When well water is available in sufficient quantities at low temperatures during the cooling season, it may be pumped directly to air washers or cooling coils. Control is usually effected through control valves on the . water supply to the cooling unit actuated by temperature or humidity controllers, or both, located either at the outlet of the conditioner or in the conditioned space.
INDUSTRIAL PROCESSES
There are many industrial processes requiring automatic temperature and humidity regulation. The control equipment operates on the same principles that have been described, but it is often especially designed for each particular process. Each installation, or the installation for each process, is likely to be a problem peculiar to that process.
PROBLEMS IN PRACTICE
1 What important functions of heating, ventilating, and air conditioning systems do automatic controls fulfill?
Controls are applied to maintain adequate requirements for human comfort and efficiency; to maintain requirements for industrial processes; to obtain economy in operation; and to provide necessary safety measures.
2 How may temperature control be obtained in a room heated by a unit heater?
With constant steam supply, the unit heater motor may be'started or stopped by a thermostat, either directly or through a relay. With intermittent steam supply, opera tion of the motor by thermostat can be limited to the timd that steam is available, by using a reverse-acting temperature or pressure limit switch.
3 How may temperature control be obtained in a room cooled by a selfcontained mechanical unit?
The fan operation may be controlled by a manual switch, while a room thermostat in con junction with a solenoid valve may regulate the flow of the refrigerant to the coil. The thermostatic circuit might be operative only when the fans are running; and the com pressor might be controlled by refrigerant pressure.
4 How may temperature control be obtained in a room heated by an auto matically-fired warm air furnace?
A room thermostat might control the combustion unit; and a limit switch in the top of the furnace unit, when at a low setting of its control might operate the fan whenever there is a rise of temperature, and when at a high setting of its control it might shut off the combustion unit. A room humidity control operating a solenoid valve on the water supply to the humidifier, or operating a relay on the recirculating pump motor to the humidifier, may be connected in parallel with the fan motor. Humidification may be supplied only when heat is supplied and when the humidity control acts in conjunction with a time switch.
5 How may humidity be controlled in a unit humidifier for a steam or hot water heating plant?
Since heat is required for evaporation, a temperature limit switch, preferably of the immersion type, may be placed in the heating supply riser to cause the unit to be in operative when heat is not available. A room humidity, control will operate a solenoid valve on the water supply to the sprays. Both the solenoid valve and the humidity control may be electrically wired in parallel with a fan motor, and be subject to the temperature limit switch.
294
Chapter 15
AIR POLLUTION
Sources of Air Pollution, Effects of Air Pollution on Health, Pul monary Effects, Occlusion of Solar Radiation, Industrial Air Pollution, Abatement of Atmospheric Pollution, Smoke Abate
ment, Dust and Cinder Abatement
THIS chapter considers the hygienic aspects of atmospheric pollution and the methods by which this pollution may be lessened. Infor mation concerning the cleaning of air brought into buildings for ventilat ing purposes will be found in Chapter 16, and a discussion of the exhaust ing of dusts and toxic gases from factories and industrial plants is con sidered in Chapter 21.
The impurities which contribute to atmospheric pollution include carbon from the combustion of fuels, particles of earth, sand, ash, rubber tires, leather, animal excretion, stone, wood, rust, paper, threads of cotton, wool, and silk, bits of animal and vegetable matter, and pollen. Microscopic examination of the impurities in city air shows that a large percentage of the particles are carbon. (See Fig. 1, Chapter 16, for size of impurities in air.)
CLASSIFICATION OF AIR IMPURITIES
The most conspicuous sources of atmospheric pollution may be arbitrarily classified according to the size of the particles as dusts, fumes, and smoke. Dusts are particles of solid matter varying from 1.0 to 150 microns in size. Fumes include particles resulting from chemical pro cessing, combustion, explosion, and distillation, ranging from 0.1 to 1.0 micron in size. Smoke is composed of fine soot or carbon particles, less than 0.1 micron in size, which result from incomplete combustion of carbonaceous materials, such as coal, oil, tar, and tobacco. In addition to carbon and soot, smoke contains unconsumed hydrocarbon gases, sulphur dioxide, sulphuric acid, carbon monoxide, and other industrial gases capable of injuring property, vegetation, and health.
The lines of demarcation in these three classifications are neither sharp nor positive, but the distinction is descriptive of the nature and origin-of the particles, and their physical action. Dusts settle without appreciable agglomeration, fumes tend to aggregate, smoke to diffuse. Particles larger than one micron will eventually settle out by gravitation; particles smaller will remain in suspension as permanent impurities unless they agglomerate to sizes larger than one micron.
295