Document 5bx7xBvMY1m473MEEEOQaDXk5
The ASME Code contains eleven sections
Section
Title
I II III IV V VI
VII VIII
IX X XI
Power Boilers Material Specifications Nuclear Vessels Heating Boilers Non-Destructive Examination Recommended Rules for Care and Opera tion of Heating Boders Unfired Pressure Vessels Division I--Pressure Vessels Division II--Pressure Vessels (Alternate Rules) Welding Qualifications Fiberglass-Reinforced Plastic Vessels
Rules for Inservice Inspection of Nuclear Reactor Coolant Systems
Any or all of these sections may be obtained by application to the American Society of Mechanical Engmeeis
When pressure vessels are to be put in, it is usually advisable to secuie the sei vices of a competent boiler 01 unfited piessuie vessel engineering consultant He will survey the plant or operation to deteimme the re quirements, design a system that wdl sahsfv them, and supervise installation and testing
If he arranges for the purchase of second hand boileis or pressure vessels, he should have them inspected by authorized code in spectors who will ieport on repairs necessary before pm chase Anangements for inspectors can usually be made thiough the user's in surance agent Also, the government inspec tion department that has jurisdiction is listed m the Synopsis previously mentioned
In geneial, installation and maintenance should be m accordance with manufacturers' instructions Operating personnel should be trained, not only to operate equipment pioperly, but also to make loutme safetv checks and to know when to call in qualified main tenance personnel
Some common causes of failure in pressure \essels which should be anticipated and avoided insofar as possible are
1 Errors m design, construction, and installa tion
2 Improper operation, human failure, and 1mpioper education of opeiators
3 Corrosion oi erosion of the metal
4 Mechanical breakdown, failure or block ing of safety devices, and failure or block ing of automatic control devices
5 Watei hammei, oi carryover of processed material
6 Failure to inspect thoroughly piopeilv, and frequently
7 Impropei application of equipment
8 Lack of planned preventive maintenance
In addition to hazards presented by the possibility of then explosion, heating service boileis also present fire hazards They are a significant factor m hotel, store, apartment house, and religious institution fires Partic ularly, oil-fired equipment is at fault, al though losses from explosion of gas-fired equipment have occasionally been cata strophic
The majority of boilers m use are auto matically fired, and they operate unattended for long periods Many are not maintained regularlv, and their condition is less than pei feet Because the boilers are unattended, fires that do stait can gam considerable head way unless adequate precautions are installed against them
The means for conhollmg and containing fires from boilers include
1 Pi ovide a fullv enclosed boiler room of fire-resistive construction (% in gypsum wallboaid oi bettei) (Be sure to leave sufficient space for maintenance, includ ing pulling of tubes )
2 Piovide a fire-resistive ceiling over the boilei, with diaft curtains at the penmetei of the ceiling and automatic sprinkler pro tection
3 Piovide pioper cleaiance around extenors of boiler loom walls so that combustible materials are not stored against the walls
In order to minimize low-pressure boiler fires and explosions caused by faulty controls and safety devices
1 Establish a test and servicing program whereby operating controls, safety controls, and safety and relief valves will be tested and maintained at regular intervals
1389