askarcl has a lower degree of chlorination (composed primarily of the 3-chlorine isomers of biphenyl) and a higher degree of bio degradability. Generally, it has not been found in animal life. It is used in capacitors where the extreme degree of nonflammability required in transformers is of less importance.
Although capacitor- and transformer-grade askarcls both contain members of the PCB family, they do differ in composition, degree of biodegrad ability, persistence in nature, electrical stability, chemical stability, and degtee of nonflammability (both are recognized as nonflammable). It is for these reasons that this section of the Guidelines is intended to apply to capacitor-grade askarcL
II. CAPACITOR-GRADE ASKAREL
In September of 1971, a new grade of capac itor impregnant, Aroclor 1016, was made avail able to the industry. This new grade contains a typical concentration of 0.4 percent by weight of tlie higher boiling homologs of the chlorinated biphenyls. * Aroclor 1016 replaces Aroclor 1242 which previously was die major capacitor inipregnant and contained around 7 percent of the higher boiling homologs (the more persistent in nature). This 0.4 percent level of die higher boiling ho mologs should be die maximum concentration acceptable in any capacitor impregnant. Aroclor 1242 and 1254, previously used as impregnants, do not meet this requirement and should no longer be used in capacitors designed and manufactured for alternating-current applications.
Aroclor 1016 has the same UL nonflammability rating as Aroclor 1242. Its typical properties are given in Table 1. (See Section 2 Page 2.)
III. PLANT HOUSEKEEPING AND EMPLOYEE SAFETY________
The following procedures and limits are in tended to be minimum requirement! to be met by manufacturers and users of capacitors contain ing askareL Handling, control and disposal pro cedures are given, together with exposure limits and indicated antidotes and cleanup procedures.
A. Material Askarcl for use in capacitors should consist of
homologs and Isomers of chlorinated biphenyl with the concentation of the higher boiling homologs at about 0.4 percent. * Aroclor 1016 is considered to be die standard impregnant meeting these require ments.
* Monsanto Method T-02302.
Section 2 Page 1
MGNS 042017
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
Table 1 Typical Properties of Aroclor 1016
Property and Method
Typical Values
Color (APIIA)...................................................................................................................... Condition........................................................................................................................ ... Specific Gravity at 25/15. 5"C (ASTM D 1810)..................................................... Acidity (mg. KOH/g.) (ASTM D 974. D 664).................................................... Moisture................................................................................................................................. Refractive Index at 25'C (ASTM D 1617)............................................................... inorganic (Free) Chlorides (ASTM D 1821)............................................................. Pout Point (ASTM D 97)................................................................................................ Dielectric Constant (ASTM D 924) (1000 Hz at 100*C)................................... Resistivity (ASTM D 1169) (500 VDC at 100"C, 0.1-inch
Gap.).............................................................................................................................
Hydrolysis Stability Test (ASTM D 1820) (As Chlorides)................................. Thermal Stability Test (ASTM D 1936) (As chlorides)...................................... Distillation Range (ASTM D 20 Corrected)
10 percent Distilled by Weight........................................................................... 90 percent Distilled by Weight............................................................... .......... Higher Boiling Homologs (Monsanto Method T-O2302) `.................................... Sulfates (ASTM D 117)................................................................................................... Dielcctrie Strength at 25'C (ASTM D 877)............................................................. Flash Point, Cleveland Open Cup (ASTM D 92).................................................. Fire Point................................................................ .............................................................. Corrosion Test (6 hours at 210*C with bright aluminum foil) Change In Weight of Aluminum.................................................................... .. VUcoaity at 100'F (SUS) (ASTM D 88).................................................................... Specific Heat at 25'C ..................................................................................................... Coefficient of Expansion (ASTM D 1903).................................................................. Fixed Chlorine (Carius)............................................ ....................... .............................. Power Factor at 100*C 60 H2 (Monsanto Method T-2273) Bulk................................................................................................................................. Drums .................................................................................................................
40, max. Clear 1. 362-1. 372 0.010 max. 05 ppm. max. 1.6215-1.6235 0.05 ppm. max. *14'C or lower 4.70-4.90
50 x 109 ohm-cm,
0.5 ppm, max. 0.4 ppm, max.
min.
323*C. min. 356*C, max. 0.4 percent, max. None 35 kV. min. 338*F. min. None to Bolling Point
^ 0.0 percent 71-81 0. 30 0,00068 cc/cc/*C 41.3 * 0.5 percent
1 percent, max. 4 percent, max.
Section 2 Page 2
MOMS 04^018
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARO DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
Commonly used solvents Include ben2cne, kero* sene, ace tone, trichlorocthane, trichloroethylene and perchloroethylcne. Typical vapor pressure data for Aroclor 101G arc:
0*c 0,001 mm 25*C = 0.006 mm 160*C = 4,3 mm 200*C * 29.0 mm
At 25*C and 760 mm Hg pressure, saturated air contains approximately 0,09 mg/litcr.
[1 mg/11 ter = 90.0 ppm (v/v]]
[l ppm (v/v) = 0.011 mg/litef]
B, Bulk Fluid Sliipment, Receiving, and Transfer
Shipment of askarel itom point of manufacture to point of receiving should be done in closed containers such as rail tank cars, truck tanks, marine or barge tanks, or sealed drums. Con tainers should be labeled as to contents and carry a label cautioning against loss of fluid to the open environment. Containers used to transport askarel should not be used for storage or to transport other material without being com pletely cleaned of all traces of askarel. (Clean ing procedures must take cognizance of pre cautions against excessive exposure and of the need for proper disposal of contaminated cleans ing solvents and materials as set forth in Part V of this Section.) Transfer from shipping containers to processing systems should be through closed piping or tubing with appropriate valves, pumps, etc. Provision should be made for trapping and disposing of fluid lost by leakage or spills from the transfer system and from the storage con tainers.
Drums to be retired from use should be cleaned before crusliing, delivery to scrap dealers, or ocher disposal. Contaminated cleaning fluids and ma terials should be disposed of as indicated in Part V.
C. General Safety Precautions Although it is generally accepted dial exposure
to capacitor-gradc askarel is not hazardous pro vided simple precautions are taken, exposure should still be avoided.
1. Vapors--The odor of askarel is noticeable well below tlie maximum air concentra tions considered safe. Up to 1.0 milligram per cubic meter of air has been determined to be the maximum safe level of exposure during an 8-hour work day (Par, G, ref erence 8). The procedures for performing the necessary analyses are contained in Section 5, "A Tentative Procedure for the Determination of Airborne-Polychlorinated Biphenyls."
Breathing vapor or fumes from heated askarel should be avoided. Provisions should be made for adequate ventilation and regulation of manufacturing operations to avoid open exposure to askarel (especially at 55*c or higher). The gases produced when askarel is decomposed by very high temperatures (such as chat of an electric arc) in the pres ence of air or organic insulating materials contain a high percentage of hydrogen chlo ride, and small percentages of carbon di oxide, carbon monoxide and oxygen. Minute concentrations of this combination of gases are very unpleasant and irritating, thus giving ample warning of their presence. If exposure to high concentrations of askarel is necessary under emergency conditions, an approved gas mask or self-contained breadiing appa ratus should be worn. Such exposure should be under the surveillance of other personnel capable of rescue in case of an accident. If the odor of askarel is detected by the person wearing protective equipment, he should im mediately go into fresh air. All gas masks, respirators and replacement parts should have Bureau of Mines approval and be maintained on a regular schedule in accordance with the manufacturer's recommendation.
Section 2 Page 3
MONS 042019
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA.
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
2. Liquid--Unlike insulating oil, there is vir tually no fire hazard in handling askarel. A limited solvent action (similar to that for palm thinner) on the fau and oils of die skin with prolonged contact may lead to drying and chapping of the skin. As with insulating oil, some people are al lergic to askarel and continued exposure may result in skin irritation. Both the liquid and vapor are modetatcly irritating to eye tissue.
Operating procedures should be such as to minimize 01 eliminate contact with askarels. Use of eye protection is recommended. The use of porous gloves which can absorb and retain askarels is to be avoided. Bar rier creams* or resistant glovest should be used if contact is unavoidable. Use of en closed transfer and handling equipment, processing equipment, and mechanical washers reduces direct contact.
Medicinal washes or mild detergents fol lowed by die application ol cold cream will reduce the irritation resulting from die contact of an open cut or abrasion with askarcL
Safety glasses with side shields or a face shield should be worn when handling askarels. II liquid askarel contacts the eyes, die eyes should be irrigated immediately with large quantities of running water for 15 minutes and then examined by a physician. (A drop of castor oil has been found to reduce ir ritation. )
Persons developing a skin irritation or res piratory tract irritation while working with askarels should be placed under the super vision of a physician.
Ingestion or swallowing of askarels is not generally regarded as a problem of die in dustry. Should accidental ingestion occur, a physician should be consulted. Hands should be washed with warm water and soap before eating, drinking, smoking or using toilet facilities.
D. Manufacturing Housekeeping Manufacturing equipment and operating pro
cedures should safeguard against loss of askarels to tiie environment through proper containment and disposal procedures.
Enclosed systems of sealed piping, properly gasketed joints, valves, containers, and pro cessing chambers should be used for any portion of the operation wiicrc askarel temperatures may exceed 55*C. Enclosure should preferably extend to all oilier portions of die system insofar as practicable.
Containment provisions should be established
around all askarel processing areas to ensure
against inadvertent loss 10 sewer systems by
spillage, leakage, or oilier uncontrolled con
ditions or events.
"
Spills of askarel should be removed promptly by means of absorptive material, such as sawdust, or trapped and removed by pumping or other suitable means.
* for example, PLY No. 9 Gel (Milburn Co., Detroit, Michigan), or Kerodex #71 (Ayers Laboratories. P. O. Box 823ti, church Street Station, New York. N. Y. 10049). or the equivalent t Edmonl, Solvit 5-302 (Mcrsick of Bridgeport, 22 Cross Street. Bridgeport, Conn. OOCOl). or the equivalent Section 2 Page 4
HONS 0<tQ2Q
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA.
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
Watte fluids containing askarcl not suitable for reconditioning or reuse should be collected (by means of traps, drip pans, trays, etc.) from the various parts of the manufacturing and processing area (including washers or other cleaning devices}. Disposal should be made in accordance with Part V of tlds section.
Wiper rags, clothing and other extraneous ma terials saturated with askarcls sliould be collected within the containment area for properly controlled laundering or disposal (sec Part V of this section).
