Document 6BBowo0Y7dg11d2om6xy1EGkg

TOWOLDMONOQ23606 TsdMfe ff mfemte SECTION A TRANSFORMER ASKARELS............................................ 1 I. Introduction............................................................ 1 II. History of Trade Name Types...............................1 Table I - The Composition of Transformer Askarels ............................................2 III. Interchangeability ................................................. 2 IV. Table 11 - Official Transformer Adcarel Shipping Specifications......................................... 3 V. Ordering Instructions ............................................2 VI. Stability....................................................................2 VII. Precautions When Handling Drums, Tank Cars and When Opening Transformers..........................2 A. Keep Dry During Handling ............................2 Table III -- Handling and Pumping Temperatures....................................4 B. Use Ordinary Personal Precautions .............. 4 C. Precautions on Opening an Askarel Transformer......................................... 5 VIII. Avoid Environmental Pollution............................5 1. Labeling Askarel Transformers...................... 6 2. Disposal of Liquid and Solid Wastes ........... 6 3. Conditioning of New or Recycled Askarel .6 4. Teardown of Transformers for Repair or Scrap ......................................... 7 6. Transformer Disposal.......................................7 IX. Expected Service Life............................................7 X. General Characteristics of Transformer Askarel Fluid............................................................7 XI. Sampling Transformer Adtarel Fluid .................8 XII. Evaluation of Askarel Received in New Equipment................................................. 8 XIII. Dielectric Breakdown Voltage - Moisture Relationship............................................9 Table IV - Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askarel and Mineral Oil......................................... 9 Table V - Approximate Solubility of Water in Transformer Askarel and Mineral Oil .... 10 XIV. Turbidity ............................................................... 10 XV. Check Points for Maintaining Askarel Insulation ............................................... 10 A. General Considerations..................................10 B. Modern Sealing Procedures ..........................11 C. The Older Sealing Arrangements..................12 XVI. Periodic Fluid Inspection and What Checkpoints Mean .....................................12 A. Visual Inspection............................................ 13 B. Dielectric Breakdown Voltage .................... 13 XVII. Inspection Checklist . . . .'................ 13 XVIII. Contamination in Transformers...........................14 Table VI -- Effect of Common Insulation Materials on Power Factor and Dielectric Strength............................................... 14 Table VII - Effect of Common Insulation Materials on Volume Resistivity of Askarel............................................................... 14 XIX. ASTM Method for Investigating the Compatibility of Transformer Insulation and Construction Materials in Askarels............ 15 XX. Refining Askarel for Re-Use............................... 15 A. Filtering Through Dry 8lotter Paper to Remove Moisture and Extraneous Particles....................................... 15 XXI. XXII. Table VIII - Water Removal by Filtering Askarel Through a Paper Press ........................ 16 B. Disposal of Solid Wastes ............................. 16 C. Solid Insulation Requiring Drying............. 16 D. Earth Treatment for Maximum Improvement of Power Factor and Volume Resistivity .......................................16 Table IX - Effect of Power Factor and Volume Resistivity ..........................17 Cleaning Arced Transformers............................ 17 Sampling Askarel................................................. 17 SECTION B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS .......................................19 I. Introduction......................................................... 19 II. Sources of Contamination ................................. 19 III. Sealing Switches and Terminal Chambers . . .20 IV. Askarel Used Under Mild Arcing Conditions . 20 V. Maintenance for Askarel F illed Switches... .20 VI. Askarel Under Excessive Temperature or Fault Conditions ............................................21 SECTION C TOXICITY AND SAFE HANDLING...............................21 I. Inhalation...............................................................21 II. Skin Contact......................................................... 21 SECTION D ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO ................................. 22 Types of Analyses Available: ............................................22 1) Routine Maintenance Check.......................................22 2) Complete Analysis...................................................... 22 31 Analysis After Earth Refinement ............................22 SECTION E APPENDICES....................................................................... 23 Appendix A - Askarel Stability and Composition of Arc Formed Gas....................................23 Appendix B -- Solubility of Gas in Transformer Askarels ...................................................... 23 Appendix C - Effect of Temperature on D ielectric Breakdown Voltage of Askarel ....................23 Appendix D -- Comparison of the Approximate Viscosity in Sayboit Universal Seconds of Transformer Askarels and Mineral Oil............................24 Appendix E -- The Density of Inerteen 54201 KA 7336-9 and Transformer Pyranol A13B3B-3............................................................24 Appendix F - Thermal Conductivity Values of Transformer Pyranol A13B3B-3................................. 