Document 5Lzrm8Xw26qO4XNkbOzbqzVvR
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY REGION 4
Laboratory Services & Applied Science Division Water Quality Section
980 College Station Road Athens, Georgia 30605-2720
November 22, 2021
MEMORANDUM
SUBJECT:
Beulah POTW Final Report Beulah, MS LSASD Project ID: 21-0363
FROM:
Chris McHugh, Environmental Engineer Water Quality Section
THRU:
Greg White, Chief Water Quality Section
GREGORY WHITE Date: 2021.11.22 14:12:07 -05'00' Digitally signed by GREGORY WHITE
TO:
Jairo Castillo-Valenzuela, P.E., Chief
Wastewater Enforcement Section
Enforcement & Compliance Assistance Division
Attached is the Final Report for the Beulah POTW NPDES Reconnaissance Sampling Inspection.
If you have any questions concerning the sampling event, please call me at (706) 410-4082 or email me at mchugh.christopher@epa.gov.
Attachments: cc (via email): Dennis Sayre, ECAD
Sandra Aker, LSASD
Mission: To provide sound Science to our customers through superior environmental evaluation
Vision: To be a solutions-oriented organization, and seen as a leader in sound science through innovation, responsive customer service, and cutting-edge expertise
Project ID: 21-0363 NPDES Reconnaissance Inspection Report
Beulah POTW
Goose Alley Beulah, MS
Project Date: September 22, 2021
Report Date: November 22, 2021
Project Leader: Chris McHugh Environmental Engineer Water Quality Section Field Services Branch Laboratory Services and Applied Science Division USEPA - Region 4 980 College Station Road Athens, Georgia 30605-2720
The ANSI National Accreditation Board attests that U.S. EPA Region 4 Laboratory Services and Applied Science Division fulfills the requirements of ISO/IEC 17025:2017 ANAB Forensic Testing & Calibration AR 3125:2019 in the field of Forensic Testing. The activities contained in this report fall within the scope of accreditation, Certificate Number: FT-0330. Expires 31 July 2022.
LSASD ID: 21-0363
Final Report
Page 1 of 6
Requestor:
Jairo Castillo, Chief Water Enforcement Branch Enforcement and Compliance Assurance Division USEPA - Region 4 61 Forsyth Street SW Atlanta, GA, 30303-8960
Analytical Support:
Inorganic Chemistry Section Laboratory Services and Applied Science Division 980 College Station Rd Athens, GA 30605
Approvals: LSASD Project Leader:
Chris McHugh Water Quality Section Field Services Branch Laboratory Services and Applied Science Division
Approving Official:
GREGORY WHITE Date: 2021.11.22 14:14:53 -05'00' Digitally signed by GREGORY WHITE
Greg White, Chief Water Qualtiy Section Field Services Branch Laboratory Services and Applied Science Division
LSASD ID: 21-0363
Final Report
Page 2 of 6
Table of Contents
1. INTRODUCTION................................................................................................................. 4 2. SUMMARY ........................................................................................................................... 4 3. GRAB SAMPLING RESULTS ........................................................................................... 4
List of Tables and Figures TABLE 1 - INSPECTION PERSONNEL ..................................................................................... 4 TABLE 2 - EPA SAMPLE RESULTS VS. PERMITTED LIMITS ............................................. 5 FIGURE 1 - SAMPLE COLLECTION POINT ............................................................................ 5
LSASD ID: 21-0363
Final Report
Page 3 of 6
NPDES Reconnaissance Inspection Beulah POTW (Permit No. MS0042285)
1. Introduction
On September 22, 2021, a representative of the U.S. Environmental Protection Agency (USEPA) Region 4 Laboratory Services and Applied Science Division (LSASD) conducted a National Pollutant Discharge Elimination System (NPDES) Reconnaissance Inspection at Beulah Publicly Owned Treatment Works (POTW) in Beulah, Mississippi. The evaluation was requested by the ECAD Water Enforcement Branch as part of the agency's goal to address significant noncompliance (SNC) facilities. A grab sample was collected 11:23 AM and analyzed for Total Suspended Solids (TSS), Ammonia (NH3), and Biochemical Oxygen Demand (BOD5), listed on the issued NPDES Permit MS00429285. The inspection followed the procedures listed in the LSASD Project No. 21-0362 and 21-0363 Sample and Analysis Plan (SAP). Table 1 lists the sampling participants.