E, Disposal of Askarcl Wastes Methods for disposal of liquids and saturated
solids generated by the manufacturing operation should be in accordance with those outlined in Pan V of this section and should include (but not be limited to) the following wastes:
1. Contaminated liquid askarel which is unsuit able for reclaiming as a dielectric fluid.
2. Liquid askatel from solvent operations or water/derergent type washers.
3. Saturated earth or oilier absorbent media from filtering operations.
4. Saturated sawdust or odier absorptive ma terials from spills.
5. Saturated filters from vapor control devices and other filters.
6. Saturated wastes (paper, rags, etc.}.
7. Saturated, spent gasket materials.
8. Askarcl-contaminatcd vacuum pump oils.
9. Askarel-contaminated sueam jet vacuum system condensates.
F. Miscellaneous procedures
1. Spills by leakage from finished capacitors should be cleaned up promptly by means of absorbent media which should then be moved to containers provided for that pur pose witliin the containment area and later disposed of properly.
2. Askarel wastes should never be disposed of down effluent drains or sewers. The utmost care must be exercised to prevent accidental loss by these avenues to the environment.
3. Capacitors failing tests or otherwise desig nated for disposal must be controlled and handled in accordance with the intent of the procedures above, finally being disposed of by one of the means outlined in Part V of this section.
G. References
1, Monsanto Industrial Chemicals Company: Technical Bulletin Q-FF/1R. Aroclor (*) Polychlorinated Polyphenyls (Biphenyls) (November 1971).
2, American Conference of Governmental In dustrial Hygienists: Threshold, limit Values for 1964. AMA Archievcs of Environmental Health 9:545 (1964).
3. Treon, J.F.. F.P. Cleveland, J. Cappel, and R.W. Atchley: The Toxicity of the Vapors of Aroclor 1242 and Aroclor 1254. American Industrial Hygiene Association Quarterly 17:204 (1956).
4. Elkins, H. B.: The Chemistry of industrial Toxicology. John Wiley and Sons, Inc., New York (1959).
Section 2 Page 5
HUNS
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
5, Drinker, C. K., M, F. Warren, and G. A. Bennet: The Problem of Possible Systemic Effects from Certain Chlorinated Hydrocarbons. Journal of Industrial Hy giene and Toxicology 19:283 (1937),
6. Drinker, C. K.: Further Observations on the possible Systemic Toxicity of Certain of the Chlorinated Hydrocarbons. Journal of Industrial Hygiene and Toxicology 21:155 (1939).
7. Greenburg, L.. M. R. Mayen, and A.R. Smith: The Systemic Effects Re sulting from Exposure to Certain Chlorlnnated Hydrocarbons. Journal of Industrial Hygiene and Toxicology 21:29 (1939).
8. Hygienic Guide Series "Chlorodiphenyls" (January-February 1965) by the American Industrial Hygiene Association, 210 Haddon Avenue, Westmont, N. J. 08108.
IV, CONTROL OF WATER EFFLUENTS
The industry goal is to eliminate askarel in plant water effluent streams. However, it is tecogniacd that existing drain systems in capac itor manufacturing plants are probably contam inated as a result of past practices, and askarel traces may continue to show up in effluent streams for some time. However, the level should continue to decrease with the proper containment of askarel wastes and no further discharges into drain systems. Other sections of this Guide provide that no askarel wastes of any kind be disposed of in any water effluent streams and that accidental spills be prevented from getting into such streams.
Section 2 Page 6
A. Concentration Limits The 1972 EPA proposals are to keep PCB
levels In rivers and lakes below 0.01 parts per billion. Plant efiluent streams should be man aged and controlled in a manner consistent with this goal.
B. Monitoring Streams On a regular basis consistent with plant sit
uations, ail effluent streams should be analyzed. The procedures for performing the necessary analy ses are contained in Section ft. Analysis of Water and Sediment for Polychlorinated Biphenyls. This procedure or its equivalent should be used.
C. Methods for Minimizing Effluent
Stream Contamination
The ideal approach is to totally isolate all
effluent streams that could be contaminated with
askarels during manufacturing processes and pre-
'vent them from being discharged Irom the plant.
Carbon adsorption, limestone beds, and solvent
extraction are techniques which can be applied to
reduce the askarel content of effluent streams. These techniques may be most useful in cleaning
up water used in plant processing and to permit
recycling.
"
V. SCRAP DISPOSAL PROCEDURES
The manufacture and use of capacitors involve processes which produce askarel-saturated solids and liquids containing or composed entirely of askarel, which should be disposed of as wastes. Specific sources of these materials appear through out this document but may be placed into three categories:
MUNS 0420ZZ
ANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OP A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
1. Capacitor units impregnated with askarcl, production and field rejects,
2. Manufacturing process liquid wastes con taining askarcl.
3. Solid waste purposely or accidently saturat ed with askarel.
Disposal should be done in a manner which is consistent with proper concern for the environment Md which mit>imi2e$ any release of askarels to the environment.
A, Disposal of Capacitor Units Scrap capacitor units can be generated during
manufacturing processes or during field service.
Production rejects arc those capacitors which arc rejected after the impregnation process in the course of production by the capacitor manufac turer, They may ,be rejected for mechanical or electrical reasons, or because of obsolescence.
Field rejects are those units wluch are re jected or which, for other reasons, arc to be scrapped after shipment Irom the plant where they were manufactured.
1. Production Rejects--'Rejected capacitors in capacitor manufacturing plants represent a concentration of askarcl. It is important dial their disposition be made in a manner consistent with proper concern for the en vironment, Therefore, capacitors should be disposed of only in supervised dry land fill sites which meet all applicable State requirements.
Care sltouitl be exercised in insure that no Ion of liquid will occur during transportation ' to the disposal sire.
Incineration of scrap capacitors in facilities designed to accept such solids should provide an alternative means of disposal as such services become available in the future.
2. Field Rejects--Small capacitors (defined as
containing less than 2 pounds of askarcl) arc
practically always used as components in
other electrical or electromechanical equip
ment. Typical examples of large quantity
usage of such capacitors arc in fluorescent
lamp ballasts and residential air conditioning
equipment. Failure of such capacitors may
result in scrapping of the device of which it
U a part (as in a fluorescent ballast) or re
placement and scrapping of the ihdlvidual
capacitor (as in a room air conditioner).
However, die majority of such capaciton do
not fail in service, but are scrapped as a
result of wearing out or obsolescence of the
devices in which the capacitors ate used as
components. Thus, the matter of disposal
Is characterized by a low concentration of
small quantities of askarel throughout the
country and, indeed, throughout the world.
Fortunately, the nature of the devices and
equipment in which such capacitors are used
is such that they arc normally disposed of
in dry landfills as a matter of convenience.
Since it is impractical *t p^sent to exerflsc-
any meaningful control over The disposition
of the bulk of such devices and equipment,-
it is Imperative'that askarel used for im- '
pregnating small capacitors' be limited-'ro
. the tecemly introduced type which conraiT#,-""
a typical concentration of 0,4, percent et 'T*?
the higher colling homologs. "* . *
~
Large capacitora (those Incorporating more **- .
than 2 pounds of askarej)' shoultl bc disposed *
of according to the procedure (oi production ,
rejects (see par, A. 1).
.
y<-&' .
Monsanto Method T-02302.
*
.*
` Sectidn 2 Page 7
HONS 042023
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
B, Plipoial of Liquid Wastes All wine askarcl or liquid wastes containing
askaral should be disposed of in accordance with one of (lie following procedures:
1. Incineration--Preseni knowledge Indicates that proper incineration must involve a suitable balance between dwell time and temperature in the incinerator plus oxygen availability and, finally, suitable scrui>* ben to remove the HCi which will be formed; c.g., (1) 2-second dwell time t 2000*1 and 3 percent excess oxygen in Stack gas; (2) 1 1/2-sccond dwell time at 2700*F and 2 percent excess oxygen in tack gas.
These facilities should meet die applicable requirements of the State in which they are located and should control effluents within the limits set forth in this document.
c. Containers used for this purpose should not be used for any other materials or retired from service until they arc com pletely cleaned. Any solvents used In cleaning diese containers will be con taminated with askarcl and should be disposed of according to the same pro cedures herein described.
C. Disposal of Solid Wastes (Sec Par. A for Scrap Capacitors) All solid wastes wltich have been saturated
with askarcl should be disposed of by die following procedure:
1. The saturated wastes should be placed into leak-proof containers and transported to a supervised dry landfill site meeting State requirements. Alternatively, they can be disposed of by incineration in State-approved facilities.
2, Toxic and Hazardous Waste Disposal SitesCertain landfill sites have been classified by State and Federal Governments as suit able for the disposal of toxic and hazard ous liquids. Where such approved sites exist, they may be used for the disposal of liquid wastes described in tills document. (See Section 4.)
2. Solid absorbents used for spills can be dis posed of uncontained in the supervised dry landfill site; transport to die site should be in closed containers. Alternatively, in cineration can be used in accordance with par. B (See Section 4 for facilities).
3. Packaging and Sltipmcnt--
a. Transportation to the disposal facility sltould be in containers which will pre vent leakage and accidental loss of askarcl to the environment.
b. Containers should be labeled as to contents and precautions relative to loss to the environment.
Section 2 Page 8
VI. LABELING
Capacitor units vary greatly in size and in end use or application. Small capacitot units arc fre quently applied as a component of another piece of equipment such as a fluorescent lighting ballast, a roadway or area lighting luminaire, a motor, etc, in such applications a label on the capacitor unit referencing approved disposal procedure would not ! normally be visible when the piece of equipment is disposed of.
HONS 04202**
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
For tire foregoing reasons the method of providing disposal instructions for small capacitors and large capacitors is treated separately.
1. Small Units (Incorporating Less Than 2 Pounds of Askarel)-- Small capacitors arc de fined as those which contain askarel in quan tities up to about two (2) pounds each and In which die free liquid does not exceed 0.4 pound. They arc hermetically sealed in me tallic eases* Such capacitors are applied as a component of a larger piece of equipment. Attacliing a label to such equipment refer encing this Guideline or describing disposal procedure* would be of limited practical value.
'a. Large Capacitor Units (Incorporating More Than 2 pounds of Askarel)--The capacitor manufacturer should affix a label in a con spicuous place, referencing this document
or describing disposal procedures consistent with it. This label should contain, as a minimum, the following Information:
CAUTION
THIS CAPACITOR CONTAINS A POLY CHLORINATED BIPHENYL (PCB). TO AVOID POSSIBLE ENVIRONMENTAL CON TAMINATION, IT SHOULD BE DISPOSED OF ONLY IN SUPERVISED DRY LANDFILL AREAS MEETING STATE REQUIREMENTS OR IN INCINERATION FACILITIES DE SIGNED FOR DISPOSAL OF PCB'S.