24 Appendix G - Heat Capacity............................................24 Appendix H - Coefficient o^Expansion......................... 24 Appendix I - Fire Resistancd............................................24 Appendix J - Seals, Properties and Procurement .............................................................. 25 Appendix K - Caution Label ............................................25 NOTICE: "Nothing contained herein is to be construed as a recommendation to use any product in conflict with any patent. MONSANTO MAKES NO WARRANTIES AS TO THE FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OF ANY PRODUCT REFERRED TO, no guarantee of satisfactory results from reliance up on contained information or recommendations, and dis claims all liability for any resulting loss or damage." 0145676 TOWOLDMONOQ23607 -y.~c ^./>' , -V.VXK Wj' v' _ ,,'sl; IntrQdiigtion ! <J '%\ * ' ' T;tJ'ttrtB'NAr*(*.*',ilf(^< V IEEE, XstM and the National >,,.- Elwtftcelv.C<>iJe:t)ener?lly describes a broad class of fire-resistant* synthetic * chforirtated hydrocarbon insulating liquids widely used in < ,,tranSfdrm*rs, reactors $hd accessory equipment operated at power r Trequfrncte. A*karels of various compositional types are in use. (For the V geoefal properties and types see ASTM 0*2283.) Under arcing Conditions the gases produced, vyhlle consisting of predominantly ^ pqn Combustible hydrogen chloride, Can contain varying amounts of * <*' Combustible gases depending Upon the askarel type. flltilfe *< * ^ S' * ' This manual describes the operating characteristics of transformer 1 ^* ^ T '1} ytJfK ,f askereJ liquid Insulation as Manufactured by Monsanto and how it , differs from mineral oif Appropriate handling and disposal procedures for both ecrap askarel liquid and impregnated solid materials are given V fitf* V&K 'fat* Pl> Si to. accordance with the guidelines recommended by the American "MMtfJWMaKto Institute, ' 4 ; ,r , "1' ` r -V ,t faf 1 t '*V' ' The information!* basejj on facts gathered by Monsanto over 40 years 6s a producer of askerelr plus knowledge gained from the experience pf transformer mgnufqpturer*'.pfid user* This guide outlines the ' Maintenance/Squired fotluVlrtel.fluid In ''modern" transformers and L`o/fers^sugge^]ohsfOj; fe%(q^f^lntainlqg askarel in old units. By * f i 'Vk'tffBu&tV 4b guide, $e w obtain maximum service from Minimum of maintenance. If 4 --jfi Vw*'gwiftmlfHl to WflrW^tedlnfl and building of transformers. '>. Wons,hf|i|fffully acHhoWts^s -the; assistance, guidance and the ,1-con(r]W(.||f cjfwt^fOT^tSpwUnfl' ]&*.< :-.' V;iftdWrd j;i, , 'll.. History of TradeNaqto Types , `'Ajjterert fa the generic IterM fbr the flrg-retltunt liquid Insulation i *M first used by Gararpl Sectrlc Company in 1932 for their pyrffrtty* brarity name flreresinant transformers, Westinghouse Electric Corporation usos their brand n^id,)nflrt^.a cl * * *,, \ ** * * , Whatever the trademarked wan'd,;the alkarel contains chlorinated i'/. biphenyl - one of the best fltfijS 1r#uD*tlohs developed by science. This - 'lnqr^ material Is fire-resistant, heat stable, /ifion bprroilve, and has ftrjfreffeftflfrlo strength under the operating {Mod^hM fnepuotgrg^ in ygjMymwk.e. ,;x v -._ . 'f* th addition .t. -n.rJ? I 1 J`* frjtb ]dU6 Mixes' *r#(4K '(([chlorinated biphenyl), IfltiB jivltH ; chlorobenzenes to described in aBitflaft . erioibpvh . ,Sn#WJ" n^tfSrSjneV _ *v ` ,y:*ftSv\M tbrSd trBdamrk'MliM r JffJAckf difficult to WmWspnwtionti imiWS Will hot burn. ipK^lEPPLUIOS are IWEfw!i\v'.'v, ; TOWOLDMONOQ23608 , W'' ftp* ` , ' Method ASTM D2283 Type D v:TvDe E Type G Trade Names Inerteen . Inerteen 70 30 100 42 . Pyranol r A13B3B3 Ingredients (% by wt.l Aroclor 1254, chlorinated biphenyl <54% chlorine by weight) ; 70 * - ' r, ~` Aroclor!242, chlorinated biphenyl {42% chlorine by weight) , 1. 'i*-7 Ha* 100 Trichlorobonrene v v r t Phenoxypropene oxide scavenger 018 to 022);,!)'<6 to 0 22 Diepoxlde scavenger 80 40 - 0.116 to 0.136 ....."r --1-- W,: :?y ASTM Method 0 2283, titled, >'/%lot`(n9tad Aromatic Hydrocarbons (Askarals) For Transformers",'also .lists the composition of all ; transformer askarels used at varloqj^tljmefjlpce 1932- Monsanto manufactures sfmllef tranWfjhbr askarel fluids In England where the trade neme r {111. 'Inttrchanoeability^ tln'general all transformer. asmMlf've Uincchgnii! ^suggested that Srhje tfansjih `` { 'mlxino In significant prbpdrtt i 'v ..ywj&M 4V..Trantfornr M<m . Specifications for theithi .^ShCwn ln Table tl, `r '.J* V, .Ordering Instruct^, Monsanto's currentpolicy, transformer meoufecttifj(i .... Contact the manufacturer (: The transformer name ty, . ' usually gives sufficient data >*(&' "s'' mefotmx fluids only t Hniheae fluids'Vidyl'l ' \ 'i 'jw 3erf;*nd hot Monsanto ' i;>f sy iTMytf*fbrim'#f"'maRaKiB'% " tSsclffC askarel fluids Used.'-* tmhr-: Ttwmammmfi ,VI. Contamination . r Askarel insulation must haver percent of mineral oil by Votufl ^mineral oil. Over tvto I'beglns to lower to fire resistance. . .fdiiiS'r.^Cn6|T,v" 0f askarel Js mamm n In modern trensformers, > the prfrtyi .v contamination by Twater.' ,.Kwb!flij) ' el 'water-free will Insure long time service " ' " v>f<' ' ' ^% Askar*! is heavier than wate^f KSiift?" ;.v. ` fs^wei insuiati.onfwyil a tihy emount (approxlmarf" *'W/war*i 1 askafeldlssolv# Iri watefy# . ,',* /u ' * Via t ' <0* Vil. PricauTionfwhsi) Hdft ;,s Opening TrsheformlM ji; -Jhi KjlJoiSIhjj arejtlyilr'' sSOjves ** the r eeasOVt ftfioytastwanwtmii Tsf, s},/' ' iV'1 Sittuf.Spo partstsPpearb.billilo$nh : # MBtojir............................. . Vjf'jrlifVS* ' . ,,andWt#rv T,7^" V tjt . y< SPilite ' d " ' *,, f. K^ep DryWrthS lfeni(IS|Kjr|, . .............,, . In handling ftorifig, sempUnfl anu Inspecting" askarel - end In ' '^' ' '' iii #r oi<tbt>?a TOWOLDMONOQ23609 , Table II ., rM<nl^t^adBpn.TI^ ^ m's&s&si&mw' -* MM ftASTrmS33>8 lASTM 097455) iZ&C.fi'.l in. c aisamK- : TdertaanWW* "W'k' .. /ASTM 02283 Type tt _ii Westinghouse -* Transformer - Inerteen 10042* . r ASTM D2283 Type . <5w'^v>h.