Document 6BDBqkjmpBOjeokmzjBdVanBm

290: CHAPTER 13 1956 Guide Table 8. Summer Design Sol-Air Temperatures Used for Tables 9 and 10 Sol-Air Temperature it Fahrenheit Deobees Mean Sun Time Any Sur Horn. North face1* Fast South West a Ratio*: -r-- Jco 12 Midnight 1 AM 2 3 4 5 6 7 8 9 10 11 12 Noon 1 PM 2 3 4 5 6 7 8 9 10 11 24 Hr Avg fm 0 0.225 : 0 0.225 0.125 0.225 0.125 0.225 0.125 77 76 76 75 74 74 : 74 75 77 80 83 87 : 90 93 94 95 94 93 91 87 85 83 81 79 83.1 77 76 76 75 74 74 76 91 106 119 129 137 142 144 140 132 120 107 96 90 85 83 81 79 100. 77 76 76 75 74 74 74 75 77 80 83 87 90 93 94 95 94 93 91 87 85 83 81 79 83.1 77 76 76 75 77 76 76 75 77 76 76 75 77 76 76 75 77 76 76 75 77 76 76 75 74 74 75 80 110 93 123 100 74 74 74 75 74 74 74 75 74 74 74 75 74 74 74 75 126 103 82 125 104 93 117 100 102 108 96 110 78 86 93 99 77 80 83 89 77 80 83 87 92 93 95 95 92 93 94 95 114 115 111 104 104 105 104 100 96 110 124 135 92 102 111 119 94. 93 91 87 94 93 91 87 99 95 91 88 96 141 120 94 139 118 91 125 111 87 103 94 .85 83 81 79 85 83 81 79 85 83 81 79 85 83 81 79 85 83 81 79 85 83 81 79 93.0 88.4 89.0 86.5 93.0 88.4 * a " surface absorptivity, dimensionless? roof -- 0.9; dark walls = 0.9, and light walls = 0.5. fco ~ unit convective conductance -- 4.0 Btu per, (hr) (F deg). b values in this column are magnitudes of to, the outdoor air temperature. of walls and roofs which appear in the literature.11'12 Both analytical and experimental studies have been made on the problem10 of heat flow through walls and roofs. Those concerned with a further study of the details of cooling-load estimates in particular relation to periodic heat flow will find much of value and interest in the reports of experimental studies of these problems.10'11 12 . . >5 The reader may also refer to the Cooling Load chapter of The Guide 1952 for the theory of heat flow through walls and roofs. PRACTICAL TABLES FOR CALCULATING SOLAR HEAT GAIN THROUGH WALLS AND ROOFS The analytical10 method reported by Mackey and Wright was used by Stewart16 to obtain temperature differentials based on Table 8 and shown in Tables 9 and 10. These analytical procedures, as well as those using Tables 9 and 10, presented here, yield generally higher rates of heat gain Cooling Load 291 than reported for Pittsburgh in early A.S.H.A.E. experimental studies. Current authoritative opinion indicates a preference for analytical calcu lations. Thermal and physical properties of materials used in these tables are given in a paper.16 The rate of heat flow is obtained by multiplying the overall heat transmission coefficient of the structure by the equivalent temperature differential obtained from the tables. Tables 9 and 10 were developed by using an outside surface conductance of 4.0 and an inside film conductance of 1.65 Btu (hr) (sq ft) (F deg). A reduction was made in the temperature differentials for roofs amounting to some 20 percent of solar radiation as explained by Stewart.16 This was to compensate for several factors, one of which is the radiant heat lost to the sky which is not included in the Mackey and Wright method. Recent experimental work by Parmelee17 and previous work by Brunt18 gives data showing the magnitude of this radiant heat loss from a roof or wall to the sky. Temperature differentials for roofs probably would be reduced be low those shown in Table 9 whenever the radiant heat lost to the sky is in cluded in calculation of sol-air temperature. The temperature differentials for roofs were based on an inside surface conductance of 1.65 because the charts prepared by Mackey and Wright10 used this value, and it was not considered practicable to repeat their work using a different film coefficient. An examination of the values given in their paper indicates that the tem perature differential would be changed very little even if a value 1.20 were used instead of 1.65. But to obtain the heat flow rates through roofs, more accurate values will be obtained if the overall heat transmission coefficient is calculated using 1.2 as the inside film conductance for summer. The roof coefficients of transmission for summer shown in Table 11 are based on surface conductances/cro of 4.0 for an outside roof surface and 1.20 for an inside ceiling surface. The outside conductance 4.0 is used for summer because it corresponds to a wind velocity of approximately 7.5 mph averaged for rough and smooth surfaces, and is more representative of summer wind velocities. Also, the lower wind velocity should be used in order to be on the safe side in determining the sol-air temperature. The inside conductance 1.20 is used because the convective portion of the film conductance for downward heat flow from a horizontal surface is appre ciably less than the winter conductance for heat flowing upward. Since there is little difference in wall transmission coefficients for summer, based on the conductances of 4.0 and 1.65, and the winter coefficients, based on 6.0 and 1.65, it is recommended that the overall coefficient U, for walls, be taken directly from the tables in Chapter 9 in which they are based on an outside film conductance of 6.0, corresponding to a 15 mph wind velocity. Advantages of Equivalent Temperature Differential Method The advantages of the equivalent temperature differential method of determining the total heat transmission are given in following paragraphs, and are apparent from Examples 6 to 7. I-. T'he total sensible heat flow is obtained by multiplying the overall heat transtabslmesou9caonedffi1c0ie. nt, U, and the equivalent temperature differential indicated in 2. The temperature, differentials listed for a few representative types of construc tion may be used on all classes of walls and roofs, even though the overall heat trans mission coefficient is different, provided the structure has thermal and physical Properties similar to one of those listed in Tables 9 and 10. 3. Adjustments can be made, according to instructions given in the footnotes, for room and outdoor conditions different from those on which the tables are based.