April 2, 1S6S WRG 001353 PlAINTIff'S | exhibit I I WRG-415 Spray Applied Fireproofing Ease of Damageabi1ity Criteria & Test Program Experience in San Francisco has indicated that some of the new fire* proofing materials may easily be damaged during construction of a building or after when maintenance work Is required adjacent to the fireproofed member. The materials in question are direct spray ap plied mixtures of asbestos, gypsum, perlite and vermlculite usually with a Portland cement binder. These new fireproofing materials have a considerable range of hardness and durability. in 1961, because of considerable damage problems with one such material on actual construction job, the Board of Examiners of San Francisco, after extensive hearings, ruled that the particular material would no longer be permitted use in this Ctty for primary member protection. The Board also indicated that this Bureau should review similar mater ials that had been approved for use in San Francisco to determine whether they too would be subject to easy damage. Acting on this request by the Board, we have conducted investigations regarding the best means to evaluate the "ease of damageabi1ity". We found that there were no standard tests available for the materials in question. As a result, the Bureau of necessity has developed test ing devices to provide the data needed in the evaluation of damageability. Attached to this letter are the details of the test device and photo graphs of our device and the testing procedures to be followed. This is so that you may determine for yoursevles, if you so desire, the performance of your materials as well as to apprise'you in advance, of our testing procedure and criteria of passage. The attached photographs indicate the several components of our device. You will note that there are several items shown on the photographs but not indicated in the plans. These items were early modifications of the device that were discerned and are not required to make the device perform. Similarly certain items are not fully detailed on the plans as they are in no way mater ial to the performance of the test device and therefore can vary in design. You are hereby requested to submit three (3) samples, each 12"xl8" in size, of your fireproofing material that has been approved by the Bureau in the past. On the attached list are the various manufacturers involved and the products of each. You are advised to check this list to determine for which of your materials you must submit. The samples shall be one inch thick on 1/2 inch gypsum wall board and shall be the density as the sample tested upon which the Bureau based its approval. In the event there were varyina densities involved in the several ap provals granted, you must submit three (3) samples of each density except where the variation between densities Is 10% or less. Failure to submit samples within forty-five (45) days from receipt of this letter will require that I automatically revoke the approvals pre viously granted for the materials involved. The samples shall each bear a notarized statement as to the weight of the wallboard prior to application of the f1 reproofing; the mix used in making the fireproofing; the density of the mix at time of applica tion (at nozzle) ; the weight of the entire sample, and the equilibrium dry density of the sample prior to delivery to this Bureau. Two of the samples will be used in the tests and the third will-act as a control and for use In the event something unforseen occurs to one of the samples. You will be responsible for assuring the delivery in good order, of your samples. in the event you desire to modify your material to provide a less damageable surface, the following shall be the Bureau's concern with the samples and the acceptance thereof: 1. if the intent is to add a surface over the tested thickness of fireproofing for which the hourly rating was achieved, we will accept a small scale (I'xlJ1) pilot test made at Underwriters' Laboratories to indicate whether delamination of the materials occurs. The surface material shall not have flame spread cha racteristics exceeding 25. 2. if the intent Is to incorporate the less damageable surface within the thickness of the approved hourly rating, we will require that a full scale fire test be performed as this would in effect be a new material with possibly different characteristics. You are invited to witness the tests on your materials and if you or a representative desire to so witness the tests, please so advise me prior to our receiving the samples. Upon completion of the test series on your samples, the approvals pre viously granted will either remain in effect or will be revoked. In the event an approval is revoked, the revocation would constitute a denial of approval which under Section 806.C of the San Francisco Building Code would enable you to appeal to the Board of Examiners. Your cooperation in this test programwil! be appreciated. If you have any questions with regard the test devices or the pro* cedures please do not hesitate to contact me. Very truly yours, S.