-'1v 450max. * _ ' cfear'.t - .*** -.^r ` S 30 max..'" -1. - - . < '-Ti3SiX^^PpSg#^. 60 max. - -' Clear '-. 35 max. \ . 0.01 max. 35KV, min - - A- >OSriWrtSC^^!l0K;,60 .; '>:4.2tb'4i5.r:C2--:. -. ;. ; , ' . -; ; ^ t".. o-s"^ ' ioo - 2 r <' * f' 4.7 to 4.9 100 - - MM spfs "'* _ <7#S*Ol80A> 5TW-fi88-56K4j 57r-' " " -s/>|| Spjeyam25715.9CV&tMWBKC K5?fe^35to1J510 Bum point tASTM 092) , ',. v,-^ - *'- None to boiling Distillation range (ASTN1020-56) corrected ., lot stem 'ar^l bju'omewic pressure g-^5^^-.aMateeK'a,fe*4 0.10 max. . . -, , . ' : .' y V'^'J ltfl53toU6173 .5610-5,12' - ' . 30 Or lower ` . .. , .; 1.518 to 1,528 ' None tob&tfng 1 st drop 20ChC/mn; 35% below 270GC ^V ...... 90%379 tb 394 :.A/ .: ^ ; _ 0X35 max. 1.6240 to 1.6260 " 82 to 92 < J -17 or lower . 1- 381 to t 392 w Noneto boiling 10% 325Cmin.; 90%36Qmax. - --6%mW mBSSTr ^orihs-^rtzOO t&2SS#C, -the.afaftiTmim mus^<^jtw&ogfttfobddeed r!uyyanr^cid:tlie0a;asakltfatf^e^tJOdMiBAdtmme*ent thee. fnoflfnowwfinna^wnacntffticeaKtfitooocstf^fs^';^'' .*.. ...2...0..0....m...a...x...,............. ..'2Wm*iu.$?ry- j;# ;im0l4''max::2;.\:- >; '0i01'.nb<. .' :3?" -52.0maxl j;? ..K-'- /.. . Clear. "s 'V. 0C18toO.22% phenoxy-propeoe oxide: pheooxYptopetie oXide ' r -* - - . jcJSw!?0** *E*pans*on <' * ".-l' "V-.I#-vi>- - 0 0007 . . . O.ocoee - ff'jy?'*' v - - ~ '` ' ^SMba^^J^Wi^iOBS'composrttonaf types are used. Under arcing Conditions ate goiti p^pd^J^^^ilWfle <Ons*5C8^4g ^ ;. - . ^^pradbe^^^'o*non-corhb<jstibte hydrogen chloride, can tndude varying amounts of coittfxrgja>BjgBes~dependtng .-r;?.s. , . - " . ' - .updntbeasfcaref type. Insulation systems incorporating these askarets and celiulosic or other orgareC mstwiaK may, . . ' when-'arced. produce caseous mnrtures which are moderately flammable. As a precaution, sucb eases should be "w*r ,n*r.t*en remoaed from the askaiel by bubbling dry nitrogen throu^i the askarel and flushing the gas space With dry nitrogen 1The* quantities are final sales q>ecificstoneonly to the extent that they coincide with Monsanto's published specifications. 2This data is based upon tnples tested in the laboratory and s not gut antted for all samples. Write us for complete sales specifications for Askarel fluids. - .- ..... 01^5679 -~ * - ' TOWOLDMONOQ23610 ....................... TMa i\.: ^ .* ... , ..................... . .. ___,t.Wkrl '.' r;.% ord drums op. thfir tidet y$jtb$he t)U(b ^4nwWt|M| "l fromfloor to keep ytmr dff the'drum tht'pDi ten be JSf* K ad Into the'askarel by the drum "breathing").This precaution 5t necessary when drums are lHd Indodri; nvtljcb Is the * preferred place for storage.,. ' -.v|p ' * 'f i * m \ |jfc--1 ' Jo avoid leakage the drums up&dl for askarVl are btvhaavy ` >4 v bonstruction. Sixteen gauge mete) jfi f^ed, with sjftpiial rtpfueil and . ' bung Construction The drums should ^e dralned'as completely a possible and then flushed bvlcewftf) (cerosede type solvent to , ^ remove atl of the eskaret.-Awuhweted liquid and washings v 'lhpuld be collected and'`thb'blfl ><<be>'incfnerated bt high `L temperatures, e.g.( about Mtroy the pgiychmlgf/libi)atied -^/.SjV>t#phaoyl* (PCBs).$ee ` '` 4 ) .*! 11 it \ > Tank oars u ed to tr^pS/fai ^ n6t used Interchangeably far `.:V-V qcts .*[ W be ( K unloaded through, the tdp.(dpTM $I?h either by pulping pr ( * ' i with controlled pressure u^tiw'diV^tjc dfy^iVoaen.Jf nitrogen* itjr l 1 ' ftai been used for unloading ft iMvPjsary to advise the Ripper so thet when the car returns fhenltrofttt pan be replaced ,, *>%'* befgte any one may enter-the car n fg be unloaded by l( li pumping it will ba necatsary to, uM,4 dryer on the air intake flno to SL> - . cdfo yrtlieh are eijahabje.for r`! ` 5%'' S# kp|ii .(.v c '*&* * ' .^PProyrdauricotl AiSb3|| , `tf# Inertoen 70-30 Inerteoh 100-44 i ' ` ------------^ ' ml . ^ rijh\nner) on the fat$ and pits of tbaJ ? 18851*? dr^ng ahef phlPafij^jr8 ) of oontecib^ifl *"jtiaitiirkS0cSl |^ay. eyCxjE <*!>'* .''-V" - TOgfer.TTOjgP1 f!< --``prolonged^intact , > . .ip ' v*> fcfF"*- "> JjS i 14&680 TOWOLDMONOQ23611 rtwrUrIW]ll by the U.S. Bureau (ogttti.: y.nder arcing jngpr |>redoiTihantly lyrgl^ir^ amount* of ^eitulostc or fube tta^epus . fljftlXpftcftutiOn. such "Stfjbubbling dry l^jf^opece with dry ^ippaatui;' ., ' ttont^Engineers Guide' j$ic|i6ns and guidance '$&($$! M Equip- ^ ^jijefctrjrial & Elec- w^orkf New York, wn^rs refer to, this r biphenyls (PCBs) which wnere over the past 40 s. ,ftjpnS, During the past jdiej&that PCBs are widely F^Y^hav can have adverse ' "i ' ' ntal Task' Force on 'pfip72 report titled, imX recommended iloal Information " |ln1aS21B1: :.j, 6Sf)fiicPKltor laWfhlirlnateti^ 0 :\n$ Ajnarlcaii' Bl&dway, Naw Iff-/''" ' ' rjjtaa are:; RFsx?,f ?'k! ' fthtie `afift disposal of Mc>ic*1 equipment. jr./?/'*'. * v' . . i" for Federal, $// . . taipfertycipation in :: MM., , . ,, committee J^ri, Electronic .. .and Electronic Jfftftrltlj; Electric (ftjlt Manufacturers tojl^ncy; Office of ^mistration; National 0H&6B1 TOWOLDMONOQ23612 3 (5 LABELING ASKARE I, TRANSFER1 4.2 2.1 New Transformeri.AH contain PCBs shall heyg'.elatjjf ofuideffugtedurability, permanently and prominently attached td the tank by the manufacture>;**'-------1------ *--------- '*- --" --------' suggei ` CAUTJO, contains ~po, .,... . . , . taken' to prevent gntw'lhtolWMi'lrOhmept. in pass malfunction 6/ leaks,'p&htuItTft'JnStiluclion manual Or the mmanuafancttuuurhefrrf,,'acwtVr,'' `,*'4i 1 4.?,z2zjnj-nBferyke'`transformers. The^transformer menu^olild'd^kebyallaftehlfMe jSafctfffitli warning #f toowrf in 4ZZ] 'ifSipt'^aiihg ............... 