CHAPTER 14
1949 Guide
given off by the heating plant will increase the basement temperature. In any case, the exact basement temperature is likely to be a somewhat indeterminate quantity, if the basement is not heated. Since the base ment temperature will generally be lower than that of the rooms above, an allowance should theoretically be made for the loss from the rooms above through the floor over the basement.
The temperature in crawl spaces below floors will vary greatly depending on the number and size of wall vents, the quantity of heating pipes and the type of insulation. It is therefore necessary to analyze the conditions and select an appropriate temperature by judgment.
TRANSMISSION HEAT LOSS
.' The basic formula for. the loss of heat by transmission through any surface is given in Equation 3:
where
Ht = AU (1 -- to)
(3)
Ht = heat loss transmitted through the wall, roof, ceiling, floor, or glass, Btu per
hour.
'
A = area of wall, glass, roof, ceiling, floor, or other exposed surface, square feet.
XJ = coefficient of transmission, air to air, Btu per (hour) (square foot) (Fahren heit degree temperature difference) (Chapter 6).
t = inside temperature near surface involved which may not necessarily be the so-called breathing line temperature, Fahrenheit degrees.
io = outside temperature, or temperature of adjacent unheated space or of the ' ground, Fahrenheit degrees.
Examples. Calculate the transmission loss through an 8 in..brick wall having an area of ISO sq ft if the inside temperature (t) is 70 F and the outside temperature ((,,) is --.10 F.
! Solution. The coefficient of transmission (If) of a plain 8 in. brick wall is 0.50 (Chapter 6, Table 7). The area (A) is 150 sqft; Substituting in Equation 3:
H, = 150 X 0.50 X [70-(-10)] = 6000 Btu per hour.
Transmission Loss Through Ceilings and Roofs
The transmission heat loss through top floor ceilings, attics, and roofs may be estimated by either of two methods:
1 1. By substituting in Equation 3 the ceiling area (4), the inside-outside tempera ture difference (t -- t,,) and the proper value of (If):
a. Flat roofs. Select the coefficient of transmission of the ceiling and roof from
Tables 14 or 15, Chapter 6, or use appropriate coefficients in Equation 1 if side walls extend appreciably above the ceiling of the floor below.
b. Pitched roofs. Select the combined roof and ceiling coefficient from Table 17,
Chapter 6 or calculate the combined roof and ceiling coefficient by means of
Equation 6, Chapter 6, where this formula is applicable as explained in Chapter
}' - 6.
,
2. By estimating the attic temperature (based on the inside and outside design temperatures) by means of Equation 1, and substituting for t,, in Equation 3, the value of thus obtained, together with the ceiling area (4) and the ceiling coefficient
(17). This applies to pitched roofs. , In the case of flat roofs it is not necessary to
Heating Load \
263
calculate the attic temperatures as the ceiling-roof heat loss can be determined as
per paragraph la.
INFILTRATION HEAT LOSS
The infiltration heat loss includes (1) the sensible heat loss or the heat required to warm the outside air entering by infiltration and (2) the latent heat loss or the heat equivalent of any moisture which must be added.
Sensible Heat Loss
The formula for the heat required to warm the outside, air which enters a room by infiltration to the temperature of the room, is given in Equation 4 :
H. = 0.240 Qd (t - t0)
(4)
where
.
H, = heat required to raise temperature at air leaking into building from f,, to l, Btu per hour.
0.240 = specific heat of air. Q = volume of outside air entering building, cubic feet per hour (see Chapter
8).
d = density of air at temperature to, pounds per cubic foot.
It is sufficiently accurate to use d = 0.075 in which case Equation 4 reduces to
Ht = 0.018 Q (l - to)
. (4a)
The volume of outside air entering per hour (Q) depends on the wind velocity and direction, the width of crack or size of openings, the type of openings and other factors, as explained in Chapter 8. Where the-crack method is used for estimating leakage, it is more convenient to express
the air leakage heat loss in terms of the crack length:
ff. B t (f - !,,)
. (4b)
where
B = air leakage per (hour) (foot of crack) (Chapter 8) for the wind velocity and type of windows or door crack involved multiplied by 0.018.
L = length of window or door crack to be taken into consideration, feet.
Example 4. What is the infiltration heat loss per hour through the crack of a 3 x 5 ft average, double-bung, non-weatherstripped, wood window, based on a wind velocity of 15 mph? Assume inside and outside temperatures to be 70 F and zero respectively.
Solution. According to Table 2, Chapter 8, the air leakage through a window of this type (based on ft in. crack and ft in. clearance) is 39 cu ft per foot of crack per hour. Therefore, B -- 39 X 0.018 = 0.70. The length of crack (L) is (2 X 5) + (3 X 3), or 19 ft; t = 70 and ta = 0. Substituting in Equation 4b,
H, = 0.70 X 19 X (70 - 0) = 931 Btu per hour.
Number of Air Changes to be Used for Computations'
Since a certain amount of judgment regarding quality of construction, weather conditions, use of room and other factors is required in estimating infiltration by any method, some designers base infiltration upon an esti mated number of air changes rather than upon the length of window cracks.