Document 61aeYD2pLMV7aD0JV1QO0nx4
HEATINC VENTILATING AIR CONDITIONING GUIDE 1944
curial glass thermometer with a resistance winding on the bulb. Current is supplied from an external source in a measured amount. The tem perature rise shown on this heated thermometer over that shown by an ordinary thermometer at the same location, and the current supplied, make it possible to calculate the non-directional velocity of the air stream. Since a smaller bulb is used than that on the Kata-thermometer, it is less affected by radiant heat sources.
The heated thermocouple anemometer employs a thermocouple instead of a thermometer17.
Another instrument is the hot wire anemometer which is available in. several patterns. In general, a measured current is supplied to raise the temperature of a fine bare wire above the temperature of the surrounding air. With the use of a very fine wire, minute fluctuations in velocity may be measured, and the area exposed to radiant exchange with heated or cooled surfaces is at a minimum. This instrument is easily adapted to remote reading or recording. A group of them may be connected together to give the average velocity in a space, or the velocity at individual points within a test space, by suitable switching arrangements18, 19.
Deflecting Vane Anemometer
The deflecting vane anemometer consists of a pivoted vane enclosed in a case, against which air exerts a pressure as it passes through the instrument from an up-stream to a down-stream Opening. The move ment of the vane is resisted by a hair spring and a damping magnet. The instrument gives instantaneous readings of directional velocities on an indicating scale. When used in fluctuating velocities, it is necessary to average visually the swings of the needle to obtain average velocities. This instrument is very useful fpr studying mixing of air in a room20 and in locating and measuring peak velocities that may be objectionable. Various attachments are available, such as the double tube arrangement for obtaining velocities in' ducts, and a device for measuring static pres sures. Each instrument and the attachments for it must- receive individual calibration.
Propeller or Revolving Vane Anemometer
The propeller or revolving vane anemometer consists of a light re volving wheel connected' through a gear train to a set of recording dials that read the linear feet of air passing in a measured length of time.. It is made in various sizes, 3` in., 4 in., and 6 in. being most common. Each 'instrument requires individual calibration. At low velocities the friction drag of the mechanism, is considerable. In order to compensate for this, a gear train that overspeeds is commonly used. For this reason the correction is often additive at the lower range and subtractive at the
"A.S.H.V.E. Research Report No. 1165--Development of Instruments for the Study of Air Distribu
tion in Rooms; by A. P. Kratz, A. E. Hershey and R. B. Engdahl (A.S.H.V.E. Transactions, Vol. 46,
1940, p. 351).
'
- , .. .
' "Development of Testing Apparatus for Thermostats, by D. D. Wile (A.S.H.V.E. Transactions, Vol. 42. 1936, p. 349).
"Linear'Hot Wire Anemometer, Its Application to Technical Physics, by L. V. King (Journal Franklin
Institute, 1916).
^
.. "A.S.H.V.E. Research Report No.- 1204--Entrainment and' Jet-Pump Action of Air Streams, by G. L. Tuve, G. B. Priester and D. K. Wright, Jr. (A.S.H.V.E. Transactions, Vol. 48. 1942, p. 241).
660
CHAPTER 35. INSTRUMENTS AND TEST METHODS
upper range with the least correction in the middle range of velocities. Most of these are not sensitive enough for use below 200 fpm.
Measurement oi Velocities at Inlets and Outlets of Ducts
In the field it is often advisable to make volume measurements at the face of the supply openings. Often it is hard to get into the duct system, or it is difficult to find sections where the flow would be sufficiently uniform. For accuracy the instrument and its application should be checked on a similar approach and grille in the laboratory before use 'in the field.
Tests have shown that the propeller type anemometer can be used successfully on most of the common types of supply grilles21,22. The core area is divided into equal squares, and the anemometer is held against the face of the grille for the same length of time in each. To get the air volume in cubic feet per minute, the average corrected velocity in feet per minute thus obtained is multiplied by the average of the gross and net free area of the grille (core) in square feet.
On exhaust grilles, the anemometer traverse is made as described previously. The air volume may be determined by multiplying the corrected velocity in feet per minute by the gross core area of the grille in square feet and by a coefficient for average conditions of 0.85.
When a propeller type anemometer is held in a stream of varying velocities, it tends to indicate higher than the true average, that is, the speed of the propeller is nearer to the top velocity in its area than it is to the minimum velocity. This is the main reason for the large difference in ratings of unit ventilators by the anemometer method and by air volume measurements in a duct approach to the inlet24.
Any of the other anemometers described can be used within their range at the face of supply grilles when properly applied. In principle it is a case of finding the velocity at many points and using the average thus found with the correct discharge area at that cross-section. The deflecting vane anemometer equipped with a jet on the end of a rubber tube has been found especially convenient and accurate on supply grilles25. On modern air conditioning grilles the core area is used without a cor rection coefficient when the jet is held one inch away from the face of the grille. At this distance the constriction due to the thin bars has disappeared since the small air jets have reunited, and the air stream has not yet spread beyond the core dimensions. With deflecting grilles the exploring jet should be turned to the angle giving a maximum reading. This method of using this instrument is only applicable to supply grilled
^A.S.H.V.E. Research Reports Nos. 857, 911 and 966--Measurement of the Flow of Air Through Registers and Grilles, by L. E. Davies (A.S.H.V.E. Transactions, Vol. 36, 1930, p. 201, Vol. 37, 1931, p. 619. and Vol. 39. 1933, p. 373).
**A S H V.E. Research Report No. 1162--Air Flow Measurements at Intake and Discharge Openings and Grilles, by G. L. Tuve and D. K. Wright, Jr. (A.S.H.V.E. Transactions, Vol. 46, 1940, p.,313).
^A.S.H.V.E. Research Report No. 1092--The Flow .of Air Through Exhaust Grilles, by. A. M. Greene. Jr. and M. H. Dean (A.S.H.V.E. Transactions, Vol. 44, 1938, p. 387).
HA.S.H.V.E. Research Report No. 936--Investigation of Air Outlets in Class Room Ventilation, by G. L. Larson, D. W. Nelson and R. W. Kubasta (A.S.H.V.E. Transactions, Vol. 38, 1932,.p. 463)..
"A.S.H.V.E. Research Report No. 1076--Air Distribution From Side Wall Outlets, by D. W. Nelson and D. J. Stewart (A.S.HfV.E. Transactions. Vol. 44. 1938. p. 77).
661