1 rii* N 1*'^' * ^ ' ........'' '" "` " ` ' DISPOSAL OF LIQU<0 A,W''SOU&' WAst$ (p0 161 f - 4 I.BS.I General, pifposal ofeskartets phd askaral-soakgd, materials shputd pa ecco'trlpljshctibymeans In pfilch therg'ls >t no significant release of uskfidlm, (he environment; At 1 preterit, disposal Is .eogoflpimegMjiaretyiy controlled, . Incineration of liquids trolled landfill, htfrlpV'1 .dooUfAMfbs/ere; and by com ' ^^dMSi.nardware^mm which tkar$ PtsMaA Priaent kmWpdgS WffB'lfMwaf/.ihSn^mbS must fctwjrf Jfe tempefaturemmf, Wa^mAmmmmid finally; suitable act wm...... formed; for1'Stamp 3* exqetb,6wtfe/f.i iJQfrf end Him These faclm'm of the state tmi/diMiiL.,* effluents within M>eiirriltji% Con trolledlandfillc wM. ,, KigmlmWiMtih mupmk'mdold^llfdMi; In diltstandard ISmmMi St 'tgm mtm- permitted by ffdetshj Radons , l>e ANSI Guldell with, the above redul fllVrsUch arv incln-' : erator at the W.. 0. -Sauget, Illinois 62301, 'Otfcan benia'de''for , scrap askarot ;Hc(Uld dlirr- of solid scrap a pontrplHfp s)ry3 flfjCan; beldsedwhere';:- permitted by Perietal, State arfd.locjl |lfj|a||ons, t CONDITIONING OF HEW OB 'flfepYCLED ASKAfiEL (Pf)l. 1lo6t) ,"- ......*.......,,<. ''I.f..................................... '......... 4 2 1.3 11.,'jksi kara. l jCondltlonlpt 'oulpment. the cohdl-. Honing unit should ba located aljhar inti the storage tank area or in the malri transformer, mthl/fecturlng area for filling ..........with e. skerel ( ........................... rec4y.c2le.1d.3e.s2keFruelllner^'sil'SS^irdms*lSesprk'psdmmMjttffkcntriOl eaitmmetvit' eskerel or.... The span t fuller'sAe&inbem^Jdf.l^S/mh replaced, should be Slow'd lAlwshfmorpughTy Qtlp'ptns to remove as., much Ijnufd aikm% possible The ftrtrlfte unltfofsteef mesh bonm/ctldg m^ohebleceifbf^e ''STEELCON- , TAMINATEO W! tfj'*Sf(ABEL''cohtelner for disposition, _ larthMpuld'bepieced In the 4SKARFL WASTE'1 container for disposition, , TOtr 01A568^ TOWOLDMONOQ23613 msmFOR REPAIR OR tM unit either Into a ' sm labeled "SCRAP frlfow sufficient time tpnsbnd coils "tjljiSSemb/y from the 'Reflet should be placed \d.tnQ still drips from k2 1.4,$ Place Hi '{fiatertafsiin'$e appropriate salvage '*'9 "*& *^14,4 AH used material^, Jncluding rags, sawdust, ; V rfojh**Pd< *K` regardless of^ quantity^ shall.be put into the * <"%pproprlete containers for dlspofftion. ; iiSM! ***"^TRXNlFWMfeK(Pfl: in '/ Tt)d ultimate jqfsppcet of an eskarei-filled trans " '^ettiia^.b9ai^.^i^im*Sdtrfffltfrer oftyvp Ways; 5'ivvu m f.t.v *4* * ^T** 'h i . 1 '.. wm., & means of junk dealers, This should be evglded unless a transformer /# fittf drained/ followed by ^soaking the interior with a ` ftliitabte solvent- Accumulated liquids and wasfu'ngs are to be ............. ! 0 30i^iY.j^iiH ned and Installed askarel for at ,east fail,a/lura V>flj4{)#l to.. ;tne 'manufacturers report 06% for all units under jtric Institute's report utilities failure rate for -^app. gnnjft at the General pertinent ^l. G;. Pyranol *V \y,; * .. ey>ecfe/w ^ppphcable In more recent 6, hen fla*<lS eft the main method (jl *<r^nsJotigir(.. These pWttJ te old with the ilnjl.thft fhe^tiOind Is in a nctrmeliyhafmeticalIy closed V * ','*>! ' Vt TJJ ` ?. -*tr ;L ' ,f . X..,tohgral Characteristic of Trahtforintr Askarel Fluid Appreciation of tht.following chefeCterl^ijss, at given In the IEEE Guide, leads to grtderttarVJInj the feetops.for selecting dielectric 1brfgkdjiSW yoltege iatffol!)gri aUhe pcnria practical tests to judge he; uuajity of ti,|^Mme|/`#kBre fluty, 'Also, due to these dteffsfics'thejxlynt Teetfr-pf treitffodtUtr.askarel will be normally Wv t, relatively polar >fotjnd their axes Mb'farm. ^Sl^reLalso exhibits )iInd fiaMtytJfnfce (hen insulating oil, Interpreting electrical Vv., V; %v- Q U is rclat.ely polar,$$poss&sles htgh solvency power, askarel much more electrically sensitive then mineral oil to traces of pXtfapeous soluble polar materials, and consequently the choice of TOWOLDMONOQ23614 - s'* nr: . TOWOLDMONOQ23615 1(0 Pj the X((flKcfqT exjraneous soluble pqlaf. matprlofs l^iCwtd users ors up optjn WMW,: , 1 < .bthlnenttria 1^w|p^j|yfiF^mnMwH^^|Smfge^ efc.) ..... .., ......................................... .. t&k.", >. la^TMrSpaK'UeWK* '1a ' ! f *tji1 /"4 * (^ofMMswvn or tbtf mtsadplicetion of the solid me lifiijs used In' . %'' - iv : .; V t e.i'f * * manulgfitgre ,ltf 'cohltct with {he ftskarol dhtKtshtliild be P fa,yJi ,} v,j j . >f Aiiwr. . s j||f^||A;, * ' i 'HU &'&& "JT\\ - <knft` Olfleftric Breakdown Voltage - Moisture ^elatiohsitlp <' .' -I* i-wf.jjSj-'tL'ii' 11 jl ,l,VfTMklsft^O:'^%hhettdri,eelleWct,rJicib>rrefee'<k<dlocnvy,nrv4ollttsdie oof aesskkeerreell IiSs hhiigghhly sseennssilttitvWe ttoo''eexxcceesstt ' ... v;;v:>, indlf-' .WBfHU/K.flOt.Wnfitivp to.tydifidry djssolved polai metpMs, While the' ||||| ;'v.tv'fi0 'Cl1^' ftdJeftgtrft'fy^Ikdoyrh volthg^jcen^aTfo be (owoied by1severe arcing, |*Atl<atfl {ufhs^iiotirieebly blt&fkidr has particles of sooty carbon floating ,,1 7 ergmd tiat orCur^jJ^ Theh the traitsformer should bt repaired u;;, Ihs'oiyfqiflric brtJkmrt/* Mfltefie Is'checked periodically and '43***V ?^eCfa*W'jtyniflcantiy Vityii'Indicates irtolsture pickup, arcing, or "* Wth Whan th* dielectric JbrASfcdowh tfoUagft has dropped to26KV or 1eM/ an. analysis for water`ft necessary If water if found in excess of 40 I*"* * fppm flfdom jemperatureMU Source fhould'bt located and corrections m ftp ppm (saturation level at tage jb? eskaref drops ' Mature content ** operating Iff ^btffjjiYo be! iV.a satisfactory |wlm|feW| the transformer ' a mi s to^mouij^of 6iaol>ad ffn'yoftanHASTWi D8f7) ^ 4 e.