Inspector Chris McHugh
Table 1 - Inspection Personnel Organization
USEPA Region 4 LSASD
Date(s) on site 9/22/21
2. Summary
The facility grounds were well maintained, and the treatment system is a lagoon with a chlorine tablet disinfection system. The sample was analyzed for the parameters listed on the facility's NPDES permit (Total Suspended Solids and Biochemical Oxygen Demand).
It is recommended that the facility consider adding baffles to the chlorine disinfection chamber to increase detention time before discharge into the receiving stream. This could prevent future short circuiting during high flow events and help keep the facility from exceeding TSS and BOD5 during those events.
3. Grab Sampling Results
The grab sample was collected past the chlorine disinfection system as the water was discharged via 90 v-notch weir into the receiving stream. The sample results for all analytes were within the NPDES permit limits. Past violations that have resulted in SNC status are most likely due to the
LSASD ID: 21-0363
Final Report
Page 4 of 6
small chamber size for disinfection. Significant rain events could easily increase the discharge rate and short circuit the detention time through the chamber resulting in higher TSS and BOD5.
Table 2 - EPA Sample Results vs. Permitted Limits
Analyte TSS BOD5
EPA Analytical
Results 27 mg/L
23 mg/L *A
Permitted Limit
45 mg/L Weekly Avg.
45 mg/L Weekly Avg.
Sample Location EFF001 EFF001
DATA QUALIFIER DEFINITIONS *A - The analyte was analyzed in replicate. Reported value is an average value of the replicates.
Figure 1 - Sample Collection Point 33 47'25"N, -90 58'34"W
LSASD ID: 21-0363
Final Report
Page 5 of 6
Appendix A
The following table lists the total number of pages for each of the Analytical Datasheets for this report. Each document is contained in the PDF portfolio.
R4LIMS ID 21-0363
Lab ID
E213906-01
Analysis TSS
Total Pages 7
21-0363
E213906-01
BOD5
7
End of Report
LSASD ID: 21-0363
Final Report
Page 6 of 6
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
October 1, 2021
MEMORANDUM
SUBJECT: FROM: THRU: TO:
FINAL Analytical Report Project: 21-0363, Beluah POTW
Laura Ackerman LSB Inorganic Chemistry Section Chief John Deatrick, Chief Laboratory Services Branch
Christopher McHugh
Attached are the final results for the analytical groups listed below. This report shall not be reproduced except in full without approval of the Region 4 laboratory. These analyses were performed in accordance with the Laboratory Services Branch's Laboratory Operations and Quality Assurance Manual (LSB LOQAM) found at www.epa.gov/region4/sesd/asbsop. Any unique project data quality objectives specified in writing by the data requestor have also been incorporated into the data unless otherwise noted in the Report Narrative. Chemistry data have been verified based on the LSB LOQAM specifications and have been qualified by this laboratory if the applicable quality control criteria were not met. Verification is defined in Chapter 5 of the LSB LOQAM. For a listing of specific data qualifiers and explanations, please refer to the Data Qualifier Definitions included in this report. The reported results are accurate within the limits of the method(s) and are representative only of the samples as received by the laboratory.
Analyses Included in this report:
Method Used:
Accreditations:
Classical/Nutrient Analyses (CNA) Demand
SM 5210B (Water)
ISO
Page 1 of 7
E213906 CNA FINAL 10 01 21 0918
10/1/21 9:18
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
Sample Disposal Policy
Due to limited space for long term sample storage, LSB's policy is to dispose of samples on a periodic schedule. Air samples collected in summa canisters will be disposed of 30 days following the issuance of this report. All other sample media including original samples, sample extracts and or digestates will be disposed of, in accordance with applicable regulations, 60 days from the date of this report.
