CHAPTER 37
1954 Guide.
of refrigeration developed. The remainder of the water at the desired : low. temperature is pumped out of the evaporator and used at the point
where it is required. The ejector compresses the vapor which has been flashed in'the evapo
rator, plus any entrained air taken from the circulated water, to a some what higher absolute pressure. The vapor and air mix with the impelling steam on the discharge side of the jet; and the total mixture then passes from the ejector into the condenser.'
The slight amount of air which may be entrained in the cooled water is removed by a small secondary ejector which raises the pressure sufficiently so that the air can be discharged to the atmosphere. A secondary con denser is then necessary to condense the' steam in the secondary jet.
While a single booster of smaller than 15 tons capacity is difficult to build, steam jet vacuum cooling units have been built for as small as 5 to 6 tons capacity'. They can readily be built for steam pressures of from
n"ir'
Refrigeration
839
The Absorption System
The absorption and compression refrigeration cycles differ only with
respect to the method of compression. Each cycle requires a condenser,
expansion valve, and evaporator, but the absorption cycle utilizes three
major equipments in place of the mechanical compressor; these equipments
are the absorber, the pump, and the generator. Vapor from the'evaporator
is absorbed by a low temperature absorbent fluid which is then pumped to
the generator where heat is' supplied to boil off the refrigerant. The ab
sorbent is now cooled and readmitted, through a pressure-reducing valve,
to the absorber.
In addition to the three primary equipments of the absorption cycle it is necessary to provide auxiliary equipment, usually an analyzer and a rectifier, to remove from the refrigerant leaving the generator, insofar as is possible, the absorbent which vaporizes and leaves the generator with the refrigerant. Removal of this material is of great importance to effec tive operation of the system, since even a small concentration of absorbent
so f
Fig. 6. Diagrammatic Arrangement of Steam Jet Vacuum Cooling Unit...
5 to 200 psig, and condenser water temperatures as high as 90 F. The
steam consumption in pounds per hour per ton of refrigeration increases rapidly as the booster steam pressure is lowered. For example, the lower ing of the booster steam pressure from 200 to 90 psig results in an increase in steam consumption of approximately 5 percent, whereas a further decrease in booster steam pressure to 10 psig increases the steam consump tion by approximately 72 percent over that required at 200 psig.
The capacity of a steam jet system is usually controlled by controlling the number of boosters in use since the unit usually has several boosters operating on the same evaporator. Usually one booster is automatically controlled, whereas the others are manually operated. The capacity Is dependent, as for all compressors, upon the evaporator temperature, in other words, the suction pressure. For example, the capacity is lowered approximately 17 percent if the evaporator or chilled water temperature is lowered from 50 to 45 F. The capacity therefore can be controlled to
some extent by regulating the evaporator temperature.
Fig. 7. Closed Absorption System
m the refrigerant will suffice to reduce greatly the evaporator pressure required for maintenance of a given evaporator temperature. Thermo dynamic analysis of absorption cycles is relatively complex, and requires the use either of tables or graphs showing the equilibrium relationships mid thermodynamic properties of the refrigerant-absorbent combination. Uata of this kind are given in the first book in the bibliography. A discus-
on of various absorbents is given in the sixth book. Thermodynamically, the effectiveness of a refrigerant-absorbent combination increases directly with its negative deviation from Raouit's Law. . Kg- 7 shows a typical absorption cycle flow diagram. Cooling water
v*' c!es *iirouSh tiie absorber (where it extracts the heat of absorption which is liberated by the sefrigerant vapor as it goes into solution), then through the condenser, and finally through the rectifier. Refrigerant rom the evaporator enters the absorber where it goes into solution in the "hsorbent; the high concentration solution is then pumped to the generator
f k applied; the refrigerant (with some absorbent vapor) leaves or the rectifier and the warm low concentration solution is returned to