>e . . \ i^KV; vVs So ' e'SRPV; ,. . . /.. M ,. it3^,\X> ' '28 ^K-g^s.-avfcv v. -s, > ` v,a'AJI'.:-1.! i'HSst'a'Cs* A :r 'T*5.tS" * t$XT:W m OlkbbBb TOWOLDMONOQ23616 TOWOLDMONOQ23617 vA3 V'-'' j&Vy'HC ji nitrogen at 2 to "` wracjrieif'ip the area daily ^|ydden 'yreisure drop is s%M^a^kV|.jy|fe checked for *SSEM^SJra^,Vjn8 -Poxy ii mod6m ya]<)iii(^>Cor(t(Hfcttotfi <^WlX,^rfWor'f(JbniWtlons, twitch ` Ucwf*^ i\ous,nfi- 'lKrum^'ior)nections etc thould lushing Connections: A'pjnlb^r of bushings have been "Slop'll, vio^(fjjteln', rtl" for. me electrical M.'SWCllWr >J. *i Classified as .............. ..... ` A '* * . . r JeVejded to tank wall) ist ^sjh-^bUsf^Q^j^K^i molded seal to the fthjrvjjjj studamless steel or copper \ tj/ ,<l knje'' the metal to porcelain ^eing rolled into r v ^'flfWj95]6 tnoorcetyinfrver Silicone rubber rings. ,,1wwr,5~i;/^ *< "V wV rS9|l between th/;CB0 and stud IS made by >* V /'V'JfV 'A 1<f|/ rfi+t \ gjfJ* [M< t 0^/ Porcelain prelaw Jsushinds with metal to glass or . ** v ' 'Y Bolted Tvixt (Botfejl^ank wall) . Is. <est resih buvhlr^S &1W kJther cast or nn.tjl flanges b" ^t^ngre^g^ei groove. vyith flanges containing stop. ( $r circular cros^-section, rooves are suitable Hn*or nitrile rubber PB, VjR ,,.w,C90>.)Ms No. 50 'J^vv pdm'pression set .Compression is ttsket Is Cm!>6U7 TOWOLDMONOQ23618 TOWOLDMONOQ23619 ` "VlrviA' .'4 V ,Aw^. *&'. ' *M(Mii j\ *- * W3 in aSSr KMI8 W After 'lonff-ternt use 'this'',!:' H'VSMikiimllglit brawn. The fluid Should i; .Indicates . mp'-r. *:?>; s^v^yac v 'jdtfVtttttMe has decreas^ iMAiflcntiyvKv o;TDr If kitKhiaws graduahlly decrrtwswtMbefclOloW' xo "'* . SJKjJN X CHECK FOR M<Sl$fe>Rl Uie , igtf^Sfttal).......................... .*.. . IHSfeteto Mkarel Is the mejdrlm&t&f *"'' .'.'! Jiq'uld fnsulation/feesldes the ' g^lMlrm bfeakcJowrt voltage: is the only r.-, vw*,ne &**$. Welf-^|1ed eskarel A to ^0 years Oh'the original ,:v i4..................... c '' ' 4illtSIYYY / j|h;dprkenad to light brown, has no lUfiirJe breakdown voltage over 26 , Sii'A I ; oht^ipr bf.blue, green,red ..; it Is 1 Jpjefiel.s.This is not, of itself, an . liie Hr'eaKdstsvn voltage stays over., r ` iMoWSveivIhlS ff occurrence ; ; ,4h$j}ithg,tTMfMpr construction "i 'HowjmrJshen sampling j ||j|p g|.nd, pertlcul| pwmrsif t*aa?i-,T,,,,v,B3,.. V&sWuraflortllwl Stoutijfi.'.ji r ESWli|npeotiBn)M^&'in^::j{ natnwr *HfS.;S.W' Siy ' jKasjsaret aurfaci, ftfdund, tWYv. *Tl twnultW for reconditioning , tf*V >* XM|ek p*H!ciMj0;Abon.'#wi;i-. *u n&tAKMfMl '?* wsTMDMjtM kouid taNMtmf ato;i: mMSKS^. IPUNG ASKAREL'V sn mm 01*b6d9 A' vthe TOWOLDMONOQ23620 v*01^ -Jiiomposltioo on ,r,n?` lii mineral oil filled trefytforrrvatf I| of little use for this ask<re|fll|ed transformers, due to. the extrema effect of adluble'j1ar materials. Tms lrtcriasi In power factor a'iIliHStrjjt Table VI has no adverse effect on dielectric breakdown voltage. .. M'-'- I". ...."J,Ms `VS-'.'i.'., f ...Sf. ]}' ,,e, ....... . TObleVI#^:-. ,,,- jmmp , ... . Ii'l' : i. fffectof Common Insulaflp'n Materials on Po*eU Si :v'.ii::'::K;f;'S';,,-PactorandOlefaCtrlcStrength ...t H| | - , v. , (Heat Aged96Houfa|n^*arel at100"C.) . . .... -terns? ms *#>/ TOWOLDMONOQ23621 swM; If'). t -- i ' ., . '' -.. *vd&tir.. :_> i, ' . r . .: < ' ' . 'ibllity of Transform IrMaflptf C#n^1or) Materials In Marks' ^ tr " 4^/ - ,..v ;. -''ThJI."it)*thcA--,ywdfylM 'cbtai $fv, wtM.^PHwpre.' chenflltfl charaGtVfstlcsof transformer askarel fesifltir^ 'frofn .lts Controlted expoiure to insulation, and construction meterieTs, in $r$tr to evaluate their Immolate majoi "contamlnatjon'^effect on the askarel fluld. Delayed or long tl(tfe contamination effects may not be ducted. * s The method also utilize; various physical t?sts on $be Insulation arid , exposure to the askarel to ^ . ^^^P'detarrhTh^1 the pomiffltltprilf^'df tne^'maftrtai* with transformer askarel. ^Property prdppft^hetf spgcthfofts of the insulation or structural * *^8 v ****** n.ioo *,#c in % to ' #M , Jft forced draft dytm/^hflnges lo^ef^rlqal jnd chemical properties of the \ *t* < , y "Jfefyformer aejtare! ^a^jJ^tedLagalpat^ a control sample of the t^ ^ *fk*rei treated mtrM^me^af)!^lptl^lnce of the test specimens. * A ? , y Dissipation factor (AjSTM P $24) dhahge Is offe of the criteria u ed The ^ ' f askir#! fluid (i reined by^bsfrjStlve,tfeatment to a dissipation factor / - t'* V* leva! of 0 06max*at fwtfTanci wJiJJMd 0.01 max. at 25*C and 60 ' ........ > Hz, Correspond)^ ^|wi!jpT^e^k*iiiUW after heating 168 hours at .1D0C in ebsen^pl^ end 0.02 respectively, The maximum tfitilf isted for the askarel after heating In preienttf |0.20 at 100C and 60 Hz 0.04 at 2pC $iXX.'vfiRepfiTnihfnlnitf >ye Moisture and .........,yi, luch as a plate , preti flftid le YfofnSparkler, Mundelein, , - * Ulmoi* sfJSsnji J , * hff vWn MrMp> $P|ttff]e1d'Massachusetts; or vflMfi uolp"Industrial Filter \CorporAjdn, UTrV)rr,.(j a. fcftter `WW tindre for the plate '. prw ary-gvellebltf ftQnt -fcc'hfelcher 'dhd Ochuell Company, V tv W. ss /!Vt *Nw.iisinfllhiif'jnBjpt'ln^cU^eri of filterpresses luted fitted wljh theory pe^jrJIjieTs,. After filtretloh the dielectric Prfeakdpwn voltage pf the eskerel should bp,35 KVrOjnlmpj^.', y i nr - *x<*ed*. meterfals ife kgjti^1 luipmept . (Materials `Ign* a7`flexible Metal _ <i r\ 1 ^Trademark of 6,1. OufonJ; beMemburilh Company, Inc. 01 <bt9 1 TOWOLDMONOQ23622 \ . v**' j Vn* ^|. `v-` ' table vm to Mato mp|ii aS^SS^tH'Filtering Aakarafthrough .ny '-' *. Asset Through ' Wteoteer'M^ W^gwrgfll `.ffr,f 'f,V< I'* *W *. 'raperPreM ^ *" ` j * * Vjfo t ,\ r o ."'< nfi t' f - ` -V* ''.