` AG: jh Enc. cci Board of Examiners Robert C. Levy, Superintendent/ Bureau of Building Inspection Hr. Jack Bono, Managing Engineer Fire Protection Department Underwriters' Laboratories, Inc. 207 E. Ohio Street Chicago 11, Illinois Mr. R. Gewaln National Board of Fire Underwri ters 85 John Street New York, N. Y. Mr. C. J. Koskinan Underwriters' Laboratories, Inc, 1655 Scott Blvd. *Santa Clara, Calif. Mr. T. H. Carter, Managing 01r. International Conference or Building Officials 50 South Los Robles Pasadena, California Mr. Herman Spaeth Pacific Fire Rating Bureau ^65 California Street San Francisco, Calif. Mr. R. Carlson State Fire Marshal's Office 1025 P Street Sacramento 1L, Calif. E-5 Committee American Society for Testing Materials c/o Irwin Benjamin Granco Steel 6506 N. Broadway St. Louis 15, Missouri Mr. R. W. 61attacher Ohio State University Engineering Experimental Sta. Columbus, Ohio Mr. Calvin H. Yui11 Southwest Research Institute San Antonio, Texas Prof. G. E. Troxell University of California Berkeley, Calif. Mr. Walter Bruger Dept, of Building & Safety City Hall Los Angeles, Calif. Mr. John Degenkolb 59*+0 Echo Street Los Angeles L2, California I. Abrasion Test 1. 12"xl3n, y" wallboard; weight to be certified to by app1icant. 2. Fireproofing 1" thick to test density of test submitted in original approval. If 2 or more different densities (varying by more than 10 percent) approved separate samples required. Mix and application shall be certi fied to by applicant. 3. Three samples to be furnished. k. If open or coarse material submitted, voids in surface will be determined by sand displacement method* prior to testing. Average area 6"x3-l/8" will be used to determine average voids. Total volume 307 cubic centi meters. Condition of Passage: Maximum removal of material at end of 3 passes of test vehicle shall not exceed 20 cubic centimeters (16.5%) with a plus tolerance of 2 cubic centimeters. Removal to be measured by sand ( displacement method*. Removal wiJl be measured for worst 6-inch length of 2 test cycles per sample. Two cycles will be made on each of 2 samples. Aver age of 2 worst, runs' will be value used for deter mination. 11. Impact Test l. Same samples as for abrasion test shall be used. 2. Surface voids will not be measured due to small area involved. 3. Low point of impact rod to be set at of sample. below surface h. Test consists of three (3) impacts of test rod with resultant volume of displaced material measured. Material "heaved up" by impact will be removed to establish reference plane of original surface. Volume of impact to be determined by sand displace ment method. Condition of passage: Amount of material. removed after three (3) impacts shall not exceed 5.0 cubic centimeters with a plus tolerance of 1.0 cubic centimeters. Two (2) impact tests will be performed on each of two (2) of the samples. The maximum on each sample will be averaged and will be the value used f rwwCwj s April 2,lSo3 Page 2 to determine passage or failure of cesc. In the event the impact rod completely moves through the sample within the 3 test cycles, the material will automatically be considered to have failed the test.* * Ottawa sand will be deposited to surface or depression to a level equal to original surface. Amount used will constitute volume. ' -* ^Impact uppoilt - AT ersT Ve h cVg csrasiom ------- j*& E'f^ZS PlPZ.-tZS'K'Al-L DDl TJONAL .AS'LEAD A7 * --r" I M /n w / f' <N0 5 -J O' k l /: -m 1 M)1 " -- /// - .j.j... _ J_.,. . Jj C- * .I DE ;.srf.'.vy ;iva*. i: - i 7.3: r>Ot*'r\DS i ---- POZiT/ON Q~ II !, IMr'A CT TSTR (SOR DET. CE'&j / li t 1ER I! i 4 ii t \ &ASE 5 a na PL6 5/ D LEV A j l rs .V i e 61 IMPACT PENETRATION TEST MONOKOTE-5 FIRE RESISTIVE MATERIAL Made for ZONOLITE CONSTRUCTION PRODUCTS DIVISION W. R. CRACE & COMPANY TRAVELERS REST, S. C. Hade by FROEHLING & ROBERTSON, INC. CREENVILLE, S. C. XJUAWEAS: Mis DUMBARTON RO*0-0O*7?SJ Richmond VA J3?si <ANCH7S ASMviue.NC* Baltimore i.'O'ChahlOTTE NC.CRDzrrv*. fATtiTEviuE NCCRE6NWttE SC ''ORfOi* va TUlECn mc C**jO*'.e .A .LYNCm3Jw VA r / 1 '/2 *7/ a. ' LOADING DIAGRAM i. 1 6- / \ * ri ii i 4 2-H .... ............... ...........4".___________ PLAN 'A-A i i 7/ i" ' i; 4 r I; / n -1 ft). i c'r. <- ,,. ....!. r *' \ \i i 1 Pop Tzz-r Vsh/cLe >T. A" /V S W.'VL SArsr y -f~. -, y r * ./ 1 - * 'n .1... ci.-- Z?ri>fS/A/5 it i; \ ---- .. t______________^ <f rry ~=Yt: V\ V. .. '-- Vch/cLz Zuprorts S*tl LONG \ ADJUST'ATS 3LOZX J"CLOT f=> L A N V I x ja~ A' I r\ V DTA!L - 'A' !* 5 IDE EE VAT ION ^\ l C- h-J r7 ?** HOLD-DQtY.V y<L7S 1 i Lm END VIEW