This sample disposal policy does not apply to criminal samples which are held until the laboratory is notified by the criminal investigators that case development and litigation are complete.
These samples may be held in the laboratory's custody for a longer period of time. If samples require storage beyond the 60-day period, please contact the Sample Control Coordinator by e-mail at R4SampleCustody@epa.gov.
Page 2 of 7
E213906 CNA FINAL 10 01 21 0918
10/1/21 9:18
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
SAMPLES INCLUDED IN THIS REPORT
Project: 21-0363, Beluah POTW
Sample ID 21-0363-0001
Laboratory ID E213906-01
Matrix Wastewater
Date Collected 9/21/21 11:23
Date Received 9/23/21 7:45
Page 3 of 7
E213906 CNA FINAL 10 01 21 0918
10/1/21 9:18
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
DATA QUALIFIER DEFINITIONS
A
The analyte was analyzed in replicate. Reported value is an average value of the replicates.
ACRONYMS AND ABBREVIATIONS
CAS
Chemical Abstracts Service
Note: Analytes with no known CAS identifiers have been assigned codes beginning with "E", the EPA ID as assigned by the EPA Substance Registry System (www.epa.gov/srs), or beginning with "R4-", a unique identifier assigned by the EPA Region 4 laboratory.
MDL
Method Detection Limit - The minimum concentration of a substance (an analyte) that can be measured and reported with a 99% confidence that the analyte concentration is greater than zero.
MRL
Minimum Reporting Limit - Analyte concentration that corresponds to the lowest demonstrated level of acceptable quantitation. The MRL is sample-specific and accounts for preparation weights and volumes, dilutions, and moisture content of soil/sediments.
TIC
Tentatively Identified Compound - An analyte identified based on a match with the instrument software's mass
spectral library. A calibration standard has not been analyzed to confirm the compound's identification or the
estimated concentration reported.
ACCREDITATIONS:
ISO
Accredited to ISO/IEC 17025:2017 and accreditation requirements for Forensic Science Testing Laboratories.
Refer to the certificate and scope of accreditation FT-0330 at: http://www.epa.gov/aboutepa/about-region-4s-science-and-ecosystem-support-division-sesd
NR
Not accredited for this test.
DW
Accredited for conformance with ISO/IEC 17025:2017 and testing elements in the Fifth Edition of the Manual for
the Certification of Laboratories Analyzing Drinking Water, EPA 815-R-05-004, 2005.
Refer to the certificate and scope of accreditation AT-2628 at: http://www.epa.gov/aboutepa/about-region-4s-science-and-ecosystem-support-division-sesd
ISO/DW
Accredited to ISO/IEC 17025:2017 and accreditation requirements for Forensic Science Testing Labs, and conformance with ISO/IEC 17025:2017 and testing elements in the Manual for the Certification of Laboratories Analyzing Drinking Water.
Page 4 of 7
E213906 CNA FINAL 10 01 21 0918
10/1/21 9:18
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
Project: 21-0363, Beluah POTW
Classical/Nutrient Analyses
Sample ID: 21-0363-0001 Station ID: 21-0363
Date Collected: 9/21/21 11:23
CAS Number
Analyte
Lab ID: E213906-01
Matrix: Wastewater
Results Qualifiers
Units
MRL Prepared Analyzed Method
E1640606
BOD, 5 Day
23 A
mg/L
9/23/21
2.0
9:46
9/28/21 10:45 SM 5210B
Page 5 of 7
E213906 CNA FINAL 10 01 21 0918
10/1/21 9:18
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
Analyte
Batch 2109048 - C SM5210 BOD
Blank (2109048-BLK1) SM 5210B BOD, 5 Day
Classical/Nutrient Analyses (CNA) - Quality Control US-EPA, Region 4, LSASD
Result
Reporting Limit
Units
Spike
Source
%REC
Level
Result %REC Limits
RPD
Prepared: 09/23/21 Analyzed: 09/28/21
U
2.0 mg/L
RPD Limit
Notes
U
LCS (2109048-BS1)
SM 5210B
BOD, 5 Day
Prepared: 09/23/21 Analyzed: 09/28/21
173.00
2.0 mg/L
198.00
87.4 84.6-115.4
A
Page 6 of 7
E213906 CNA FINAL 10 01 21 0918
10/1/21 9:18
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
Notes and Definitions for QC Samples
U
The analyte was not detected at or above the reporting limit.