> (V- " ` i( :-.;,,41K- '^1^/5% a, ` ^ *: ad6^r ,'-'^l4^., L., v'- * TOWOLDMONOQ23623 m 1 * ,,W r.WVi ^ `itl Vii irx #(rtgthel Resistivity m(at Breakdown Vofei. Voltage lira 36C,0.r'Qap ,36.. a 100 ' 0Q,:*O " nw. 36 KV 35 36 36 36 ' ftriht takpfi to pr&vttrftMyJpji of IkjujdMKarel to effluent streams.;, 'grain dul'aH ^ark.'jftj'bon phhtamlnated askarel. Arrange to have'' the scrap fluid inQjcjDrafed ifn<W jprpppr conditions. (See ANSI CornmitteeCt07rt^^J pr%A to 48 hours; then'^ turning it tp the unit j r^a-i ' ' -A |i5TOiac^'aspossible. Many"! jmttHSgtube, hear the surfedo your sample truly? Either sample from the > pfcfldh*' are contrived on the. ,,nn, ,,,,,,ir r,,iMiaean glass, stainless steel, Viton or Teflon tubing m' sffi hey y and thoroughly 0_f , fi - n;- J * * cap'With alumfnjHP |^ wlth a Bakelite*" screw ^ njMmmended for quiok, on-site A VfriMjf W complete atitfysll is to t>0$Je, a'5-pint size sample l*i Stf.--V' - ;4kT............................................. Am A *4 tfruf'.'j'.f' ' ' (J'Wf'vVJ -<--- ?..>____ .jjj. . f.t . . *..^4 T8HP $si .. Tim that' atyWhV *! t'oltt*,TM. \ abulfi/'^hUprooMuftC^i *" *.'Tr,tHma't of Union c<f' ______1 . ppeh to collect dust op Jjplng two Or three timef-J jjn.Wthe sample will tjec O'sed. |f sample is to btp Of w/ap clear glass witfyj u,-vi'*v'V` ' ~ A,, '-.;v ' ;^oh oha warm, moist dayg . . .,;,1 leltlfblished Snd corrections medeV; l astly necessary and the unit ' itfg oyt the repaired units. /. s^iSfe-V' 0L46693 11 TOWOLDMONOQ23624 cahCp^dehse f -r '* ' f sampling askafel from transfprni'irs. it best to*take wneh thfi^nlt Is warm and ptjeratftjg 41 'twrog o* maximum load, especially for a check op moUfdta as reflected"by a dielectric breakdown voltage test $*tyij>jihg ^ y/$rm a^karal more truly represents its condition during opefatfOq: - > Vn ' A* Experience shows that water will migrate from 0 transformer's solid insulation to the askarel liquid ahd yl<5e vaf*^ depending on temperature Therefore, when the transfotfner Is hot, the moisture is most likely to be found in the hqujd* TM$ accounts largely for periodic variations in dielectric breakdown yoltage. For example, a relatively high dielectno breakdown voltage may bt found durlno winter months and a relatively |ovy dieleotr|e'brayiKdpwn voltage during the summer month* on samples taken '`from the same unit. 'v xf i ^ v1 When tasting has.tyen fipmpijeted/tnp fimeinflfr'Qf the fluid >sample should be.destroyed by/Won tempefatOre'incineration described 'n6ect,on VIII, , . ,, V , 1' A.'vsi^r'' . v-, %iw# _ rf- i^ iiia rh iifc b i^ i i " t v '- ' -Vg ..... ,,,.,,.... 01<sb69<t TOWOLDMONOQ23625 As Filled Swift andjcrml ^ r. Jed^'askard ifi^lnerdicMl-fitled ti-y. r--. -intersthrdugh tp/rrilnal chambers aTnd Wjtfihesr,-jMn m6miw Ssqs terminal Chambers arffloi used, and the Wjh vtitfcgt jeads arj connected directly tp the switch terminals They W *? Tilled V/l|h either askarel or mineral oil. Switches are usually * thtMA with I revolving block and porcelain unit as ^neprjrtcipaF fllernfent ^rfehpfed for three-phase service * ^ . . ' W itched switches have been m use for about ^'*i<:.,ih^f^'M!/:rSVn,roduce,d'the "`"'ability of insulating tivf(,ai1(ilnn tT,iH.1,i;ii t8,hilr |irtite(j ,nd 8ven ,he bes, materi8|s ` yvi'.niv OTJi uioieilai) at i--j-- . g. aske..t.ing #tj nitrile rubberandcork period of time, W;.- l'J :!ftd|ki'*ipoijl tor the expected long life of or below the switch W''?(?Ilhrou9h whlch ^ bushings '($j* S?.:^fvPe^y selected and correctly rah^ftpertment to the bther. With Ml|1^Hfer*hOve the switch, potting iRiMd/tM jskarel. When the terminal W ^ra,n int0 the terminal leri^rttege Of failure, it extremely small. When "'^.mat rwt falll/ret originate In the switch source Of Contamination. However, heavy trplati/m end asphalt'material, due to K fW,ffll;(|%(|jjnal chiihbe'rs, Wh'efi either JfJ5`>,`(t*r*!1<'0 great ^rm results. The imiYwalpaifaJiN iki4,,:ei'w;>vL':i'l.j^':..^ the' ' .m^rw9.jwc\v9uwyum.-iinB ganger is. causa *' potting if tljSl bushing seals ant HW'SKWPM'wPWP'*'* power Y 'b*"p6tfin|'bOrnpdurtd'dr Oable oil end ^Cgn* dislWrjp.lQss. If this mixture Is drawn Into the cable ,i|<' .................... i,A w '$i. v.'; ................ . -, 019069b W TOWOLDMONOQ23626 $ M*ln^ Chambers ' *' *s fero^rVuini^ fcorWtUdtlftfi, t#9 giiastifi teals and wfeldf * . 0ot<ft>ld4 is Mghly defcftebfe Has covered in Section At ' ^fittoirjfnc leal is tote used .In contact with both' tVoleJm oil, DuPontVViton Is suggested * ^; , jPof /^,;equipment the user-should aj^eclfy! thes Arr^hoomQrjt^ to keep out contan)inant^>nd rtiinlmi^e m . / ot-i mi $w!tch life {'rffifr's.r * "-*":* `. v? 0U&696 TOWOLDMONOQ23627 v ^ , i: \ J V* * - I' *mm '1 Tubturtho p| crfijUliiiAi.wsselt, illincees prreeHllnure build up cah be *$>*0 <V 4axtryfufyfpi(Jyn$ryipMtarcingconrjrtlphi- .-'IntialatlorT ' `fflnary iem On Askerel have pot Jjkrd of , potential jjtohlorfnated, more|roft).the standpoint 1 fields tfB used at ^"ptifld/elther by njj^t ventilation m *ratun - IJfjfpJ-'ba. jyythed In a .ISw ''>t, tlevated jdjf'Mto, th?`general &'" ' IfMatfan W* concantra- yfl* `'oft * vapor'Ji'MACaW f frorb 6,f i<i 1.0 milligram bar cubic *'** ft. rmL#&00.1mm6 WowaWe concen- ration of art 9+pur '-ymrlfjng <4yV Mft by^tbi Apwrlobn Conference * - of Government -Hyglenlitt are I.O.miUloftrt of 'lht lower-chtorlnatad ^M * IraPiBKS'&lf Wp retorts should M `"V' :l j/For disposal instruction^ Askarel fluids, see Section A VIII, page 6. \ ' 'JiY. .... ,v. ......... . /. 