SEE AMERICAN NATIONAL STANDARDS
INSTITUTE GUIDELINES C107.1- (
)
FOR FURTHER INFORMATION. (WHEN
APPROVED, COPIES WILL BE AVAILABLE
FROM ANSI. 1430 BROADWAY, NEW YORK.
NEW YORK 10018.)
Section 2 Page 3 MQNS 04^5
o
o
GUIDELINES FOR HANDLING AND DISPOSAL OF CAPACITOR- AND TR A N S F O R M E R-G R A D E ASKARELS
CONTAINING POLYCHLORINATED BIPHENYLS
SECTION 3 TRANSFORMER GUIDELINES
o
HONS 041026
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
SECTION 3 TRANSFORMER GUI DELINES
l, GENERAL GUIDELINES
A. Definitions-- Types of Transformer Askarcls Tlic term askarcl generally describes a broad
class of nonflammable synthetic chlorinated hydro carbon insulating liquids widely used in transformers, reactors, and accessory equipment operated at power frequencies. Askarels of various compositional types arc in use Qor tire general properties and types, sec ASTM Specification (or Chlorinated Aromatic Hy drocarbons (Askarcls) for Transformers, D 2283}. Under arcing conditions die gases produced, while consisting of predominantly noncombustiblc hydro gen chloride, can contain varying amounts of com bustible gases depending upon die askarcl type.
The following trademarks arc used by electrical manufacturers 10 designate die askarcls used in their products:
Asbcstol Chlorcxtol inertccn No-Flamol Pyranol Saf-T-Kuhl
B, Safety Precautions Based on about forty years of safe industrial
usage, askarcls have been considered as relatively harmless materials to humans. There lias been no known instance of human injury when askarcls arc used under die normally prescribed conditions of precaution and handling.
Although it has been generally thought that ex posure to askarcls is not hazardous provided simple precautions arc taken, exposure should still be avoided and minimized.
1, Vapors-- The odor of askarcl is noticeable well below the maximum safe air concen trations. Depending upon die composition of the askarcl used, from 0, & to 1.0 milli gram per cubic meter of air has been de termined to be the upper safe level of ex posure during an 8>hour work day. (See American Industrial Hygiene Association Hygienic Guide Series-- January/February, 19C5.) The procedures for performing the necessary analyses are contained in Sec tion S, "A Tentative Procedure for the Determination of Airborne-Polychlorinated Biphenyls. " Tills procedure or its equiva lent shall be used.
Breathing vapor or fumes from heated askarels should be avoided. High concen trations of vapors can cause irritation of the eyes, nose, throat and upper respiratory tract. Provisions shall be made for ade quate ventilation and regulation of manu facturing operations to avoid open exposure of hot askarels (5 >*C or tiighcr). The gases produced when askarcl is decomposed by very high temperatures (such as that of an electric arc) in the presence of air or organic insu lating materials contain a high percentage of hydrogen chloride, and small percentages of other gases. Minute concentrations of tills combination of gases are very unpleasant and irritating, thus giving ample warning of their presence. If exposure to liigh concen trations of askarcls or its arced products is necessary under emergency conditions, an approved gas mask of the organic canistertype or self-contained breatliing apparatus must be worn. Such exposure should be under the surveillance ol other personnel capable of rescue in ease of accident. U the odor of askarcl or its arced products is detected by the person wearing prntet bvc
Section 3 Page 1
MOMS 04!0i7
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA.
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
equipment, he should immediately go into fresh air. All gas masks, respirators and replacement parts should have Bureau of Mines approval and be maintained on a tegular schedule in accordance with the manufacturer's recommendation.
2. liquid--Unlike mineral insulating oil, there is no fire hazard in handling askarcls. A limited solvent action (similar to that for paint thinner) on the fats and oils of the skin with prolonged contact may lead to drying and chapping of the skin. As with insulating oil, some people are alletgic to askarel and continued exposure may result in skin irritation. Both the liquid and vapor arc moderately irritating to eye tissue.
Operating procedures should require avoid* ance of contart with any ajkarcls. The use of porous gloves which can absorb and retain askarcls is to be avoided. Resistant gloves and aprons of die neoprene, polyethylene, viion type should be used if contact is un avoidable. In ease of spillage on the cloth ing, the clothing should be removed as soon as practical, the skin washed and die cloth ing laundered.
Medicinal washes or mild detergents followed by dre application of cold cream will reduce die irritation resulting from die contact of an open cut or abrasion widi askarcL
Safety glasses widi side shields or a face shield should be worn when handling askarcls. Eyes whit It have been exposed to liquid askarel should be irrigated immediately widi large quantities of running water for lf> min utes and then examined by a physician if die irritation persists. (A drop of castor oil tins been found to reduce irritation.)
Section 3 Page 2
Persons developing a skin irritation or respir atory tract irritation while working with askarels should be placed under supervision of a physician.
Ingestion or swallowing of askarels is not generally regarded as a problem of the in dustry. Should accidental ingestion occur, a physician should be consulted. Hands should be washed widi warm water and soap before eating, drinking, smoking or using toilet facilities.
C. Transport Container Marking Any container such as tank cars, tank trucks,
drums, cans, etc., used to transport transformer askarels, new or used, should be labeled with the following:
CAUTION
THIS PRODUCT CONTAINS POLYCHLORINATED BIPHENYLS (PCB'S). CARE SHOULD BE TAKEN TO PREVENT ENTRY INTO THE ENVIRONMENT THROUGH SPILLS. LEAKAGE, USE. VAPORI ZATION, OR DISPOSAL Or LIQUID OR CON TAINERS. AVOID PROLONGED BREATHING Or VAPORS OR MISTS. AVOID CONTACT WITH EYES OR PROLONGED CONTACT WITH SKIN. IF SKIN CONTACT OCCURS, REMOVE BY WASHING WITH SOAP AND WATER. FOL LOWING EYE CONTACT. FLUSH WITH WATER. IN CASE OF SPILLAGE ONTO CLOTHING, THE CLOTHING SHOULD UE REMOVED AS SOON AS PRACTICAL. SKIN WASHED. AND CLOTHING LAUNDERED.
P. Receiving, Handling and Storage of Askarcls Askarcls arc shipped in tank cars, tank trui ks,
steel drums, moral cans and test sample containers. When received, all containers should be impeded for leaks.
NO NS CHiOia
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
1. Storage Tanks--Storage tanks should be erected so that inspection can be made for leaks or spills. Construction should be such dial inadvertent leakage or spills arc pre vented from reaching streams and sanitary or storm sewers.
2. Tank Cars and Tank Trucks--All bulk ship* ment equipment should be inspected for leaks immediately upon receipt. Drain pans mutt be provided to prevent spillage from unload ing hoses and connections. Atkarel liquid collected in drain pant should be placed in "SCRAP ASKAREL" drums for disposition.
3. Steel Drums, Cans, and Test Sample Coirtaincr^-On delivery, all such s/iipmcnts should be carefully inspected for leaks. The containers should be stored indoors in an area especially selected for this purpose. A curb should enclose the area to provide a basin for containing the askarel from one or more containers should the containers be damaged. The area must not have a drain which is connected to a sanitary or storm sewer.
If an Indoor storage area is not possible, the containers should be stoted under a lean- to.
E. Water Effluents--Sampling, Concentration limits and Analytical Procedures
The industry goal is to eliminate askarel in plant water effluent streams. However, it is rccogniacd that existing drain systems from man ufacturing plants, repair shops and installation sites may be contaminated as a result of past practices. Other sections of cilia Guide provide that no askarel wastes of any kind be disposed of In any water effluent streams and that accidental Spills be prevented from getting into such streams.
1. Concentration Limits--The 1972 EPA pro posals are to keep PCB levels in rivers and lakes below 0.01 parts per billion. Plant effluent streams should be managed and controlled in a manner consistent with this goal.
2. Monitoring Streams--All plant effluent streams should be monitored on a regular basis, consistent with plant situations* The procedures for performing the neces sary analyses are contained in Section o, "Analysis of Water and Sediment for Poly chlorinated Biphenyls." This procedure or its equivalent shall be used.
3. Methods for Minimizing Effluent Stream Contamination-- The ideal approach is to totally Isolate all effluent streams that could be contaminated with askarcls during manu facturing processes and prevent them from being discharged from the plant.
F. Disposal Procedures and Services
1. Sources of Materials Requiring Special Handling and Disposal Procedures--liquids containing PCB's and solids containing or contaminated with PCD's may be obtained from any of the following sources: transport containers, transformer manufacturing processes, in-test failures, liquids con taminated beyond reclamation, in-scrvicc transformer leaks and failures, askarclfilled transformers scrapped for any reason, etc,
2. '
Classification for Disposal of Materials Containing PCB'S--In general, there are three types of materials requiring disposal: liquids, burnable solid materials contain ing PCB's and nonburnablc solid materials contaminated with PCB's,
Section 3 page 3
HONS 04Z029
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
a. Liquids. Liquids containing PCB's re quiring disposal by high-temperature incineration may consist of the follow ing:
(1) PCB's contaminated with mineral oiL
(2) Mineral oil contaminated with PCB's.
(3) Nonreclaimable contaminated trans former askarels, arced askorels, askarels from manufacturing spills, and sump accumulation, etc., rich in PCB's. and askarels from holding basins, drip and drain pans, wash ings, sample jars and containers, etc.
b. Burnable Solid Waste Material Contain ing PCB's. These materials can be dis posed of by high-temperature incinera tion and consist of cellulosic materials, rags, pressboard, wood, sawdust, fuller's earth in bulk or in cloth bags, blotter papers, nitrile or cork gaskets, etc.
c, Nonburnable Solid Waste Materials Containing or Contaminated With PCB's. These materials may consist of coll structures, steel, copper, alu minum filter units of die steel mesh construction type, askarel drums, cans, etc.
Materials of dtis nature should be allowed to drain with die liquid collected in drip pans, etc. Further removal of adhering PCB'S can be accomplished by washing or solvent extraction wills kerosene or
Section 3 Page 4
odier approved washing liquids such as perchloroctbylene or trichloroethylene. Accumulated liquids can be disposed of as indicated in par. F. 2. a. Solid ma terials may be handled as normal scrap.