A
The analyte was analyzed in replicate. Reported value is an average value of the replicates.
Page 7 of 7
E213906 CNA FINAL 10 01 21 0918
10/1/21 9:18
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
October 1, 2021
MEMORANDUM
SUBJECT: FROM: THRU: TO:
FINAL Analytical Report Project: 21-0363, Beluah POTW
Laura Ackerman LSB Inorganic Chemistry Section Chief John Deatrick, Chief Laboratory Services Branch
Christopher McHugh
Attached are the final results for the analytical groups listed below. This report shall not be reproduced except in full without approval of the Region 4 laboratory. These analyses were performed in accordance with the Laboratory Services Branch's Laboratory Operations and Quality Assurance Manual (LSB LOQAM) found at www.epa.gov/region4/sesd/asbsop. Any unique project data quality objectives specified in writing by the data requestor have also been incorporated into the data unless otherwise noted in the Report Narrative. Chemistry data have been verified based on the LSB LOQAM specifications and have been qualified by this laboratory if the applicable quality control criteria were not met. Verification is defined in Chapter 5 of the LSB LOQAM. For a listing of specific data qualifiers and explanations, please refer to the Data Qualifier Definitions included in this report. The reported results are accurate within the limits of the method(s) and are representative only of the samples as received by the laboratory.
Analyses Included in this report:
Method Used:
Accreditations:
Classical/Nutrient Analyses (CNA) Solids
USGS I-3765-85 (Water)
ISO
Page 1 of 7
E213906 CNA FINAL 10 01 21 0914
10/1/21 9:14
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
Sample Disposal Policy
Due to limited space for long term sample storage, LSB's policy is to dispose of samples on a periodic schedule. Air samples collected in summa canisters will be disposed of 30 days following the issuance of this report. All other sample media including original samples, sample extracts and or digestates will be disposed of, in accordance with applicable regulations, 60 days from the date of this report.
This sample disposal policy does not apply to criminal samples which are held until the laboratory is notified by the criminal investigators that case development and litigation are complete.
These samples may be held in the laboratory's custody for a longer period of time. If samples require storage beyond the 60-day period, please contact the Sample Control Coordinator by e-mail at R4SampleCustody@epa.gov.
Page 2 of 7
E213906 CNA FINAL 10 01 21 0914
10/1/21 9:14
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
SAMPLES INCLUDED IN THIS REPORT
Project: 21-0363, Beluah POTW
Sample ID 21-0363-0001
Laboratory ID E213906-01
Matrix Wastewater
Date Collected 9/21/21 11:23
Date Received 9/23/21 7:45
Page 3 of 7
E213906 CNA FINAL 10 01 21 0914
10/1/21 9:14
None
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
DATA QUALIFIER DEFINITIONS
ACRONYMS AND ABBREVIATIONS
CAS
Chemical Abstracts Service
Note: Analytes with no known CAS identifiers have been assigned codes beginning with "E", the EPA ID as assigned by the EPA Substance Registry System (www.epa.gov/srs), or beginning with "R4-", a unique identifier assigned by the EPA Region 4 laboratory.
MDL
Method Detection Limit - The minimum concentration of a substance (an analyte) that can be measured and reported with a 99% confidence that the analyte concentration is greater than zero.
