American Society of Heating and Ventilating Engineers Guide, 1934 of the heat may be dissipated to the air, but a fair estimate of the amount to be removed by the air can usually be made. The next step is to select the temperature difference to be maintained. Knowing the amount of heat to be removed and having selected a desirable temperature difference, the amount of air to be passed through the building per minute to maintain this temperature difference can be determined by means of the following equation: where c = 0.24 = specific heat of air. V = specific volume of the air, cubic feet per pound, about 13.5. (See Chapter 41). H = heat to be carried off, in Btu per minute. Q = air flow in cubic feet per minute. D = inlet-outlet temperature difference in degrees Fahrenheit. Fig. 11. Rotating Roof Ventilator For disposing of air impurities, the required air flow must be such that the outside air will' dilute the-;impurities! to. a :degrpe that they are no longer objectionable. For human.occupancy,: such'as- in auditoriums and classrooms, 10 cfm per person is usually taken as the minimum of outside air necessary for ventilation (see-Chapter 2). .'For garage ventilation, sufficient air must be admitted to dilute'the carbon monoxide content of the indoor air to 1 in 10,000 (see Garage Ventilation in this Chapter). Air quantity and quality are not the only requirements. For human occupancy, air distribution is important. In ventilation the air distribu tion is almost entirely a matter of the number, the design, and the location of inlets and outlets. In locating openings, special precautions should be taken against the formation of dead air spaces or pockets within the zone of occupancy. Suggested methods for estimating the air flow due to temperature difference alone and to wind alone have already been given. It must be remembered that when both forces are acting together, even without interference, the resulting air flow is not equal to the sum of, the; two 64 . Chapter 4--Natural Ventilation estimated quantities. The same openings have been assumed in both cases, and since the resistance to flow through the openings varies ap proximately with the square of the velocity3, this resistance becomes a limiting factor as the flow through the openings is increased. Recent investigations1 2 show that the total flow is only 10 per cent above the flow caused by the greater force when the two forces are nearly equal, and this percentage decreases rapidly as one force increases above the other. Tests on roof ventilators indicate that this is too conservative in the direction of low total flow quantities, but there is in any case a large judgment factor involved. The wind velocity and direction, the outdoor temperature, or the indoor activities cannot be predicated with certainty, and great refinement in calculations is therefore not justified. When designing for winter conditions, an added variable is. the heat lost by direct flow through walls and windows and by infiltration. Example 1. Assume a drop forge shop, 200 ft long, 100 ft wide, and 30 ft high. The cubical content is 600,000 cu ft, and the height of the air outlet over that of the inlet is 30 ft. Oil fuel of 18,000 Btu per lb is used in this shop at the rate of 15 gal per hour (7.75 lb per gal). Temperature differences are 10 deg Fahr in summer and 30 F in winter, and the wind Velocity is 5 `mph in summer and 8 mph in winter. What is the necessary area for the inlets and outlets, and what is the rate of air flow through the building? Solution. The system must be designed for the summer conditions as these are the more severe. The heat to be removed per minute is: H = 4^- X 7.75 X 18,000 = 34,875 Btu per minute. By Equation 3, the air flow required to remove this heat with a temperature difference of 10 deg is: Q VH cD 13.5 X 34,875 0.24 X 10 196,172 cfm. This is equal to 19.6 air changes per hour. The assumption is made that the average temperature difference between indoors and outdoors is the same as the temperature rise of the air from the inlet opening to the outlet opening. Actually, the latter difference is larger and so the value of 19.6 air changes per hour is conservative as it allows for more cooling than is necessary for an average temperature difference of 10 deg. If 196,172 cfm are to be circulated by the force of the temperature difference alone, the area of opening would be, by Equation 2: A= 9.4 VH (t, - lj) 196,172 9.4 V 30 X 10 1,205 sq ft If this area of openings were provided, a wind velocity of 5 mph, acting alone, would produce a flow according to Equation 1, of: Q = EAV = 0.50 X 1,205 X 5 X 88 = 265,100 cfm. If the inlet openings do not face the wind, but are at an angle with it, about half this amount may be considered to flow. A factor of judgment must now be exercised in making the selection of the area of openings to be specified. Apparently 1205 sq ft are a very *This is true for turbulent flow only. It would be more correct to state that the resistance varies approxi mately with V2 for high to moderate velocities, with V1 * for moderate to low velocities, and with the first power of the velocity for very low velocities through small openings. 65