HEATING VENTILATING AIR CONDITIONING GUIDE 1941
Table 1; Summary of Data Applied to Warm Air Research Residence
Rooms
From Chapter 7 Estimating
Heat Losses Btu
Heat Losses
B
Leader Area
Sq In.
Stack Area Sq In.
0.7 X X*4
Leader Diameter
Inches
Stack Size Net
Register Size Gross
First Floor
Breakfast___
Sun_________ Hall and stair Second Floor Owner's____ S. W. Bed___ Bath_______ N. Bed_____ Third Floor
F.. Red W Rod
17250 6810 2300 9210 25710 12570
15030 9800 2450 14800
8220 8220
= 0.009H 155 61 21 83 230 113
= 0.006H 90 59 15
QQ
= 0.005H 41 41
--
____
63 41 10 62 29 29
14 9--
8
11 or 12 Two 12
12
14 X 16 8 X 12 8 X 10 - 12 X 14 Two 12 X 14
12 X 14
11 or 12 5 X 12 9 3J-6 X 12
8 3 X 10 11 or 12 5 X 12
12 X 14 8 X 12
8 X 10 12 X 14
8 3 X 10 8 3 X 10
8 X 10 8 X 10
BOOSTER FANS
Booster fans often may be arranged to operate when gas or oil burners are running and to stop automatically when the burners shut down. The booster equipment is most effective in increasing output at low operating temperatures. According to tests, efficiencies may be advanced from 60 per cent for gravity to 70 per cent with boosters at low operating tem peratures, but at high operating temperatures gravity and booster efficiencies are almost identical9.
University of minds. Engineering Experiment Station Bulletin No. 141, p. 79, and No. 246.
358
Chapter 19
MECHANICAL WARM AIR FURNACE SYSTEMS
Furnaces, Fans and Motors, Sound Control, Sprays and Filters, Air Distribution Design, Automatic Controls, Design of Heat ing System, Selecting the Furnace, Selecting the Fan, Heavy Duty Fan Furnaces, Humidification, Cooling Methods, Cooling
System Design
MECHANICAL warm air or fan furnace heating systems1, which are a special type of central fan systems, are particularly adapted to residences, small office buildings, stores, banks, schools, and churches. Circulation of air is effected by motor-driven fans instead of by the difference in weight between the heated air leaving the top of the casing and the cooled air entering its bottom, as in gravity systems described in Chapter 18. The advantages of mechanical systems, as compared with
gravity systems are:
1. The furnace can be installed in a corner of the basement, leaving more basement room available for other purposes.
2. Basement distribution piping can be made smaller and can be so installed as to give full head room in all parts of the average basement, or be completely concealed from view except in the furnace room.
3. Circulation of air is positive, and in a properly designed system can be balanced in such a way as to give a greater uniformity of temperature distribution.
4. Humidity control is more readily attained.
5. The air may be cleaned by sprays or filters, or both.
6. The fan and duct equipment may be utilized for a complete cooling and dehumidi fying system for summer, using either ice, mechanical refrigeration, or low temperature water for cooling and dehumidifying, or adsorbers for dehumidifying,
7. The use of the fan increases the volume of air which can be handled, thereby increasing the rate of heat extraction from a given amount of heating surface and insuring sufficient air volume to obtain proper distribution in a large room. .
Much of the equipment used in central fan systems is the subject matter
of other chapters. It is the purpose of this chapter to discuss the co
ordinated design and to deal in detail only with problems not covered
elsewhere which refer particularly to the whole problem of fan warm air
furnace heating and air conditioning.
__
*See University of Illinois Engineering Experiment Station Bulletin No. 266 by A. P. Kratz and.S. Konzo . for details of tests conducted in Warm Air Research Residence.
359