MRL
Minimum Reporting Limit - Analyte concentration that corresponds to the lowest demonstrated level of acceptable quantitation. The MRL is sample-specific and accounts for preparation weights and volumes, dilutions, and moisture content of soil/sediments.
TIC
Tentatively Identified Compound - An analyte identified based on a match with the instrument software's mass
spectral library. A calibration standard has not been analyzed to confirm the compound's identification or the
estimated concentration reported.
ACCREDITATIONS:
ISO
Accredited to ISO/IEC 17025:2017 and accreditation requirements for Forensic Science Testing Laboratories.
Refer to the certificate and scope of accreditation FT-0330 at: http://www.epa.gov/aboutepa/about-region-4s-science-and-ecosystem-support-division-sesd
NR
Not accredited for this test.
DW
Accredited for conformance with ISO/IEC 17025:2017 and testing elements in the Fifth Edition of the Manual for
the Certification of Laboratories Analyzing Drinking Water, EPA 815-R-05-004, 2005.
Refer to the certificate and scope of accreditation AT-2628 at: http://www.epa.gov/aboutepa/about-region-4s-science-and-ecosystem-support-division-sesd
ISO/DW
Accredited to ISO/IEC 17025:2017 and accreditation requirements for Forensic Science Testing Labs, and conformance with ISO/IEC 17025:2017 and testing elements in the Manual for the Certification of Laboratories Analyzing Drinking Water.
Page 4 of 7
E213906 CNA FINAL 10 01 21 0914
10/1/21 9:14
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
Project: 21-0363, Beluah POTW
Classical/Nutrient Analyses
Sample ID: 21-0363-0001 Station ID: 21-0363
Date Collected: 9/21/21 11:23
CAS Number
Analyte
Lab ID: E213906-01
Matrix: Wastewater
Results Qualifiers
Units
MRL Prepared Analyzed Method
E1642818
Total Suspended Solids
27
mg/L
5.0 9/23/21
9/23/21 USGS I-3765-85
10:00
10:00
Page 5 of 7
E213906 CNA FINAL 10 01 21 0914
10/1/21 9:14
Analyte
Batch 2109047 - C 2540 Solids Blank (2109047-BLK1) USGS I-3765-85
Total Suspended Solids
LCS (2109047-BS1) USGS I-3765-85 Total Suspended Solids
LCS Dup (2109047-BSD1) USGS I-3765-85 Total Suspended Solids
Duplicate (2109047-DUP1) USGS I-3765-85 Total Suspended Solids
MRL Verification (2109047-PS1) USGS I-3765-85 Total Suspended Solids
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
Classical/Nutrient Analyses (CNA) - Quality Control US-EPA, Region 4, LSASD
Result
Reporting Limit
Units
Spike
Source
%REC
Level
Result %REC Limits
RPD
Prepared & Analyzed: 09/23/21
U
5.0 mg/L
99.100
Prepared & Analyzed: 09/23/21
5.0 mg/L
100.00
99.1 77.1-110
96.900
Prepared & Analyzed: 09/23/21
5.0 mg/L
100.00
96.9 77.1-110 2.24
Source: E213906-01
Prepared & Analyzed: 09/23/21
28.800
5.0 mg/L
26.900
6.82
3.5000
Prepared & Analyzed: 09/23/21
5.0 mg/L
5.0000
70.0 57.1-130
RPD Limit
Notes
U
10
10
MRL-2, U
Page 6 of 7
E213906 CNA FINAL 10 01 21 0914
10/1/21 9:14
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 4 Laboratory Services and Applied Science Division 980 College Station Road, Athens, Georgia 30605-2700
D.A.R.T. Id: 21-0363 Project: 21-0363, Beluah POTW - Reported by Laura Ackerman
U MRL-2
Notes and Definitions for QC Samples
The analyte was not detected at or above the reporting limit. MRL verification for Non-Potable Water matrix
Page 7 of 7
E213906 CNA FINAL 10 01 21 0914