CHAPTER 28
1954 Guide
626
PIPE INSULATIONS
Pipe insulations are of several general forms and are made of various types of material. The most common form is the rigid sectional covering either split longitudinally into halves or cut through on one side and scored on the other, to facilitate assembling on pipes. Preformed ma-
Table 1. Heat Losses fbom Horizontal Babe Steel Pipes Expressed in Blu per {hour) (linear foot) (Fahrenheit degree difference between the pipe
and surrounding still air at 70 F)
Nominal Pipe
Size , (Inches)
1 I*
!H
-3H 45
8 10 12
120 F
150 F
60 F
0.455 0.555 0.684 0.847 0.958 1.180 1.400 1.680 1.900 2.118 2.580 3.036 3.880 4.760 5.590
80 F
0.495 0.605 0.743 0.919 1.041 1.281 1.532 1325 2.064 2.302 2.804 3.294 4.215 5.180 6.070
180 F
.. 1 227.1 F
210 F J (5 Lb)
299.7 F (50 Lb)
337.9 F (100 Lb)
Temperature Difference
110 F
0.546 0.666 0.819 1.014 1.148 1.412 1.683 . 2.010 2.221 2.534 3.084 3.626 4.638 5.680 6.670
140 F
0.584 0.715 0.877 1.086 1.230 1.512 1.796 2.153 2.433 2.717 3.303 3.886 4.960
6.090. 7.145
157.1 F
0.612 0.748 0.919 1.138 1.288 1.578 1.883 2.260 2.552 2.850 3.470 4.074 5.210
6.410 7.500
227.7 F
0.706 0.866 1.065 1.324 1.492 1.840 2.190 2.630 . 2.974. 3.320 4.050 4.765 6.100
7.490 8.800
267.9 F
0.760 0.933 1.147 1.425 1.633 1.987 2.363 2.840 3;215 , 3.590 4.385 5.160
6.610 8.115 9.530
Table 2. Heat Loss fbom Horizontal Tarnished Copper Pipe Expressed in Blu per (hour) (linear foot) (Fahrenheit degree difference between the pipe
and surrounding still air at 70 F)
Steam (Standard Pipe Size Pipe)
terials are supplied in segments for assembly on large pipes. The sectional coverings are generally supplied with a pasted-on canvas jacket. Blanket insulations are sometimes used for wrapping large pipes, .particularly
where removal for frequent servicing of the pipe is necessary. Fittings Kenrls are commonly covered with portions of standard preformed
Pipe Insulation
627
Table 3. Extehnal Sobface peb Lineab Foot of Pipe
Nominal Pipe Sub (Inches)
H H 1 IK ltt
Surface Area (Sq Ft)
0.22 0.275 0.344 0.435 0.498
Nominal Pipe Size (Inches)
2
m
3
m
4
Surface Area (Sq Ft)
0.622 0.753 0.917 1.047 1.178
Nominal Pipe Size (Inches)
5 6 8 10 12
Surface Area (Sq Ft)
1.4561.734 2.257 2.817 3.338
Table 4. External Surface peb Lineab Foot of Coppeb Tubing
Outside diameter $ in. greater than nominal size
Tube Sub (Inches)
a H
1 m 1H
Surface Area (Sq Ft)
0.164 0.229 0.295 0.360 0.426
Tube Size (Inches)
2
2H
3 3H 4
Surface Area (Sq Ft)
0.556 0.687 0.818 0.949 1.080
Tube Size (Inches)
5 6 8
Surface Area (Sq Ft)
1.342 1.604 2.128
insulation or, when' irregular in contour, with plastic materials known as insulating cements. Insulation is secured to pipes with staples which are used to bridge the joint between half sections, and with metal pipe covering bands or rings of wire which secure individual sections and effect a junc tion between abutting sections. Surface finishes used over pipe insulation depend upon the service encountered and appearance desired. Canvas jackets are most common, although asbestos paper or asbestos finishing cements are sometimes employed. Insulation outdoors should be water proof; and is generally protected with an asphalt felt for piping and asphaltic cements for fittings. Insulation on lines carrying cold water, brine, or other cold fluids is carefully finished to obtain adequate sealing against the penetration of water vapor.
The selection of pipe insulation for a particular service condition must be made with full consideration of a number of properties in addition to thermal conductivity. Factors which may be of more importance than the thermal conductivity are: ease of application, fire resistance, heat, stability; weathering stability, resistance to damage by physical. abuse, and others which may apply to a particular installation. A complete
Table 5. Abea of Flanged Fittings, Squabe Feet*
Flanged AL Coupling ZB SS)
90 Deg Ell
Long Radius Ell
Ter
Cross
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
i
IK
0.320 0.383
0.438 0.510
0.795 0.957
1.015 1.098
0.892 1.084
1.083 1.340
1.235 1.481
1.575 1.925
1.622 2.07 1.943 2.53
i* 0.477. 0.727 0.672 0.848
1.174 1.65
1.332 2.01
1.337 1.84
1.874 2.16
1.815 2.54
2.68 3.09
2.38 3.32
3.54 4.06
0.841
i* 0.945
|H 1.122
1.107
1.484 1.644
2.09
2.38 2.98
2.57
3.49 3.96
2.32 2.68 3.28
2.76 3.74
4.28
3.21 3.66
4.48
4.05
5.33 6.04
4.19 4.77
5.83
5.17
6.95 7.89
1.344 1.914 3.53 4.64 3.96 4.99 5.41 7.07 7.03 9.24
l* 1.474 2.04 3.95 5.02 4.43 5.46 6.07 7.72 7.87 10.07
6 8 10 12
1.622 1.82 2.41
3.43 4.41
2.18 2.78 3:77
5.20 6.71
4.44
5.13 6.98
10.18 13.08
5.47 6.99
9.76 13.58
17.73
5.00 5.99
8.56 12.35
16.35
6.02 7.76
11.09 15.60
18.76
6.81 7.84
10.55
15.41 19.67
8.52
10.64 14.74 20.41
26.65
8.82
10.08 13.44 19.58
24.87
10.97 13.75 18.97
26.26 34.11
Including areas of accompanying flanges bolted to the fitting.