CHAPTER 41
1949 Guide
. -SECTION-A o' - SEC-B - *o --SEC-C -- *o--SEC-0 *o
AO-PT
20-FT
20-FT
20-FT
Fia. 7. Duct Layout fob Examplb 1 -
Example S. (Velocity Reduction Method). A duct layout is shown in Fig. 7. The fan delivers 8000 cfm. Four-oiitlets deliver 2000 'cfm each. Find duct dimen sions and total pressure loss.
' Solution. . Select velocity for Section A (1600 fprn) and reduce velocity arbitrarily along run. Find duct areas by using Equation 16. For. selection : of Circular equivalents of rectangular ducts refer to Table 2 and for. determination of friction loss in duct refer to Fig. 1 (See Example l). Results are tabulated in Table 5.
2. Equal Friction Method
When the equal friction method of.design is used, the duct system.is designed for equal friction per foot of length. This prevents one section of,,the duct from, having an excessive resistance;.compared with another. The usual procedure -in this method is to, select the main duct velocity, to be consistent with good practice from a standpoint of noise for a particular, type of building.. This velocity should be less than the fan outlet velocity. All ducts are then sized for equal friction per unit length by the use of Pig. 1. and Table 2. The equal friction method has the advantage of .automati cally reducing the velocities in. the various sections of the system and also of allowing a quick check of the total duct resistance.
. In cases where.the fan or factory assembled air conditioning unit can operate against only a limited external resistance, it is necessary to divide the permissible total resistance by the total equivalent length of the longest or most complicated run of duct to determine the design resistance per. 100 ft and then to size all ducts at this resistance value. This will aiito matically determine the duct velocities and give the desired total duct resistance. . A further refinement, which is sometimes used in large systems, is. to size each branch duct so that it has a. resistance equal to the resistance of the main system, at the point of juncture. Even when this refinement is added, regulating dampers are recommended in each branch.
- Example J+. Equal Friction Method. A duct layout is shown in Fig. 8. The fan
delivers 2500 cfm. Outlets No. 1 and 2 deliver 750 cfm each and outlet No. 3 delivers
1000 cfm. Trunk velocity is assumed as 1500 fprn; the area will be 1.67 sq ft; (240
sq in.); and the size will be 20 x 12 in. Determine sizes of ducts for sections B, C, D
and E and find the total pressure loss.
'
Solution. The equivalent round diameter of a 20 x 12 in., rectangular duct is 16.8 in. (fromTable2). Referring to Friction Chart, Fig. 1, a volume of 2500 cfm through a 16.8 in. duct gives a resistance of 0.2 in: per 100 ft. <The amount of air to be handled by each section is known and the corresponding round duct.sizes with equal pressure drop for these values can be located on the 0.2 in. friction line. The equivalent rect angular duct sizes are then selected from Table 2.
Results are tabulated in Table 6.
2-0
SECTION-A 20-FT
SEC-0,. 10*FT
SEC-C . -FT
SEC-C IS-FT
SEC-8 -FT
15-FT
5-FT
3-6
Fig. 8i Duct Layout for Example 4
AfcDuct Design
825
Section
A .. B
C D
Table 5. Tabulation of Results (Example 3) ,,,
Axb Volume
flfm
Velocity {pm
Area sq. ft.
Area -
sq. in.
Duct 8ub
in.
: Diam. . Fbxct.peb 100 FT.
Fbxct.
Loss
-in'. in. HK) in. HsO
8000 6000 4000 2000
2200 2000 1800 1600
3.64 . 524 26x20
3.00
432 22 x 20
2.22
320 . 20 x 16
1.25
180 ,12.x 16
24.8 22.9. 19.5 15.1
.25
.23 .24 . .24 .
0.10 0.05 .0.05 0.05
Total resistance, 0.25
The total pressure loss in the longest run is the friction loss in Sections (A + C 4- E), plus the shock loss in one elbow and the loss through the outlet (3). The pres
sure loss in the elbow will be assumed as 12W (Fig. 4), the equivalent length of duct
is then 10 ft and the design loss will be 0.02 in.
Friction loss (A 4- C + E).. 0.12 (Duct length ~ 20 ft -f 10 ft + 15 ft + 15 ft)
Shock loss elbow................. 0.02
Loss through outlet:...... 0.12
`
``
. Total pressure loss in duct....,......................... = 0.26 in.
The pressure required at the beginning of the main run is therefore 0.26 in. The fan selected for the duct system must not only deliver the required volume of air against this loss, but also against the losses in all air conditioning apparatus such as washers or spray chambers, heating or cooling coils and filters. /The static head required of the fan for the usual air conditioning installation is between 1 and 1.5 in. of water. About one-third of this represents losses in the duct system. The losses in the air conditioning apparatus can-be obtained from manufacturers1 catalogs.
Resizing of Ducts
In order to equalize the pressure drop in the system the following addi tional procedure is recommended.
Assume Ri, Rt, R to be the total pressure loss through ducts (1), (2) and (3); r, rb, re, ra, r0 the friction losses in the straight sections of the system; ru, ra, r,, the elbow losses, and ri, r*, r* the loss through the outlets then becomes
Ri = r + fb + 2rbo + ri f2* = r.+ r + ra + ra + r*
Ri - r + r + r + r** + U If R\ = Rt * Rt = R
n. + 2fbe .= K ^ r -- ri ' ra + ra* = <R -- r -- r -- ri
.
.* -
or with the values from Example
.
n + 2rt. == 0.26 - 0.04 - 0.12' = 0.10 in.
ra + ra = 0.26 - 0.04 - 0.02 - 0.12 => 0.08 in.
Table-6. Tabulation of Results (Example 4)'
Section
Air
Friction
Diam.
Volume PER 100 FT.
cfm in. in.
Rectan gular . Duct
-in.
Veloc- Friction
. ITT
erIOOft.
fpm '
-.in. .
Diam. in..
RectanOULAB Duct
in.-
Veloc ity
fpm
A 2500 0.2 16.8 20 x 12 1500 0.2 17 20 x 12 i6oo;
B 750 0.2 10.7 10 x 9 1190 0.286 10 10 x 8 1350
C
1750
0.2 14.8 15 x 12 1400 0.2
14.5 15 x 12 1450
D 750 0.2 10.7 10 x 9 1190 0.4 9.8 10 x 8 1350
E
1000
0.2 .12 10x12 1200.. 0.2 , 12. 10 x 12 .1300