3. Shipment of Scrap Liquids for Disposal-- All liquid scrap material should be placed in appropriate metal transport drums, prop erly labeled, for shipment to a company offering an acceptable disposal service.
4. Shipment of Burnable Solid Waste Ma terial Containing PCB's for DisposalMaterial of this type should be placed in open head drums with suitable closures and with the drum properly labeled for shipment to a company offering an ac ceptable disposal service.
5. Liquid and Solid Waste Disposal Service Organizations--
a. General Disposal of askarels and askarel-soaked materials should be accomplished by means in which there Is no significant release of askarel to the environment. At present, disposal is accomplished by carefully-controlled incineration of liquids and soaked soft ware, and by controlled landfill burial of apparatus and other hardware from which askarel has been previously drained and washed.
Present knowledge indicates that proper incineration must involve a suitable balance between dwell time and tem perature in the Incinerator plus oxygen availability and, finally, suitable scrub bers to remove the HC1 which will be formed; e.g., (1) 2-second dwell time at 2000*P and 3 percent excess oxygen in stack gas; (2) 1 1/2-second dwell time at 2700T and 2 percent excess oxygen in stack gas.
HONS 042030
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
On IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSJOE OF NEMA
These facilities should meet the appli cable requirements of the Slate in which they are located and should control efluents within the limits set forth in this document.
Controlled landfill or deep-well dis posal can be used where permitted by Federal, State and local regulations,
b. Costa. In addition to the normal costs of collecting scrap liquids and solids for disposal, additional costs borne by the owner of such scrap include shipping containers, cost of transport to the dis posal service organization, and a dis posal fee usually based upon a per gallon or per pound charge.
c. Disposal Services. Organizations offering disposal services are listed in Section 4, including their location, facilities available, types of material handled, and disposal procedures used. Speci he shipping directions, disposal procedures and costs should be obtained from tile organization.
II, SPECIFIC GUIDELINES
A. Transformer Manufacturers, Service Shops, etc, ^Housekeeping
It is necessary to assume that in filling equip ment with askarei and during further handling of this equipment an askarei spill may occur. There fore, it Is necessary to provide facilities and a pro cedure for clean-up to prevent contamination.
1. Askarei Filling Area--
a. The location of the askarei filling area should be adjacent to tire test area and final shipping area to minimize the danger of damage of units during han dling.
b. The main manufacturing area for fill ing equipment with askarei should be provided with impervious surface floors or suitable basins so constructed that any inadvertent leakage or spills are prevented from reaching streams, san itary, or storm sewers. All askarelhandling equipment such as pumps, hoses, etc., shall be of the askareiresistant type.
c. Drip pans shall be provided for hose connections and Ailing valves.
2. Special Containers fot Scrap Materials--
a. Drums labeled SCRAP A5KARL should be available for handling all spilled and waste askarei from sumps, failed units, drip pans, sample jars, etc.
h. Open-head drums with suitable closures and labeled "SCRAP BURNABLE ASKAREL WASTE" should be available for handling contaminated cellulose in sulation. rags, paper pressboard, wood, gaskets, sawdust, etc.
c. Separate containers for handling steel, copper, and aluminum, each adequately marked, shall be provided for the com ponents of contaminated core and coil assemblies. These containers are re quired for the various materials when repairing or scrapping assemblies.
d. Container for supplies of material for absorbing small askarei spills or clean-up of larger spills should be provided.
Section 3 Page 6
HONS 042031
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA.
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION 8Y ORGANIZATIONS OUTSIDE OF NEMA
3, Conditioning of Askarcls--
a, Askarci Conditioning Equipment. The conditioning unit should be located either in the storage tank area or the main transformer manufacturing area for filling with askarci,
b. Fuller's Earth. Conditioning of new askarel or recycled askarci requires fuller's earth treatment. The spent fuller's earth in cartridges or bags, when replaced, should be allowed to thoroughly drain over drip pans to re move as much liquid askarel as possible. The cartridge units of steel mesh con struction should be placed in the "STEEL CONTAMINATED WITH ASKAREL" con tainer for disposition. Cloth bags filled with fuller's earth should be placed in tile "SCRAP BURNABLE ASKAREL WASTE" container for disposition.
4. Tcardown of Units for Repair or Scrap--
a. Drain all askarci from the unit either into a holding tank fur reuse or into the drum labeled "SCRAP ASKAREL" for disposition, and then allow suffi cient time for all of the askarci to drain from the core and coils.
b. Remove the core and coil assembly from the transformer. Sufficient ab sorbent material should be placed on the floor to absorb any askarci fluid that still drips from the transformer.
c. Place all materials in the appropriate salvage containers during the dis mantling for later disposition.
d. All used materials, including rags, sawdust, tape, etc., regardless of quantity, shall be put into the appropriaic containers for disposition.
Section 3 Page d
B. Transformer labeling
1. New Transformers--All new transformers that contain PCB's shall have a label of adequate durability permanently and prominently at tached to the tank by the manufacturer, giving adequate warning and instructions. A suggested label includes the following:
CAUTION
THE INSULATING LIQUID IN THIS TRANS FORMER CONTAINS POLYCHLORINATED BIPHENYLS (PCB'S). CARE SHOULD BE TAKEN TO PREVENT ENTRY INTO THE ENVIRONMENT. IN CASE OF MALFUNCT ION OR LEAKS, CONSULT THE INSTRUC TION MANUAL OR THE MANUFACTURER.
2. In-service Transformers--The transformer manufacturer should make available suitable labels with a similar warning as shown in par. B. 1 for use on existing transformers.
C. Transformer Users--Shipping, Installation. Maintenance, Sampling, Appar*jus Disposal_____________________________
1. General-- Askarel-filled transformers are delivered to customers as sealed units from which there is no escape of askarel under normal operation. While certain types of equipment failures can permit loss of some askarel to the environment, such cases arc extremely rare.
2. Transportation and Receiving--l nmediatcly upon receipt of the equipment and following any transportation or handling accident wiuiit could affect the integrity of the tank, busli-
MQNS 042032
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA.
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
ings or radiators, the transportation vehicle, tank and fittings should be examined for any leakage or spillage that may have occurred in shipping* If leakage is evident, the cause should be corrected and the spillage soaked up with absorbent materials such as sawdust, followed by a clean-up of the affected area with rags soaked with kerosene or other ap proved solvent such as perchloroethylene or trichloroethylene. All materials used should be collected for proper disposition as described in Section 3 Part I. par. F. "Disposal Pro cedures and Services."
3* Installation and periodic Inspection--'Fol lowing installation, tire unit should again be inspected for any damage or leakage. It is recommended that periodic in-service Inspections be made for any leaks.
4, Filling. Filtering, or Drying Askarel-- Most askarel units arc shipped with the proper amount of askarel but if it becomes neces sary to top off a unit, the manufacturer's instructions should be followed.
If It Is necessary to dry or fuller's-earthcreat an askarel unit, the manufacturer's instructions should be followed. When fil tering or conditioning askarel, all of the
precautions previously described (or drip pans, proper disposal of filter media, etc., apply.
5. Sampling--It is common practice to sample askarel from a transformer for periodic maintenance testing. As previously de scribed. such samples should be taken in a manner to avoid any contamination of tile environment. Washings should be col lected for proper disposal. Field and labo ratory test samples, washings, etc., should also be collected for proper disposal.
6. Transformer Disposal-- The ultimate dis posal of an askarel-filled transformer may be accomplished in either of two ways:
a. Complete drainage and dismantling with the proper disposal of the askarel and askarel-soaked components as de scribed earlier in Section 3, Part l, par. F, " Disposal Procedures and Services."
b. Disposition of askarel transformers by means of junk or scrap dealers should be avoided unless a transformer is first drained, followed by soaking the interior with a suitable solvent. Accumulated liquids and washings are to be disposed of as described earlier.
Section 3 Page 7 MQNS 04*03.3
o
o
GUIDELINES POR HANDLING AND DISPOSAL OP CAPACITOR- AND TR A N S FORM E R-C R A DE ASKARELS
CONTAINING POLYCHLORINATED BIPHENYLS
SECTION 4 DISPOSAL SERVICES
O
nans 04^034
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
SECTION 4 DISPOSAL SERVICES
In addition to die supervised dry landfill sites which may be used for the disposal of askarelcontalnfng scrap, (he following additional known facilities and scrvircs have been established, and others may be available.
Clicm-Trol Polotion Services, Inc,, 4818 Lake Avenue BlaidcU, New York 14219 Phone 716-82G-5850
This organization has facilities and services capable of handling:
1. Liquids--Askarcls alone or mixed with solvents or oils. Disposal by high tem perature incineration.
2. Solids (Software)--Askarel-soaked com pounds, rags cartons, absorbing earths, etc. Disposal by incineration or scientific landfill.
3. Solids (Hardware)--Capacitois, transformer tanks, cores, askarel-soakcd metals. Dis posal by scicndfic landfill. Has solvent extraction capability.
Monsanto Company 600 No, Lindbergh Boulevard St. Louis, Missouri 631 GO Phone 314-094-3332
This organization has facilities and services capable of handling askarcl liquids alone or mixed with other oils or solvents by high-temper ature incineration. Liquid is pumped through a gun with atomizing steam into incinerator. Temperatures arc maintained at 20OO-2'OO*!: with auxiliary natural gas. Exit gases arc quenched to 1 SOT by contact with water. Cas is then passed through a high-energy venturi scrubber for removal
of particulates. Before exhausting to air fllO*F), gases arc passed through a packed column scrubber to remove HCL
Nuclear Engineering company
Eastern Division P. O. Box 146 Morehead, Kentucky 40351 Phone 606-784-6611
Disposal Division Sheffield, Illinois Phone 815-454-2624
This organization provides containerization, transportation and disposal services of all liquids and solids (including hardware). Disposal is in controlled chemical and scientific landfill area, AEC licensed for radioactive waste disposal. Has two West Coast locations in states of Washington and California in addition to above.
Rollins-Purle, inc.* 1 Box 3349 Wilmington, Delaware Phone 302-478-5150
19899
This organization has facilities and services capable of handling:
1. Liquids--Askarcl alone or mixed with solvents or oils. Disposal is by hightemperature incineration.
3. Solids (.Software)--Askarel-soakcU com pounds, rags, cartons, absorbing earths,
. etc. Disposal is by incineration ai com bustion temperatures up to 2300*1'. In cineration gases are scrubbed, and en trained solids removed before exhausting to air.
