CHAPTER 17 -
1953 Guide
/ ' ,2\, = temperature of flue gas, Fahrenheit, absolute. W = flue gas now rate, pounds per second. / = coefficient of friction.
L = length of friction duct (approximately equal to H), feet. D = minimum diameter of round chimney, feet. x and y = length and width of cross-section of rectangular, chimney, feet.
The following notes facilitate the use of Equations 3 and 4.:
1. The barometric pressure, represented by Bo, is the actual pressure at the site of the chimney and not the pressure reduced to sea level datum.
In general, the barometric pressure decreases approximately 0.1 in. Hg per 100 ft increase in elevation. : 2. The unit weight of a cubic foot of chimney gases at 0 F and sea level barometric pressure is given by the equation:
JFo = 0.131COi + 0.0950, +' 0.08317,
(5)
In this equation CO,, O, and IV, represent the percentages of the parts by volume of
the carbon dioxide, oxygen and nitrogen content, respectively, of the gas :analysis.;
For ordinary operating conditions, the value of W* may be assumed at 0.09.
,
The density effect on the chimney gases, due to superheated water vapor resulting from moisture and hydrogen in the fuel, or due to any air infiltration in the chimney
proper; is disregarded. Though water vapor content is not disclosed by:Orsat analy sis, its presence tends to reduce the actual weight per cubic foot of chimney gases.
3. The atmospheric temperature is the actual observed temperature of the outside air at the time the analysis of the operating chimney is made.. The mean atmospheric temperature in the temperate zone is approximately 62 F.
` 4'. The chimney gas temperature decreases from the breeching connection to the top of the stack. This drop in temperature depends upon the material and construction
of the stack, its tightness or freedom from leaks, its area, its height, and the velocity of the gases through it. The same chimney will suffer different temperature losses depending upon the capacity under which it is working, and the variable atmospheric conditions. No general equation covering all these variables .has been suggested, but from observations on chimneys varying in diameter from 3 to 16 ft, and in height from 100 to 250 ft, Equation 6 was deduced :s
- r-
where
Ti = temperature at the center of the connection from the breeching, Fahrenheit degrees, absolute.
He = the height of the stack above center line connection to breeching, feet.
5. The coefficient of friction between the chimney gases and a sooted surface has been taken by many workers in this field as a constant value of 0.016 for the' condi tions involved. This value, of course, would be less for a new unlined steel stack than for a brick or brick-lined chimney, but in time the inside surface of all chimneys, re gardless of the materials of construction, becomes covered with a layer of soot, and thus the coefficient of friction has been taken the same for all types of chimneys and generally constant for all conditions of operation. For reasons of simplicity and convenience to the reader, this constant value of 0.016 has been employed in the de velopment of the various special equations and charts shown in this chapter.
In important large chimney design, especially when the construction or the mate rials are unusual, it is recommended that use be made of the Reynolds number1 in determining the friction factor, f.
The following problem illustrates the use of Equation 3 :
Example 1: Determine the available draft of a natural draft chimney 200 ft in
Chimneysand Draft Calculations
413
height and 10;ft. in diameter, operating under the following conditions; atmospheric temperature, 62 F; chimney gas temperature, 500 F; sea level atmospheric pressure, B<>-= -29.92 in.- Hg; atmospheric and chimney gas density, 0.0863 and:0:Q9,,respectivgly; coefficient of friction, 0.016: length of friction duct, 200 ft. The chimney discharges
100 lb of gases per second.
Solution: Substituting these values in Equation 3 and reducing,
/0.0863 0.09\ 0.00126 X 100s X 960 X 0.016 X 200
D. = 2.96 X 200 X 29.92 X I
" n~r. I
ms v on no v n no
= 1.27 - 0.14 = 1.13 in.
Fig. 2 shows the variation in the available draft of a typical 200 ft by 10 ft chimney operating under the general conditions noted in Example 1. When the chimney is under static conditions and no gases, are flowing, the available draft is equal to 1.27 in. of water, the theoretical intensity. As
Fio. 2. Typical Set op Operating Characteristics op a Natural Drapt Chimney
the amount of gases flowing increases, the available draft decreases until it becomes zero at a gas flow of 297 lb per second, at which point the draft loss, due to friction, is equal to the theoretical intensity. The point of maximum draft and zero capacity is called shut-off draft, or point of im pending delivery, and corresponds to the point of shut-off head of a centrif ugal pump. The point of zero draft and maximum capacity is called the wide open point, and corresponds to the wide open point of a centrifugal pump. A set of operating characteristics may be developed for any size chimney operating under any set of conditions by substituting the proper values in Equation 3, and then plotting the results in the maimer shown
in Fig. 2. Fig. 3 is a typical chimney performance chart giving the available draft
for various gas flow rates and sizes of chimney. This chart is based on an atmospheric temperature of 62 F, a chimney gas temperature of 500 F, a unit chimney gas weight of 0.09 lb per cu ft, sea level atmospheric pressure, a coefficient of friction of 0.016, and a friction duct length equal to the height of the chimney above the grate level. These curves may be used for general operating conditions. For specific conditions, a new chart may be
prepared from Equations 2 or 4.