CHAPTK 45
1965 Guide And Data Book
Refrigerant Control Devices
739
T\
Fig. 37 .... Basic Rating Curves for Condenser-to-Evaporator Capillary* (Refrigerants 12 and 22)
flow-rate.1 This is understandable, when the back pressure is below the critical pressure. Actually", the' curve for increase in flow rate flattens, for all practical purposes, considerably above the critical pressure. Hopkins' points out that the use
of the flow factor to correct tube diameter and length results in some additional inaccuracy. ' The effect of the suction pressure on capillary capacity may be calculated. First, the critical pressure b determined' from