Section 4 Page 1
MGNS 042035
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
Disposal facilities are available at the following locations:
Rollins-Purle, Inc. Route 322 Logan Township Bridgeport, New Jersey
08014
Baton Rouge:
RolUns-Purle, Inc. Scenic Highway & W, Cheatham Lane Scotlandvillc East Baton Rouge Parish Louisiana 70807
Houston:
Rollins-Purle, Inc. Tidal Road & Highway 134 Deer Park, Texa* 7753G
Suction 4 Page 2
O1*
I
o
GUIDELINES FOR HANDLING AND DISPOSAL OF CAPACITOR- AND TR AN S FORM ER-G R A DE ASKARELS
CONTAINING POLYCHLORINATED BIPHENYLS
SECTION 5 APPEN DIX ANALYTICAL PROCEDURES AND LABORATORY SERVICE ORGANIZATIONS
O HONS 042037
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARO DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OP NEMA
SECTION 5 APPENDIX
ANALYTICAL PROCEDURES AND LABORATORY SERVICE ORGANIZATIONS
Analytical procedures for determining PCB's in air, water, and sediments are given in Parts 1 and 1[ of Section 5.
The following laboratories are representative of those offering services for PCB analyses:
Carus Chemical Corp, 1375 Eighth Street LaSalle. Illinois 61301 phone 815-223-1500
Umnetics. Inc. (Subsidiary of Carus Corp.) 6132 West Fond du Lac Avenue Milwaukee, Wisconsin 53218 Phone 414-461-9500
Gollob Analytical Service Corp. 47 Industrial Road Berkeley Heights, New Jersey 07922 Phone 201-44-3331
I. A TENTATIVE PROCEDURE FOR THE DETERMINATION OP A1RDORXE-POLYCHLORINATED DIPHENYLS
A. Scope Tliil procedure is based on techniques used by
rite Monsanto Industrial Chemical Company for the isolation and determination of polychlorinated biphenyls (PCB's) in water, soil/sediment, and biological materials.
Absolute confirmation ol PCB structures is not obtained wills this method. Where needed, addi tional structure proof should be obtained using techniques such as mass spectrometry to further identify GO fractions.
B. Principle Airborne PCB's arc absorbed in toluene by
drawing the air through one or more fritted bubblers or impingers in cylinders filled with toluene. After sampling a suitable amount of air, the scrubbing solvent is diluted or concentrated, and interfering components, if present, arc removed by chemical treatment and column absorption chromatography. The amount and type of PCB's present is deter mined by electron capture gas chromatography (EC/CC).
Section 5 page j
MONS 042038
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
C, Reagents Hexane.................... . Toluene.................... Sodium sulfate, Alumina adsorption
Distilled water ............................................................ Sulfuric acid........................................ .......................... Potassium hydroxide................................................... Ethanol............................................................................. 2.5ft (w/v) alcoholic potassium hydroxide .... 9/1 (v/v) sulfuric acid-water......... .. PCB Standards.......................................................... Section 5 Page 2
Nanogradc, Mallinckrodt Chemical Works, Catalog No. 4159.
Nanograde, Mallinckiodt chemical Works, Catalog No. 8092.
Anhydrous, granular; AR grade, Mallinckiodt Chemical Works, Catalog No. 8042. Heat at 400*C for 1 hour prior to use.
(For chromatographic analysis) 60/200 mesh, Fisher Scientific Company, Catalog No. A540. Heat at 400*C for a minimum period of 4 hours and deactivate with 5ft (w/w) distilled water.
Alumina column preparation: Fill a chromato graphic column witli hexane up to die point where the reservoir joins the column and push a glass wool plug to the bottom with a glass rod. In a 50 ml beaker measure 35 ml of de activated alumina ( a* 30g), and pour this slowly into the column. Tap or vibrate lire column to settle the alumina and top the alumina with 2-3 cm of anhydrous sodium sulfate. Wash the column with 50-100 ml of hexane prior to the addition of the sample.
Extracted with hexane to remove hexane soluble electron capturing impurities.
Analytical Reagent Grade, SG = 1.84.
Analytical Reagent Grade.
Formula 2B.
Dissolve 12.5 grams of AR grade KOI! in 500 ml of ethanol.
Carefully add 270 ml of AR grade sulfuric acid to 30 ml of distilled water in a 500 ml iced beaker.
Aroclor 1016, 1221. 1242, 1248, 1254 and 1260. See Fig. 5-3 through 5-9 (pages 17 to 23).
,,ONS 042039
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
D, Apparatus
1, Gas scrubbing bottles, high form, ground glass joint, fritted coarse discs,
2. Separatory funnels equipped with ground glass stoppers and Teflon stopcocks: 125, 250, 500. 1000 and 2000 ml capacities.
i
7. Hot plates, Corning PC-100: Fisher Scientific Company.
8. Water bath, Thelco, Precision Scientific, Model No. 84, Fisher Scientific Company.
9. 10 ji 1 Hamilton syringes. Catalog No. 701N.
3, Kundcrna-Danish evaporative concentrators, 500 ml capacity equipped with 3-ball Snyder columns and graduated 5 ml ca pacity vials: Ace Glassware Company, Catalog No, 6707.
10. Dry test meter or wet test gas meter. 11. Laboratory vacuum pump. 12. Rotating vacuum evaporator.
4. Chromatographic columns, glass, 10" x 20 mm (OD) with a 5" x 50 mm (OD) reservoir at the top, equipped with Teflon slopeoc ks.
5, Flat-bottomed boiling flasks, 125 ml ca pacity: Acc Glassware Company, Catalog No. 6806. Code - 04.
6. Liebig condenser, 200 mm In length: Acc Glassware Company, Catalog No. 5015, Code - 12.
13. Usual laboratory glassware.
E. Sampling (See Fig, 5-1) The air to be sampled tor airborne PCB's is
drawn through a gas scrubbcr(s) and a dry test i meter using a laboratory vacuum pump. The sam
pling (low rate is controlled by bleeding in air via I a needle valve located between die pump and the j meter. At the end of the sampling period, the
metered gas volumes are corrected lor temperature : and pressure to cubic meters at 25*c and 7d0 mm
"S-
Sample _ inlet
Gas Scrubbcr(s)
$ Air Bleed
Dry Test Meter
.Jt, [_J
Laboratory Vacuum Pump
Exhaust
Fig. 5-1 SAMPUNG TRAIN
Section 5 Page 3
MONS 042040
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA.
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
It Is Important to note that neither the capacity nor the efficiency of the gas scrubbcr(s) for removal of airborne PCB's have been experimentally eval uated. For this reason, it Is best to minimize the sampling flow rate and maximize the sampling time period to obtain measurable amounts of pBC's. When high How rates must be employed or a larger capacity may be needed, it is recommended that several gas scrubbers be used in tandem.
It is cautioned that, until the efficiency and capacity of the toluene gas scrubber has been ex perimentally established, this procedure should be only used to measure relative PCB levels sampled under equivalent conditions.
F, Procedure
1. After scrubbing the desired amount of air, record the metered volume, pressure, and temperature.
2. Quantitatively transfer the scrubbing solvent to a round-bottomed flask and reduce the volume to approximately 2 ml by rotary vacuum evaporation.
3. Quantitatively transfer the concentrate to a 30-ml beaket with the aid of several small portions of toluene.
4. Inject a fraction of a M 1 of the concen trate into the gas chromatograph to check for Interferences and determine the approx imate level of PCB's present. If no Inter ferences are present, dilute or concentrate the sample to a known volume, as deter mined by the electron capture chromato gram, and proceed with the gas chroma tographic analysis.
5, If interferences arc present, proceed wi h die chemical treatment and column chro matographic clean-up procedures.
Section 5 Page 4
6. Transfer the concentrate to a 125-mi ex traction flask with the aid of several small portions of solvent.
7. Evaporate the concentrate just to dryness with a gentle stream of dry filtered air and add 25 ml of 2. 5% alcholic potassium hy droxide.
8. Add a boiling chip, put a water condenser in place, and allow the solution to teftux for 45 minutes.
9. After cooling, transfer the solution to a 250-ml separatory funnel with the aid of 25 ml of distilled water.
10. Rinse the extraction flask with 25 ml of hexane and add it to the separatory funnel.
11. Stopper the separatory funnel and shake vigorously for at least 1 minute. Allow the layers to separate and transfer the lower aqueous phase to a second sepa rator funnel.
12. Extract the saponification solution with a Second 25-ml portion of hexane. After the layers have separated, add the first hexane extract to the second separatory funnel and transfer the aqueous alcohol layer to the original separatory funnel.
13. Repeat the extraction with a tliird 25-ml portion of hexane. Discard the saponifi cation solution and combine the hexane extracts.
14. Carefully add 25 ml of the sulfuric acid - solution (9:1 concentrated sulfuric acid/ water) to the hexane extracts.
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
15, Stopper the separatory funnel and shake vigorously for at least 1 minute. Allow tire layers to separate and discard die lower aqueous acid layer. Repeat this step until tire acid layer is colorless.
16, Wash the hexane with a 25-ml portion of water. Discard the water wash.
17. Filter the hexane extract through a 4" funnel plugged with glass wool wluch is covered with a layer of sodium sulfate into a Kunderna-Danish evaporative con centrator.
18. Add a small boiling chip, put the Snyder column in place, and reduce the hexane volume to less than 5 ml by heating the apparatus in a 80-90*C water bath.
19. After cooling, remove the 5-ml graduated tube and transfer the hexane extract to an alumina adsorption column, washing it in with several 5-ml portions of hexane.
20. Carefully add 100 ml of hexane to the column reservoir and collect the total eluent in either a 250-ml volumetric flask or a Kunderna-Danish evaporative concentrator,
21. If the column eluent is collected in a volumetric flask, dilute to volume with hexane, and proceed with the gas chro matographic analysis.
22. If the column eluent Is collected in a Kunderna-Danish evaporative concentrator, reduce solvent volume, cool, dilute to volume, and proceed with gas chromato graphic analysis.
G. * Electron Capture Gas Chromatographic Procedure
Instrument........... F & M 402 Biomcdial Gas Chromatograph
Detector................ High Temperature Ni3
Election Capture Cell 6 mm x 6* Glass Column,
4% XE-60 on 80/100 mesh
Chromosotb W, HP, AW-DMCS Column Temper
ature ................ 160-190*C Detector Temper
ature ................ 300*C
Injection Port Temperature,. 195-215`C
Pulse...................... 150
Flow Rates ...... Helium Carrier *"vj 60 ml/min
Argon-Methane Purge ml/mm
120
Using EC/GC as the determinative step, inject in duplicate 1-10 p 1 of each solution into the chromatograph. By comparison with standard so lutions injected, in duplicate, under die same operating conditions, determine the amount and type of Aioclor using the individual or total peak height and area methods.
