Document 6R1x7XzMak3Vrr6xrpNrZae09

322 CHAPTER IS 1949 Guide' Latent Load Infiltration 07 cfm X 4840 X 0.0071 =........................... .. 2,300 People 85 X 250 -.......................................................................................... .. 21,250 Total Latent Space Load.......................................................... ............ ............... Ventilation Air Sensible 1275 cfm X 1.08 X 15 =......................................................... ............. Latent 1275 cfm X 4840 X 0.0071 =.............................................................................. 23,550 20,700 43,800 Grand Total Load.............................................................................. 272,815 LETTER SYMBOLS USED IN CHAPTER IS 0 = solar altitude, degrees. y = difference between the azimuth angle of an outdoor wall and the azimuth angle of the horizontal projection of the sun's rays, degrees. M -- Permeability of material to moisture transmission, grains per (sq ft) (hr) (inch Hg). A .= amplitude decrement factor, a variable depending on thickness, material, and orientation of the wall or roof dimensionless. ^ ;. 9 = angle of incidence for sun's rays striking a surface, degrees. - r = fraction of incident radiant energy transmitted through a glass section, dimensionless. A = area across which heat is being transferred, square feet. a = fraction of incident radiant energy absorbed within a glass section, dimension less. 6 = fraction, of incident radiant energy absorbed by a non-transparent surface, dimensionless. e = ratio of direct solar radiation to sky radiation falling on a horizontal surface, dimensionless. f\ = unit convective conductance for indoor surface = film coefficient of heat trans fer of indoor air, Btu per (square foot) (hour) (Fahrenheit degree). fi = unit convective conductance for outdoor surface = film coefficient of heat transfer of outdoor air, Btu per (square foot) (hour) (Fahrenheit degree). Of = fraction of total window area receiving direct solar radiation when shaded by window reveal, dimensionless. hi = enthalpy of indoor air per pound of dry air, Btu per pound, ho = enthalpy of outdoor air per pound of dry air, Btu per pound. li = direct solar radiation incident upon a surface at any angle of incidence, Btu per (square foot) (hour). - /n = direct solar radiation incident on a surface at normal incidence, Biu per (square foot) (hour). .v . /. = sky radiation incident upon a surface, Btu per (square foot) (hour). It = /. + Id, Btu per (square foot) (hour). K = cosine of angle of incidence for.direct solar radiation striking a surface, dimen sionless. - k = thermal conductivity of building material, Btu per (square foot) (hour) (Fahrenheit degree per foot). L = thickness of building material, feet. 1 -- height of window, feet. Q = rate of entry of outdoor air, cubic feet per minute. Qn = required air quantity through conditioning equipment, cubic feet per minute. q = instantaneous rate of heat transfer, Btu per hour. q. = instantaneous latent heat load, Btu per hour. Cooling Load 323 ^ = Latent head load due to moisture transmission through materials, Btu per (hr) (sq ft). ' q, = instantaneous sensible heat load, Btu per hour. - ` qt = g. + Per tour. q* = the heat-moisture ratio of the room load based upon the ratio of the total heat added divided by the required rate of water-vapor removed. r -- fraction of incident radiation reflected from glass surface, dimensionless. t. = sol-air temperature, Fahrenheit degrees. = sol-air temperature at a time earlier than the time for which heat gain is being found by an amount that is equal to the time lag of the wall or roof, Fahren heit degrees. = indoor air temperature, Fahrenheit degrees, k = temperature of outer surface of building, Fahrenheit degrees. = 24-hr cyclic average sol-air temperature, Fahrenheit degrees. = (m + (*.* -- tm), net equivalent outdoor temperature for combined periodic and mean heat flow, Fahrenheit degrees. U = over-all coefficient of heat transfer of a structural section, Btu per (square foot) (hour) (Fahrenheit degree). c,, = volume of outdoor air per pound of dry air, cubic feet. w = width of window, feet. '. Wi = humidity ratio of indoor air, pounds moisture per pound of dry air.... yfo = humidity ratio of outdoor air, pounds moisture per pound of dry air. REFERENCES 1 Application Engineering Standards for Air Conditioning for Comfort (Air Con ditioning and Refrigerating Machinery Association, Inc., 1947, p. 4-7). .1 Proposed Standard Solar Radiation Curves for Engineering Use, by P. Moon (Journal of the Franklin Institute, November, 1940, Vol. 230, No. 5, p. 583-517). 3 Summer Cooling for Comfort as Affected by Solar Radiation, by G. A. Hendrick son and J. H. Walker (Heating and Ventilating, Vol. 29, No. 11, November, 1932, p. 14-21)-. 3 Dynamic Meteorology, by B. Haurwitz (McGraw-Hill Book Co., Inc., New York, 1941). 3 Summer Weather Data and Sol-Air Temperature--Study of Data for New: York City, by C. O. Mackey and E. B. Watson (A.S.H.V.E. Transactions, Vol. 51,1945, p. 75). " A.S.H.V.E. Research Report No. 1268 --Summer Weather Data and Sol-Air Temperature--Study of Data for Lincoln, Nebr., by C. O. Mackey (A.S.H.V.E. Transactions, Vol. 51, 1945, p. 93). 7 A.S.H.V.E. Research Report No. 923--Heat Transmission as Influenced by Heat Capacity and Solar Radiation, by F. C. Houghten, J. L. Blackshaw, E. M. Pugh and Paul McDermott (A.S.H.V.E. Transactions, Vol. 38, 1932, p. 231). Ef fect of Heat Storage and Variation in Outdoor Temperature and Solar Intensity on Heat Transfer Through Walls, by J. S. Alford, J. E. Ryan and F. O. Urban (A.S.H. V.E. Transactions, Vol. 45, 1939, p. 369). Periodic Heat Flow in Building Walls Determined by Electrical Analogy Method, by Victor Paschkis (A.S.H.V.E. Trans actions, Vol. 48, 1942, p. 75). Periodic Heat Flow--Homogeneous Walls or Roofs, by C. O. Mackey and L. T. Wright, Jr. (A.S.H.V.E. Transactions, Vol. 50, 1944, p. 293). Periodic Heat Mow--Composite Walls or Roofs, by C. O. Mackey and L. T. Wright, Jr. (A.S.H.V.E. Transactions, Vol. 52, 1946, No. 1299). A.S.H.V.E. Research Report No. 1002--Cooling Requirements of Single Rooms in a Modern Office Building, by F. C. Houghten, Carl Gutberlet, and Albert J. Wahl (A.S.H.V.E. Transactions, Vol. 41, 1935, p. 53). Study of Actual vs. Predicted Cooling Load on An Air Conditioning System, by James N. Livermore (A.S.H.V.E. Transactions, Vol. 49,1943, p. 287). 10 A.S.H.V.E. Research Report No. 1195--Heat Gain Through Walls and Roofs