Document 5kyBevRa9d1wqBa3EdV62Km24

CHAPTER 28 1954 Guide 626 PIPE INSULATIONS Pipe insulations are of several general forms and are made of various types of material. The most common form is the rigid sectional covering either split longitudinally into halves or cut through on one side and scored on the other, to facilitate assembling on pipes. Preformed ma- Table 1. Heat Losses fbom Horizontal Babe Steel Pipes Expressed in Blu per {hour) (linear foot) (Fahrenheit degree difference between the pipe and surrounding still air at 70 F) Nominal Pipe Size , (Inches) 1 I* !H -3H 45 8 10 12 120 F 150 F 60 F 0.455 0.555 0.684 0.847 0.958 1.180 1.400 1.680 1.900 2.118 2.580 3.036 3.880 4.760 5.590 80 F 0.495 0.605 0.743 0.919 1.041 1.281 1.532 1325 2.064 2.302 2.804 3.294 4.215 5.180 6.070 180 F .. 1 227.1 F 210 F J (5 Lb) 299.7 F (50 Lb) 337.9 F (100 Lb) Temperature Difference 110 F 0.546 0.666 0.819 1.014 1.148 1.412 1.683 . 2.010 2.221 2.534 3.084 3.626 4.638 5.680 6.670 140 F 0.584 0.715 0.877 1.086 1.230 1.512 1.796 2.153 2.433 2.717 3.303 3.886 4.960 6.090. 7.145 157.1 F 0.612 0.748 0.919 1.138 1.288 1.578 1.883 2.260 2.552 2.850 3.470 4.074 5.210 6.410 7.500 227.7 F 0.706 0.866 1.065 1.324 1.492 1.840 2.190 2.630 . 2.974. 3.320 4.050 4.765 6.100 7.490 8.800 267.9 F 0.760 0.933 1.147 1.425 1.633 1.987 2.363 2.840 3;215 , 3.590 4.385 5.160 6.610 8.115 9.530 Table 2. Heat Loss fbom Horizontal Tarnished Copper Pipe Expressed in Blu per (hour) (linear foot) (Fahrenheit degree difference between the pipe and surrounding still air at 70 F) Steam (Standard Pipe Size Pipe) terials are supplied in segments for assembly on large pipes. The sectional coverings are generally supplied with a pasted-on canvas jacket. Blanket insulations are sometimes used for wrapping large pipes, .particularly where removal for frequent servicing of the pipe is necessary. Fittings Kenrls are commonly covered with portions of standard preformed Pipe Insulation 627 Table 3. Extehnal Sobface peb Lineab Foot of Pipe Nominal Pipe Sub (Inches) H H 1 IK ltt Surface Area (Sq Ft) 0.22 0.275 0.344 0.435 0.498 Nominal Pipe Size (Inches) 2 m 3 m 4 Surface Area (Sq Ft) 0.622 0.753 0.917 1.047 1.178 Nominal Pipe Size (Inches) 5 6 8 10 12 Surface Area (Sq Ft) 1.4561.734 2.257 2.817 3.338 Table 4. External Surface peb Lineab Foot of Coppeb Tubing Outside diameter $ in. greater than nominal size Tube Sub (Inches) a H 1 m 1H Surface Area (Sq Ft) 0.164 0.229 0.295 0.360 0.426 Tube Size (Inches) 2 2H 3 3H 4 Surface Area (Sq Ft) 0.556 0.687 0.818 0.949 1.080 Tube Size (Inches) 5 6 8 Surface Area (Sq Ft) 1.342 1.604 2.128 insulation or, when' irregular in contour, with plastic materials known as insulating cements. Insulation is secured to pipes with staples which are used to bridge the joint between half sections, and with metal pipe covering bands or rings of wire which secure individual sections and effect a junc tion between abutting sections. Surface finishes used over pipe insulation depend upon the service encountered and appearance desired. Canvas jackets are most common, although asbestos paper or asbestos finishing cements are sometimes employed. Insulation outdoors should be water proof; and is generally protected with an asphalt felt for piping and asphaltic cements for fittings. Insulation on lines carrying cold water, brine, or other cold fluids is carefully finished to obtain adequate sealing against the penetration of water vapor. The selection of pipe insulation for a particular service condition must be made with full consideration of a number of properties in addition to thermal conductivity. Factors which may be of more importance than the thermal conductivity are: ease of application, fire resistance, heat, stability; weathering stability, resistance to damage by physical. abuse, and others which may apply to a particular installation. A complete Table 5. Abea of Flanged Fittings, Squabe Feet* Flanged AL Coupling ZB SS) 90 Deg Ell Long Radius Ell Ter Cross Standard Extra Heavy Standard Extra Heavy Standard Extra Heavy Standard Extra Heavy Standard Extra Heavy i IK 0.320 0.383 0.438 0.510 0.795 0.957 1.015 1.098 0.892 1.084 1.083 1.340 1.235 1.481 1.575 1.925 1.622 2.07 1.943 2.53 i* 0.477. 0.727 0.672 0.848 1.174 1.65 1.332 2.01 1.337 1.84 1.874 2.16 1.815 2.54 2.68 3.09 2.38 3.32 3.54 4.06 0.841 i* 0.945 |H 1.122 1.107 1.484 1.644 2.09 2.38 2.98 2.57 3.49 3.96 2.32 2.68 3.28 2.76 3.74 4.28 3.21 3.66 4.48 4.05 5.33 6.04 4.19 4.77 5.83 5.17 6.95 7.89 1.344 1.914 3.53 4.64 3.96 4.99 5.41 7.07 7.03 9.24 l* 1.474 2.04 3.95 5.02 4.43 5.46 6.07 7.72 7.87 10.07 6 8 10 12 1.622 1.82 2.41 3.43 4.41 2.18 2.78 3:77 5.20 6.71 4.44 5.13 6.98 10.18 13.08 5.47 6.99 9.76 13.58 17.73 5.00 5.99 8.56 12.35 16.35 6.02 7.76 11.09 15.60 18.76 6.81 7.84 10.55 15.41 19.67 8.52 10.64 14.74 20.41 26.65 8.82 10.08 13.44 19.58 24.87 10.97 13.75 18.97 26.26 34.11 Including areas of accompanying flanges bolted to the fitting.