H, Sample Concentration Concentration of sample extracts is necessary,
prior to clean up by chromatographic or chemical means, to reduce sample size and increase sensi tivity. The prefetred method of concentrating allows minimum loss through volatilization or chemical decomposition and requites a minimum time. The three methods of solvent volume re duction most commonly used are evaporation by exposure to a stream of air, evaporation employ ing a Kunderna-Danish evaporative concentrator equipped with a Synder column, and evaporation under reduced pressure. All three techniques have been used without encountering any significant losses from volatization or chemical alternation.
Section 5 page 5
HONS 042042
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
1. Column Adsorption Chromatography and Chemical Clean Up
Silica gel. Morisil and alumina deactivated with 0, 1,0, 1,5, 2.0 and 5 percent water were investigated as adsorbents for die elimination of Interferences. Alumina (5% water) was found to be more effective and reproducible titan either silica gel or HorisiL The activity of alumina varies with age and lot; therefore. 5/i> water was added to die alumina, after heating for a minimum of 4 hours at 400*C, to insure a re producible activity.
Saponification and subsequent extraction of the sample widi sulfuric add is an effective way to remove a number of chlorinated hydrocarbon in terferences as well as other matrix interferences. PCB'i arc not affected.
J, Column Performance Column performance is the key to effective
gas chromatograpliic analysis and, as such, the choice of column materials is particularly im portant. Ideally, die support employed should be Inert, mechanically strong, and of high surface area. Chromosorb W, IIP, AW-DMCS fulfills these requirements and is recommended for dill work.
A variety of polar and non-polar liquid phases have been investigated. The following columns have been found to provide adequate separation, etc,, for use in PCB analysis by electron capture: 4% (w/w) DC-200, SI-06, OV-17. SE-30. SE-54, XE-GO, Apiezon L. and 6% Qr-1. DC-200 and XE-GO or Ql-l have been lound to be die most suitable of these liquid phases.
Another important consideration when working with an extremely sensitive detector and conse quently low levels of materials is column con ditioning, With polar phases such as XE-GO and
Section 5 Page 6
QF-1, operating a new column overnight at a temperature 20-50*c higher than that to be used during analysis results in a more stable column, A no-flow conditioning technique is employed to condition noti-polar columns. The column is purged with carrier gas, heated for 30 minutes at an elevated temperature without carrier flow and then cooled to room temperature. At die end of this cycle, the carrier flow is resumed and the conditioning Is completed as in the case of die polar liquid phase. Two precautions: during con ditioning, die column should not be connected to the detector, and one should not exceed the max imum safe temperature of the liquid phase.
Since all liquid substrates bleed to one degree or another and columns eventually degrade, all new columns should be characterized with two column performance indicators--die number of theoretical plates (N) and a tailing factor (T). p,p'-DDT is employed to check these parameters because it is known to degrade on "poor'' columns. In this manner, one can determine if the perform ance of a new column is satisfactory and when the column performance begins to fall off. A column is considered good if die number of theo retical plates per foot is on the order of 400-500 with tailing factors of 1.0-1.3. Calculation ol these parameters is shown in fig. 5-2, page 8. Additionally, there should be no significant ex traneous peaks upon injection ol a pure p. p'-DDT standard.
Other chromatograpliic conditions that can be adjusted are column temperature and flow rates. Although resolution of a mixture increases with decreasing temperature, a temperature should be chosen that allows the elution of all components witlun a convenient time period. The flow rates shown arc optimum fo. a given instrument, column and detector system. These should be adjusted il better results can be achieved.
HONS O^O1*3
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARO DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
Two gas chromatographic systems have been
used (or PCB analysis--1: & M Model 402 and
5750. Any sysicnt of instrument and column
suitable (or chlorinated pesticides is satisfactory
for PCB analysis. The use of the high temper
ature
electron capture cell is highly recom
mended. The ability to operate at higher tem
peratures prevents maintenance problems due to
contamination from liigh boiling components.
Class columns should also be employed.
K. Detection and Measurement Quantitative determinations employing the elec
tron capture detector arc non-stoichiometric measmenu made by comparing peak heights or areas for known concentrations with those for unknown compositions. Three variations of the peak height or area quantification procedures have been em ployed:
Cue l
-- EC gas chromatogram of PCB un known unchanged with respect to standard PCB with no evidence of Interferences.
Cue 11 -- EC gas chromatogram of PCB un known altered with respect to standard PCB with no evidence of Interferences.
Cue III-- EC gas chromatogram of PCB un known unchanged with respect to standard PCB with evidence of in terference.
The amount of PCB's in Cue 1 samples is deter mined by preparing a plot of the major peak height or area versus concentration. With Case 111 sam ples, a peak free from interference is used. When dominant interferences arc present, one or more of the chemical clean-up procedures is employed.
In all cues, the response of the electron cap ture detector must be linear for quantitative analysis.
L, Contamination In determining PCB's in biological materials
by electron capture gu chromatography, labora tory sources of contamination can be a major problem. The samples and extracts should never be allowed to conic in contact with materials other than glass, Teflon or metal. Laboratory glassware should be thoioughly washed with hut, soapy water, rinsed with distilled water, acetone. and then hexane. All equipment should also be rinsed again with hexane just prior to use. and blanks should be frequently carried through all steps of the procedures to insuic against die possibility of contamination.
M. Sensitivity
Two parts per billion.
Absolute sensitivity--0.5 x 10"^, grams.
Volume injected--5 jr 1.
final volume of extract--o mL
Sample size--
ml.
HONS 042044
Section 5 Page 7
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA.
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
1. Theoretical Plater, N
N 16 (*/y)2
Calculating Column Efficiency
2. Tailing, T
T - a/2b
Section 5 Page B
Fig. 5-2 COLUMN PERFORMANCE INDICATORS
OieiO'*5 RONS
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSCO STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
IU ANALYSIS OF WATER AND SEDIMENT FOR POLY CHLORINATED BIPHENYLS
A. Scope Thli methodology U used by the Monsanto Industrial Chemical Company for the determination of the
amount and type of polychlorinated biphenyls (PCB's) in water and sediment samples. Absolute confir mation of PCD structures is not obtained with this method. Structure proof can be obtained using addi tional techniques such as mass spectrometry to further identify the GC fractions.
B, Principle The PCB's in water and sediment samples are extracted into an organic solvent. Interfering compo
nents arc then removed from the extracts by chemical treatment and column adsorption chromatography. The amount and type of PCB's present is determined by electron capture gas chromatography (EC/CC).
C, Reagents
Hexane................................... ........................................
Nanograde, MalLinckrodi Chemical Works, Catalog No. 4159.
Acetonitrile................ ...................................................
Nanograde. Mallinckrodt Chemical Works, Catalog No. 2442.
Sodium sulfate......... ....................................................
'Anhydrous, granular.- AR grade Mallinckrodt Chemical Works, Catalog No. 8042. Heat at 4O0*C for 1 hour prior to use.
Alumina adsorption ........................,
(For chromatographic analysis) 80/200 mesh, Filhcr Scientific Company, Catalog No. A540, Heat at 400*C for a minimum period of 4 hours and deactivate with 5% (w/w) distilled water.
Alumina column preparation: Fill a chromato graphic column with hexane up to the point where dm reservoir joins die column and push a glass wool plug to the bottom with a glass rod. In a 50 ml beaker measure 35 ml of de activated alumina (/\-<3Qg), and pour this slowly into the column. Tap or vibrate the column to settle die alumina and top die alumina with 2*3 cm of anhydrous sodium sulfate. Wash the column with 50-100 ml of hexane prior to die addition of die sample.
(Continued)
MGNS 04G46
Section 5 Page 9
IAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
Distilled water Sulfuric acid Potassium hydroxide......... ..................... ................... Ethanol.,..,................................................ 2.5`ft (w/v) alcoholic potassium hydroxide ... 9/1 (v/v) sulfuric acid-water
PCB Standards.
Extracted with hexane to remove hexane soluble electron capturing impurities.
Analytical Reagent Grade, SG 1.84,
Analytical Reagent Grade.
Formula 28.
Dissolve rv> 12.5 grams of AR grade KOH in S00 ml of cthanoL
Carefully add 27Q ml of AR grade sulfuric acid to 30 ml of distilled water in a 500 ml iced beaker.
Aroclor 1242, 1248, 1254 and 1260. (See Fig. 5-4. page 18, and Tig. 5*6 through 5-9. pages 20 to 23.)
p. Apparatus
,
1. Separatory funnels equipped with ground glass stoppers and Teflon stopcocks: 125, 250, 500, 1000 and 2000 ml capacities.
2. Kunderna-Danish evaporative concentrators, 500 ml capacity equipped with 3-ball Snyder columns and graduated 5 ml ca pacity vials: Ace Glassware Company, Catalog No. 6707,
3. Chromatographic columns, glass, 10" x 20 mm (OD) with a 5" x 50 mm (OD) reservoir at the top, equipped with Teflon stopcocks.
6. Liebig condenser, 200 mm in length-. Ace Glassware Company, Catalog No. 5915, Code - 12.
7. Hot plates. Coming PC-100: Fisher Scientific Company.
8, Water bath, Thelco, Precision Scientific, Model No. 84, Fisher Scientific Company.
9. Reciprocating variable speed "thakcr, Eberbach Corporation, Fisher Scientific Company.
10. 10 p 1 Hamilton syringes, Catalog No. 701N.
11. 32 02 all-glass mortars and pestles.
4. Sintered glass filter funnels, 600 ml ca pacity, 90M.
12. 8" x 12" x 2" (2 1/2 qt> Pyrex baking dishes.
5, Flat-bottomed boiling flasks, 125 ml ca pacity: Acc Glassware Company, Catalog No, 689G, Code - 04.
Sections Page 10
13. U. S. Standard Sieve, No. 30, Fisher Scientific Company,
,
14. Usual laboratory glassware.
HONS
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA.
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
E Sampling It it to be assumed that a raUier wide variety
of sampling techniques may be employed in col lecting samples submitted for analysis. For this tcason water and sediment samples should be treated as follows:
1. Water--Where possible the entire water sample, including the container in which It was collected, should be extracted with hexane. With larger samples, where this Is not physically possible, die containers should be simply agitated and a 250 mi portion used for the analysis. (See par, F.)