0US>697 TOWOLDMONOQ23628 Analytical Services on Transformer Askarel Available From Monsanto Transformer users not wishing to make their own fluid analyses can obtain the service from Monsanto. Simply ContacfMonsanto and specify what analyses are wanted. You will be sent the proper-j&lzed, clean sample Container, fitted with a proper label. When you receive this, carefully take your sample (following the procedure for sampling In this guide). Send the container to Monsanto's laboratory. Charges listed Include sample container and laboratory costs. The charges are those In effect March 1r 1976, and are subject to change. : . , ^, * Types of Analyses Available Analysis 1) ROUTINE MAINTENANCE CHECK , ^ v ;: 1* Total Charge: $30 00 To determine the general condition of the fluid end find Whether further analysis is necessary, (one-quart sample required) Properties Tested .. Dielectric Breakdown Voltage < > Color and Condition Moisture , You will be notified of the, results of this test. If further testing is indicated, end you Went a complete analysis, you will be sente five-pint sample Container. Ihissemple will be used for the following series of test*! v. Analysis 2) COMPLETE ANALYSIS Total Charge: $75.00 (1) To determine the extent of fluid contamination, (2) earth refinement to determine what degree of restoration of electrical and insulating properties is possible, (3) check test to see how the fluid responded tp eaffh treatment. a) Complete Analysis: to determine the extent of contamination -, Properties Tested Free Chlorides rr / Color and Condition ^ , Acidity -V Specific Gravity /' . - ' Dielectric Breakdown Voltage ', . Refractive Index . ^ ' < ,, s bovver Factor, Dteiectrlc CojtstantV Wajer / y , v; s t *`fr, . b)) EEaarrtthh RReeffiinneemmeenntt RReessppoonsned! f&J* * Consists of treatment for 2.S ^pursjrt 60-$J"*C- with 0.1 to 0.22 percent by *j and t.thheen filtration thfModggfiK^"ddrr'y fi,lltteer papder. X v * of^prpperfy conditioned Attapulgus clay c) Analysis After UboriatdtorrVy J^Sretrrtvfv RtfMeflineenmW*frltVt; ' r ,, ? Jt, ms ' . Properties Tested 1 /, rt*'n` - J Apldity * , v/ Refraotive index ' i\^||'<?le|ecvlc Breakdown Voltage Water Free Chlorides k- i You will be notified of ,fhe Asul factor, Dielectric Cope^t ana Resistivity " ,* ' it series bn your sample, fhep efterififInina your entire transformer fluid fill you can check on the results'#/ ret))"1 ^Insdislyslt: SJr' ^ u , '. Analysis 3) 1 ,^ ANALYSIS AFTER EARTH ftEFI ( .i*f * * #VtouI Charge- 16600* MBs hhis charge will not apply when" 4**` artatysef 1 end 2 have already been made.), ^ . To determine whether the entire lot of the asfcatei.dill responded to the same extent as the laboratory sample, (five-pint sample required) " - , Properties Tested .>' _ * Ff#feJZhlorides v; ' Color end Condition > ' 4 AcldHy , * t,, _ Refractive Index .a v.r ' .* - Dielectric Breakdown Voltage ; 1 Watei _ ^ Pgwer Factor, Dielectric Constant, And Resistivity To arrange for the tests described above vwfte td"vie following address: . 'David Wood ' vf Monsanto Industrial Omi B00 North iindber^ Blvd^; St. Louis, Missouri Samples fo be tested should'be clearly marked Identification and sent directly Monsanto Company * ^ wA v W.G, Krummrlch laboratory Sauget, Illinois 62201 r Attention: R, Kuster ': / > *r 01^b69b TOWOLDMONOQ23629 ** ,W .JNit)J> 1 ` tf-Ai U% f ^ - *>A$v :;v "< b'lbxjifi APPENDIX A Atksrel I retlftant, 150*C. or tmall emogntt of carbon, -Mi-fp, . > , ,*- A ~jr%g)fr$zr?w?-- ,* > A *` * APPROXIMATE COMPOSITION i ,. ? V r APtf-FORMEC GAS FR^IftANSfOhMERASKAREL blends > ; *' >T'. ' AS1MtypesDANDO , 1, , *'. '^WTfW,^ AN^YRANOl A13B30-S, ftjSPe^TIVELYI V; ' ,\ M)t>nmonpxl* O^V r j ,, > * ' 03%. ' *' "" ''T^'w'S**W***' an4 non-combustible. f*^n$a^jtion It about 100 cubic $' . .. i-?--<**^ *f f *%? 4^ \ > TOWOLDMONOQ23630 `, I (sOMPAfySON OF TH6 ARf80>i|MAlB ^W08lTY in saybolt UNIVERSAL SECONDS , OF TftANSFOUMEQ $ARELS and MINERAL oil ,, ^ , \ Temp.*C 'PVfflnol A/S63B-S ; APPENDIX E "30 Wk`i' If, , lv ?<I0' ,, , *,, * ` ;>4 EEN 70-30 llOL A1383B-3 0m/cc. \ ft, , ',VM ' 1 * of J>"1 Pyrtnol ' A1383B3 f , ' 1-67? . '685 ' t 1.632 1.510 -*' ' 'APPENDIX ' .............. Tha thermal conductivity Valyas 01 trjAsI canilmataM. dMl*# ee/ttljraoasai i This unit approxlmctlop 5pll'wji 13^363 at 27*p and " r;^approximately 0.06 B.` 5.8 x 10 * calories ft,) (P.) per foot. ....... . H"i --.twp--lift'< i^|i>i|Mii F APPENDIXH ,*> , 'M Coefficient^f ySnSTI!& The average coefficient of expaiU; ' gallon would increase to 1^066 ge|lj APPENDIX I Fire Resistance ................. Askarels of various pompositjonBl types; predominantly non-combustible hydrbgei| eskarel type. Jnsulatlotf&toerns I-r mlxtlirii i^fcdmlmoderwfv^1^ i* s \ * .. Undej arcing conditions the gates iwv$>ia uafying amounts of comtj,,*` $$iV'; : `.''v.1' A %'3t 'h \,V fa?'to" JV'/:.. ,f< f(6*^ i 4 - ^ 1 i ^ rj^per gram per *i-v Whjla consisting of depending upon the .produce gaseous ` bubbling dry ^" 0145700 TOWOLDMONOQ23631 APPENDIX J SeaIs. Properties and Procurement Dow Corning Corporation, Midland, Michigan with Districts at Atlanta, Boston, Chicago, Cleveland, Dallas, Los Angeles, New York City, Washington, D.C. and Toronto has available Bulletin 09-019, August 1962 entitled "Silastic Design Data". This lists the gasket fabricators throughout the country from whom the "Silastic 50" gasketing can be purchased in sheet, extrusions or molded shapes. Generally, Silastic 50 sheet goods are stocked by local die cutters, hence, could be generally purchased locally. Usually small quantities of gaskets are die cut. If larger quantities are needed, tools are made of the same type used to cut other elastomers. Where the gasket is extruded for fitting into a machined groove or between gasket stops, Dow Corning advises use of a scarved joint. This joint is then cemented using Dow Coming's Silastic 140 (clear) or their RTV 731 (white) materials, which air cure. Dow Corning points out that the local "rubber" fabricators purchase the Silastic 50 in billet form. This is worked on a roll mill in preparation for sheeting or extrusion. Then to obtain the desired physical