Document 5eoEOgLaE1zkY82gmgyw8g9e
Section Number: Issue Number: Original Date: Revision Date: Title: References:
Ethanolamines/Glycol Ethers
Tier 3 Procedure
1310
1.3
01-14-92
Author: Dwayne Leglue
3-28-95
Prepare Fn-500 For Maintenance
Glossary Of Equipment Identification (Text #114)
USA-5 Confined space Entry
LAD -5 Confined space Entry
1310. Preparing FN-500 For Maintenance.
1.0 Objective: 1.1 To perform this task in a safe and efficient manner without damage to equipment or injury to personnel.
2.0 Responsibility: 2.1 It is the responsibility of the operations supervisor and the senior operation specialist to ensure that this procedure is fully complied with.
2.2 It is the responsibility of the senior operations specialist and operations specialist to ensure that this procedure is executed in a safe and efficient manner.
3.0 Safety Notations: 3.1 Flash suit must be worn when racking out a cooling tower fan switch gear.
3.2 The fan blade should not be used to tie off safety harnesses.
4.0 Special Notations: 4.1 Maintenance on the cooling tower fans should be scheduled during a plant shutdown if possible. Should this option not be available to us, then we must make sure that the plant can run good with the use of just one cell on the cooling tower.
5.0 Procedure: 5.1 Shut fan down in field. Make sure water is diverted to remaining cell if it is required.
5.2 Depress stop button on switch gear in motor control center.
5.3 Rack out the switchgear with the proper safety equipment.
5.4 Have the fuses pulled by a qualified person and lockout the switch gear.
Date Printed: April 19, 1998
Paper Copies Of This Document Are Uncontrolled & Not Subject To Update. The Controlled Document Resides In File: Ctfnmain.doc
Page 1 Of 2
DO A 059039 CONFIDENTIAL
5.0 Procedure: Cont'd.
5.5 Check the field switch to be sure the motor will not run and tag the switchgear and field switch open.
5.6 After pulling the door on the fan cylinder, scaffold boards will be set up and secured.
5.7 Secure two blades of the fan by rope to prevent rotation.
5.8 People entering for maintenance work will wear safety harnesses.
6.0 Revisions
Revision No. 1
07-20-93
Yearly Review
Revision No. 2
12-23-94
Yearly Review
Revision No. 3
03-28-95
Added references for confined space entry
Date Printed: April 19, 1998
Page 2 Of 2
Paper Copies Of This Document Are Uncontrolled & Not Subject To Update.
The Controlled Document Resides In File: Ctfnmain.doc
DO A 059040
CONFIDENTIAL