2. Sediment--Any excess water should be de canted and die entire sediment transferred to a glass baking dish to air dry at room temperature. Hie dried material should be transferred from the dish into a mortar and ground. The ground sediment should be sieved, remixed, and a 250 g portion taken for analysis. (See par. G.)
F, Extraction of Water Samples
1, After agitating, transfer the entire aqueous sample or a 250 ml aliquot into a gradu ated glass cylinder. Record die volume of the sample and quantitatively transfer It to a separau>7 funnel widi distilled water.
2, Rinse the graduated cylinder with two 50-ml portions of hexane and add each to die separatory funneL
3, Stopper the separatory funnel and shake vigorously for at least 1 minute. Allow die layers to separate and transfer die lower aqueous phase to a second separa tory funneL
4* Extract the water sample a second time with a 50-ml portion of hexane. After die layers have separated, add tire first
hexane extract to the second separatory funnel and transfer die aqueous layer to the original separatory funnel,
5, Repeat the extraction with a third 50-ml portion of hexane. Discard the aqueous layer and combine die hexane extracts.
C. Filter die combined extracts through a 4" funnel plugged with glass wool which is covered with sodium sulfate. Collect die filtrate in a Kunderna-Danish evaporative concentrator, add a small boiling chip, put the Snyder column in place, and reduce the hexane volume to less chan 5 ml by heating the apparatus in a 80-90*0 water bath. (CAUTION: SOLVENT VAPORS MUST 8E VENTED TO A HOOD.)
7. After cooling, remove the 5-ml graduated tube and transfer the hexane extract to an alumina adsorption column, washing it m with several o-mi potaons of hexane.
8. Carefully add 100 ml of hexane to die column reservoir and collect die total eluent in either a 250-ml 'volumetric flask or a Kunderna- Danish evaporative concentrator.
9. If die column eluent is collected in a volumetric flask, dilute to volume widi hexane, and proceed with the gas cluomatograpluc analysis.
10, If tire column eluent is collected in a Kunderna'Danish evaporative concentrator, reduce solvent volume, cool, dilute to volume, and proceed with tire gas chro matographic analysis.
Section S Page 11
HONS OVZOtd
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS. FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
Q Extraction of Sediment and Soil Samples
1. Decant off any excess water and tranfer the entire sediment sample to a glass baking dish. Air dry at ambient temperature (heat should not be applied).
2* When dry, transfer the soil/sediment to a mottar and grind. Sieve the ground mate rial through a No. 30 mesh sieve and weigh 2S0 g (to the nearest 0.01 g) into a 16-oz narrow neck screw cap (aluminum foil liner) glass bottle.
3. Moisten the soil with water (sv 10 ml) and add 150 ml of acetonitrile. Cap the bottle tightly, and mechanically shake it for a minimum period of 1 hour.
4. Quantitatively transfer the acetonitrile ex tract into a 600-ml sintered glass filter fun nel containing a 1/4" layer of anhydrous sodium sulfare. collect the filtrate in a 600-ml beaker (vacuum filtration may be necessary).
5. After the acetonitrile has completely drained into the beaker, wash the bottle twice with 50-ml portions of acetonitrile, adding each wash to the funnel after tire previous wash has completely percolated through die sed iment.
6. Quantitatively transfer the extract to a Kunderna-Danish evaporative concentrator, add a small boiling chip, put the Snyder col umn in place, and reduce tire solvent volume to less than 5 ml by heating the apparatus in a 80-90*C water bath. (CAUTION: SOLVENT VAPORS MUST BE VENTED INTO A HOOD.)7
7. After cooling, remove tire 5-ml graduated tube and transfer the concentrate of extracts to a 125-ml extraction flask with the aid of several small portions of solvent.
Section 5 page 12
8. Evaporate the extract just to dryness with a gentle stream of dry filtered nitrogen and add 25 ml of 2.5% alcoholic potassium hy droxide.
9. Add a boiling chip, put a water condenser in place, and allow the solution to reflux for 45 minutes.
10. After cooling, transfer the solution to a 250 ml separatory funnel with the aid of 26 ml of distilled water.
11. Rinse the extraction flask with 25 ml of hexane and add it to the separatory funnel.
12. Stopper the separatory funnel and shake vig orously for at least 1 minute. Allow the layers to separate and tianticr the lower aqueous phase to a second separatory (unneL
13. Extract die saponification solution with a second 25-ml portion of hexane. After the layers have separated, add the first hexane extract to the second separatory funnel and transfer the aqueous alcohol lay er to the original separatory funnel.
14. Repeat the extraction with a third 25-ml portion of hexane. Discard die saponifi cation solution and combine the hexane ex tracts.
15. Carefully add 25 ml of the sulfuric acid solution (9:1 concentrated sulfuric acid/ water) to the hexane extracts.
16. Stopper the separatory funnel and shake vig orously for at least 1 minute. Allow the layers to separate and discard the lower aqueous acid layer. Repeat this step until the acid layer is colorless.
17. Wash the hexane with a 25-ml portion of water. Discard the water waslu
MONS 042049
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
IB, Filter the hexane extract through a 4" funnel plugged with glass wool which is covered with a layer of sodium sulfate into a Kunderna- Danish evaporative concentra tor.
19. Add a small boiling chip, put the Snyder column in place, and teduce the hexane volume to less titan 5 ml by heating the apparatus in a 80-90'C water bath.
Column Temper
ature.................. 160*C
Detector Temper
ature.................. 300'C
Injection Port
Temperature.. 195*C
Pulse......... ..
150
Flow Rates........... Helium Carrier 60 ml/min
Argon-Methane Purge ro 120
ml/mln
20. After cooling, remove the 5-ml graduated tube and transfer the hexane extract to an alumina adsorption column, washing It in with several 5-ml portions of hexane.
21. Carefully add 100 ml of hexane to the col umn reservoir and collect the total eluent In either a 250-ml volumetric flask or a Kunderna-Danish evaporative concentrator.
Using EC/GC as the determinative step, inject in duplicate 1-10 fil of each solution into the chromatograph. By comparison with standard so lutions injected, in duplicate, under the same op erating conditions, determine the amount and type of Aroclor using the individual or total peak height method.
22. If the column eluent 1$ collected in a volu metric flask, dilute to volume with hexane, and proceed with the gas chromatographic analysis,
23. if the column eluent is collected In a Kunderna-Danish evapotative concentrator, reduce solvent volume, cool, dilute to vol ume, and proceed wit!) gas chromatographic analysis.
The electron capture detector should also be used to guide the isolation procedures. Water and sedi ment extracts can be checked for the presence of , PCB'S and/or Interferences by Injection i*l portions
of the extracts at various points in die extraction and concentration schemes, in tills manner, it can be determined if the sample needs to be concentrated or diluted and if the clean-up procedures should be employed.
H. Electron Capture Gas Chromatograpliic* 6 Procedure___________________________
Instrument ...... F& M402 Biomedical Gas Chromatograph
Detector................ High Temperature Ni63 Electron Capture Cell 6 mm x O' Glass Column. 4`Vo XE-GO on 80/100 mesh Chtomosorb W, HP, AW-DMCS
(Continued)
1. Extraction The extraction of PCB's from water, employing
hexane as the extractant, has been found to be quantitative and sufficiently simple and rapid fot use as a routine procedure.
The evaluation of tills method was based on spik ing water samples with standard acetone solutions of PCB's, The spiking method consisted of adding the PCB's In acetone (25-50 jil) to 500 ml of tap water
MONS 0^050
Section 5 Page 13
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANOABDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANOARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
In a 32-o* narrow-ncck screw cap jar. After thor ougly mixing die sample, duplicate 225*250 ml aliquots were taken and subjected to the proposed sample preparation and worked up as outlined. The results were quantified by preparing a calibration curve using standard hexane solutions of the PCB's used to spike die water samples. The major iso mer peak height was used to construct the calibra tion plot.
The average recovery and deviation achieved substantiated the applicability of the method for the quantitative recovery and analysis of PCB's from ware/ at the ppb-ppm level.
No PCB recovery experiments from spiked sedi ment and soil samples have been performed, in stead, several of the residual solids representative of some of the types of sediment or soil analyzed were re-extracted with hexane/acetone (40/60) in a soxhlct extractor to test for tire efficiency of the acetonitrile extraction step. The hexane, after iso lation by dilution with distilled water, was then carried through the purification steps. Recoveries by soxhlct extraction have indicated that die ace tonitrile extraction of PCD's was essentially quan titative in die eases checked.
J. Sample Concentration Concentration of sample extracts is necessary,
prior to clean up by chromatographic or chemical means, to reduce sample size and increase sensi tivity, The preferred method of concentrating al lows minimum loss through volatilization or chem ical decomposition and requires a minimum time. The tiiree methods of solvent volume reduction most commonly used are evaporation by exposure to a stream of air, evaporation employing a Kunderna- Danish evaporative concentrator equipped widi a Snyder column, and evaporation under re duced pressure. All three techniques have been used, and no significant losses from volatilization or chemical altcma ion have been encountered. However, the KuiuJerna-Danish evaporative con centrator and the stream-of-air methods arc easier to use.
K. Column Adsorption Chromatography and Chemical Clean Up
Silica gel, Flotisil and alumina deactivated widi 0, 1.0, 1.5, 2.0 and 5 percent water were investigated as adsorbanu for the elimination of interferences. Alumina (5% water) was found to be more effective and reproducible than either silica gel or Florfsfl. The activity of alumina varies widi age and lot; therefore, 5% water is j added to the alumina, after heating for a mini mum of 4 hours at 400*0, to Insure a reproduc ible activity.
Saponification and subsequent extraction of the sample with sulfuric acid is an effective way to ; remove a number of chlorinated hydrocarbon inier ferences as well as other matrix interferences. ! PCB's are not affected.
i
i
| L, Column Performance
i Column performance is die key to effective ! gas chromatographic analysis and, as such, the | ,, choice of column materials is particularly im ' portant. Ideally, the support employed should be
inert, mechanically strong, and of Iiigh surface area. For these reasons, Chromosorb W, UP. AW-DMCS Is recommended for diis work.
A variety of polar and non-polar liquid phases have been investigated. The following columns have been found to provide adequate separation, etc., for use in PCB analysis by electron capture- 4'^ (w/w) DC-200, SF-9G, OV-17, SE-30, SE-54. XE-60, Apiezon L. and &;' OF-1. DC-200 and XE-60 or QF-1 are the most suitable of these liquid phases.