properties the fabricator must oven cure the Silastic 50 for 24 hours at 480*F. SPECIFICATIONS* ASTM D676 ASTM D412 ASTM D412 ASTM D395 Color Specific Gravity at 77*F Hardness, Shore A. Scale Tensile Strength, psi, min Elongation, percent, min Compression Set after 22 hrs at 300*F, percent, max White 1.20 0.02 45 to 60 800 250 30 *AII physical properties measured on 0.075 inch thick samples molded 5 minutes at 240*F, and oven cured 24 hours at 480*F. APPENDIX K________________________________________________________________________________ Caution Label The following or equivalent caution statements should be fixed on all containers of transformer askarels and the transformers themselves: This product contains Polychlorinated Biphenyls (PCBs). Care should be taken to prevent entry into the environment through spills, leakage, use, vaporization, or disposal of liquid or containers. Avoid prolonged breathing of vapors or mists. Avoid contact with eyes or prolonged contact with skin. If skin contact occurs, remove by washing with soap and water. Following eye contact, flush with water. In case of spillage onto clothing, the clothing should be removed as soon as practical, skin washed, and clothing laundered. Monsanto MONSANTO INDUSTRIAL CHEMICALS COMPANY SPECIALTY PRODUCTS GROUP 800 N. LINDBERGH BLVD. ST. LOUIS, MISSOURI 63166 The information herein regarding obtaining optimum results from askarel fluids in your transformer has been accumulated by Monsanto for over 40 years from the experience of makers and users of askarel transformers and it is believed will be helpful. Nothing herein shall be construed as applying to other than askarel insulation. Data and maintenance suggestions herein do not apply to the other components of the transformer. All operating and maintenance suggestions recommended by the manufac turer of the transformer should also be carefully followed. Because these maintenance directions apply only to the askarel insulation, Monsanto disclaims any liability for damage to property or injury to persons arising from transformer operation. 0145701 TOWOLDMONOQ23632 U (CUSTOMER SERVICE CENTERS ASTDON. OHIO 4431S nt.aimtM4itt Arum*. MOMIA 30330 boston, Massachusetts osias Eyerert Station Td. t9W 387-8010 HOUSTON, TSXAS 77037 1301 Aott Oak Tower 8001 Mtatfiaimer Rood TV. (713) 831-9880 L0SAN08L8X CALIFORNIA 1401 Dove Street Newport Omth, California 93000 Td. (714) 933*180 NOW YORK. NOW YORK 10030 11114 Amum of the Amarleee Td. (313) 704*000 OT. LOUIS. MISSOURI 03100 900 N. Lindbergh 01*d. TO. (314)004-1000 SAN FRANCISCO OAY AROA 3710 Lafayette Sonto CNrt, California 90003 Tat. (400) 3430414 WIU4INOTON, DOLAWARS 19010 Suite 304, Santnft Old* 3411 SUverddt Road 7*. (303) 4704000 INTERNATIONAL OFFICES AROSNTINA Mmwm Argentkve SALC Avda Medero 1030, Floon 17th* 1 BuenotAlree, Argentine AUSTRALIA Momenta Auavolio Limited tan Town, Frinam Qam Old* 181 FHndera Street Melbourne, Victoria 3001 Morrnnto Auttraila LlmNad 30 Tarry Snoot RoaotN, Sydney. NSW Auttraila 3039 Momenta Auttraila Limited Fon Otflea Son I111K, Adelaide Sovdi AoanoHa 0031 Monaento Auttraila Limited Srlabana F. 0. ton S3, Hamilton Central Quoanaland, Australia 4007 Monaento Auttraila Limited Farm F. 0. Boa 77 Ooubiedew Wan Auttraila 9010 AUSTRIA Homanto GmbH Auntie RudoHapiett 13 A-IOIOWIen t.Auanla SSLOIUM Monaartto turonaSA I.FteoaMadou 1030 Orutaolt, Belgium Monaanao Europe NV/SA lOSMeMMeeaaeenwoo 3000Antwerp. BHglam BRAZIL lOONrk Royata, Sntaa 701 dm Vanootwor. SC. Canada CHILE Manaante Chile Opmartial a btduetrtei Llmlaado EddUo iapana Ofkina 80S Cana iatedo 337 Santiago da ChUe COLOMBIA Manaante CMemblene Inc. Carrera 14.No77-89 Bofota, Colombia 08NMARK Manaante A/S 0 Ryaenneentgede OK 1804 Copanhaptn Danmark 8L SALVADOR Manaante Canneamarka (81 Salvador) S.A EdHido Plata 87 AvenidaSury Celle a Santa Tacit San Salvador, 81 Salvador FINLAND Manaante (Scandinavia) AS Arkadfankttu SC 30 00100 Haitink110. Finland FRANCS Sealed Monaante SA 9 me d'Areanaon 78 Park (9) France 0UAT8MALA Manaante Guatemala Inc. Sdiflde Cam 7a Avanida 7-11 Zona 9 HONOKONO Menmnto Far Seat Ltd. Manapamant Heuaa, 2nd Floor 38 Canal Road Watt Nano Kan* ACC bNndla Chemicata Ltd. ISRa/andrenath Mukharfae Rd. Odeum 700 001, Indie ______ ..la Ltd. 3/0AaefAJi Road " V 110001. India INDONESIA R. T. Memento Fan Electronic* 101 Of. Or Sehardfo Jakarm. fndonatia ITALY Mamaato hafiana S^JL Via Matahiam Qtoie S Mdane 30134, Itaty OdpodoAu. Tokyo, Japan FatahngJaya, Selangor, Mataryaia M8XIC0 Menmnto Cemarcml SA. daC.V Thiart No. 340 Mexico 8.0.F.. Mexico oNnSorianda.H N8W38ALANO 19 Otoot Saudi Road Ramuare Auckland 8. New Zealand NICARAGUA Manaante (Nicaragua) SA F. 0. Box 300 Managua, Nicaragua NORWAY Menmnto Norpa A.S Fred dmnapata 11 Ode 1. Norway FHIUFFIN8S Montand Phlllppinet Inc. Suita 1101 Security Bank B Trurt 8700 Ayala Ave. Makati Rita10-700, Philippines FU8RT0 RICO Monaante Puerto Rico Company Munoa Rivera Ave. Sem>ouan Sr Rio Fiadraa. Puerto Rico SINQAFOR8 Monaante Singapore Company -Pta., l:o. Suite 708 Cathey Old*. 7m Floor Mount Sophia, Singapore 9 SOUTH AFRICA Monaante South Africa iFry.i Ltd. 11th Floor, Sandton City Bidg. Sandten, Trammel, South Afr-ea SPAIN SW8DSN SWITZERLAND CHB032 Zuridt, Swhxarland TAIWAN Momenta Far Eatt Ltd. (Taiwan Branch> 3d Chanp An Beat Read, 8th Floor Station 1, Taipei THAILANO Monaanto Thailand Ltd. 8th Floor. KaaatrkH Sid* 120 atom Rood Bangkok, Thailand UNITED KINGDOM Monaante Lad. IO t$ Victoria Street Momenta Haute London SW1H ONQ England VENEZUELA Momenta (Vanatuttt) CA Torre Phetpe PHo 34 WEST GERMANY Memento (Oaataakland) GmbH (34000Ooaaofdert.Weat Germany Monsanto Monaanto MunrW Chantfcah CO. / A Unit of Monants Comoany / 800 N. LlndOartfl Mvtf.. St. Louit. Mo. 63168 01*5702 TOWOLDMONOQ23633