Another important consideration when working with an extremely sensitive detector and conse quently low levels of materials is column condi tioning. With polar phases such as XE-GO and QF-1. operating a new column overnight at a temperature 25-50*C higher than that to be used during analysis results in a more stable column.
Section 6 Page 14
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
A no-flow conditioning technique it employed to condition non-polar column*. The column it purged wltli carrier gas. heated for 30 minutes at an el evated temperature without carrier flow and then cooled to room temperature. At the end of this cycle, the carrier flow Is resumed and the condi tioning is completed as in the case of the polar liq uid phase. Two precautions: during conditioning, the column should not be connected to the detec tor, and one should not exceed the maximum safe temperature of the liquid phase.
Two gas cliromatographic systems have been used for PCB analysis~F & M Model 402 and 5750. Any system of instrument and column suitable for chlorinated pesticides is satisfactory for PCB anal ysis. The use of the high temperature Ni63 elec tion captute cell is highly recommended. Tire ability to operate at higher temperatures prevents maintenance problems due to contamination horn high boiling components. Glass columns should also be employed.
Since all liquid substrates bleed to one degree or another and columns eventually degrade, all new columns should be characterized with two column performance indicators--the number of theoretical plates (N) and a tailing factor (T). p.p'-DDT is employed to check these parameters because It it known to degrade on "poor" columns. In this manner, one can determine if the performance of new column (s satisfactory and when the column performance begins to fall off, A column is con sidered good if the number of theoretical plates per foot It on the order of 400-500 with tailing factors of 1.0-1.3. Calculation of these parameter* is shown In Fig. 5-2, page 8. Additionally, there should be no significant extraneous peaks upon in jection of a pure p.p'-DDT standard.
Other chromatographic conditions that can be adjusted arc column temperature and flow rates. Although resolution of a mixture increases with de creasing temperature, a temperature should be chosen that allows the elution of all components within a convenient time period. The temperatures given are optimum for 42*, chlorinated biphenyl; temperamrex are increased when specifically ana lyzing for the highci chlorinated biphenyls, i.e.,
UO','-'. etc. The Row rates ihown arc optimum for a given instrument, column .and detector system. These should be adjusted tf better results can be achieved.
M, Detection and Measurement Quantitative determinations employing the elec
tron capture detector are non-stoichiomctric meas urements made by comparing peak heights or areas for known concentrations with those for unknown compositions. Except for sharp peaks, peak area measurements are usually more reproducible than peak height measurements but are extremely time consuming unless a recording integrator is employed. However, peak height measurements are as accu rate as disc integration of triangulation and, if the peak shape represents a gaussian curve, the height may be considered independent of the base. Con sequently. peak height measurements were gener ally used. Three variations of the peak heigh! quantification procedure were employed.
Case I
-- EC gas chromatogram of PCB un known unchanged with respect to standard PCB with no evidence of Interferences.
Case II -- EC gas chromatogram of PCB un known altered with respect to stand ard PCB with no evidence of inter ferences.
Case 111-- EC gas chromatogram of PCB un known unchanged with respect to standard PCB with evidence of in terference.
HONS 042032
Section 5 Page 15
OFFICIAL STANDARDS PROPOSAL
THIS OFFICIAL STANDARDS PROPOSAL IS AN OFFICIAL DRAFT OF A PROPOSED STANDARD DEVELOPED WITHIN NEMA,
OR IN COOPERATION WITH OTHER INTERESTED ORGANIZATIONS, FOR CONSIDERATION BY ORGANIZATIONS OUTSIDE OF NEMA
The amount of PCB's In Case I samples is de termined by preparing a plot of the major peak height versus concentration. For Case 11, a plot is prepared of die total sum of all major peaks versus concentration. With Case III samples, a peak free from interference is used. When dom inant interferences are present, one or more of the chemical clcan-up procedures is employed.
In all cases, the response of the electron capture detector must be linear for quantitative analysis.
N. Contamination In determining PCB's in water, soil and sedi
ment by election capture gas chromatography, lab oratory sources of contamination can be a major problem. The samples and extracts should never
be allowed to come in contact with materials other than glass, Teflon or metaL Laboratory glassware should be thoroughly washed with hot, soapy water, rinsed will) distilled water, acetone, and then hexane. All equipment should also be rinsed again with hexane just prior to use, and blanks should be frequently carried through all steps of the procedures to insure against the possibility of contamination.
0. Sensitivity
Two parts per billion. Absolute sensitivity-- 0.5 x 10"9 grama. Volume injected--5 jiL Final volume of extract--5 mL Sample size--250 mL
Section 5 page 16
HONS 042053
o AROCI.0R 1016 HSP 402 Ni-63 EC 1/4" X 6' 4% XE-60 on 80/100 Chromosorb W HP
Col. Temp. - 200C Inj. Temp. - 220C
Det. Temp. - 250"C Carrier Gas - He 60 ml/min. Purge Gas - 10% CH^/Argon 120 ml/min. Pulse Interval - 50 nsec Amt. Injected - 5 nl Std. Cone. - 1 (ig/ml. Range - 10
Attn. - 8
I i>
0 12 3 4 5 6 7 8 9
MINUTES
MONS 042054
o
Fig. 5-3
Section 5 Page 17
ooo
HONS 0 4 2 0 5 5
AROCIOR 1221
HSP 402 Ni-$3 EC 1/4" x 6' 4% XE-60 on 80/100
Chromosorb W HP Col. Temp. - 170C Inj Temp. - 220C Det. Temp. - 250C Carrier Gas - He 60 ml/min. Purge Gas - 10% CH./Argon 120 ml/min. Pulse Interval - 50 psec Amt. Injected - 5 pi _6 Std. Cone. - 1.48 x 10 g/ml Range - 10 Attn. - 4
% 40
30 20 10
MINUTES
654 3210
Fig. 5-5
See don 5 Page 19
RONS 042056
AROCLOR 1248
H&P 402 Ni-63 EC 1/4" x 6' 4* XE-60 on 80/100
Chromosorb W HP Col. Temp. - 190"C Inj. Temp. - 220C Det. Temp. - 250C Carrier Can - He 60 ml/min. Purge Gas - 10% CHij/Argon 120 ml/min. Pulse Interval - 50 ysoc Amt. Injected - 5 yl Std. Cone. - 1.31 x 10" g/ml Range - 10 Attn. - 4
10
1
14
(! (1
t
50 40 30
11 1 r~' ' i' 1 1 -- -i' ' --'i-...... *i....... -r----r .......r - i i
I --T
13 12 11 10 9 e 7 6 5 4 3 2 10
MINUTES
Fig. 5-7
Section 5 P23C 21
HONS 042057
AROCLOR 1254
HiP 402 Ni-63 EC 1/4" x 6' 4% XE-60 on 80/100
Chromosorb W HP Col. Temp. - 205'*C Inj. Temp. - 220C Det. Temp. - 250"C Carrier Gas - He 60 ml/min. Purge Gas - 10% CH^/Argon 120 ml/min. Pulse Interval - 50 visec Amt. Injected - 5 pi Std. Cone. - 1.02 x 10~6 g/ml Range - 10 Attn. - 8
r
L 40 U 30 k 20
10
I------ | --T
T--' 'T
"1---- -- T"
y i 'r
12 11 x:>r:rr~
10
SccdOM -r) Page 22
9876543210
Pig. 5-8
MQNS 042058
AKOCLOR 1260 1UP 402 Mi-63 EC 1/4" x 6' 4% XE-60 on 80/100
Chromosorb W HP Col. Temp. - 220C Xnj. Temp. - 220"C Det. Temp. - 25QI,C Carrier Gas - He 60 ml/min. Purge Gas - 10% CHs/Argon 120 ml/min. Pulse Interval - SO usee Amt. Injected - 5 ul Std. Cone. - 0.98 x 10_ g/ml Range - 10 Attn. - 8
20
26 2 2
19
2 1, )9
50 40 30 20 10
12 11 10 98765 MINUTES
fig. 5-9
43210
Section f Page .rt MONS G42Q59
NATIONAL
MEMBER COMPANIES OF THE
ELECTRICAL MANUFACTURERS
ASSOCIATION
Allis-Chalmers Manufacturing Co. T Milwaukee. Wis. 53201
Cenual Moloney Transformer Division t
Colt Industries
Pine Bluff. Ark, 71601
'
Chance, A, B,, Co. t Tramfotmet Division
Washington, Mo. 63090
Dowser Electric Inc. t (Division of Sola Basic Industries)
Mount Vernon, I1L 62B64
Eico Manufacturing Co. t Greenville, Tex. 75401
Federal Pacific Electric Co. New Bedford, Mass. 02744 # Newark, N.J. 07101 t
General Electric Co. Hudson Falls, N.Y. 12830 * Pittsfield. Mass. 01201 t
Hevl-Duty Electric t (Division of Sola Buie Industries)
Goldsboro, N.C. 27530
High Voltage Power Corp, t Westboro, Mass. 01581
1-T-E imperial corp. t Philadelphia, Pa. 19130
Kuhlman Electric Co., A Division of t Kuhlman Corp.
Birmingham, Mich,
Magnetics Inc. t Sandy Lake. Pa. 16145
McGiaw-Edlson Power Systemif Division So. Milwaukee, Wis. 53172 * Canonsburg. Pa. 15317 t
* Member ,of capacitor Section, t Member pf Transformer Section.
Niagara Transformer corp. f Buffalo, N.Y. 14225
Northern Engineering Division t Sta* rite Industries Inc.
Baraboo, Wis. 53913
Sangamo Electric Co. * Springfield, lit 62708
Sierra Transformer Co., t Cerritos, Calif. 90701
Sorgel Electric Corp. t Subsidiary of Square D Co.
Milwaukee, Wis. 53204
Spokane Transformer Co. f Spokane, Wuh. 99202
Sprague Electric Co, * North Adams, Man. 01247
Standard Transformer Co,, Division of t American Gage and Machine Co.
Warren, Ohio 44481
Tierney Electrical Manufacturing Co. t Seattle, wuh. 98108
Uptegraff, R. E., Manufacturing Co. t Scottdale, pa. 15683
Wagner Electric Corp, t Su Louis, Mo. 63133
Westinghouse Electric Corp. Bloomington, ind. 47402 * Sharon, Pa. 16146 t
Zinsco Electrical products t Su Louis, Mo, 63113
HONS 042060