American Society of Heating and Ventilating Engineers Guide, 1930
always available gas is highly desirable, as it saves the trouble of operating a steam boiler.
Where steam is available it is probably more satisfactory than gas in that it can do no harm if a unit boils dry, whereas with gas under such a unit serious damage might ensue.
For ranges and ovens hard, liquid or gaseous fuels may be used. Elec tricity finds a wider use for cooking as each day passes.
Water Consumption
Hot water requirements for kitchens may be taken as 20 gal. per hour for each sink faucet and 40 gal. per hour per 1,000 pieces capacity per hour of dishwasher; There is a peak load which occurs at dishwashing time, and this may be met either by instantaneous heaters or by storage type heaters. The requirements of the dishwashing machine are somewhat under control of the operator, for by more liberal use of steam less hot water is'used, and vice versa.
Cold water requirements are approximately double the hot water . requirements.
Water Connections
*
Hot and cold water connections to sinks are 34 in.; hot water only is
provided for dishwasher from 34 to 134 in- according to size: 34 in. hot
and cold water to "bain marie"; and 34 in. cold and hot water to coffee
urns. Stock kettles, soup kettles, vegetable steamers, roasting steamers
and potato peeler sinks are frequently provided with a 34 in. faucet over
each of them, supported independent of the fixture. Generally hot water
only is so connected. These are not an absolute necessity but often a
great convenience. Drinking fountains and water coolers require }4 'n-
cold water connections.
I
In sizing mains to care for two or more items make the mains about one-half the sum of the areas of the branches.
Steam Consumption
The dishwashing machine will consume from 50 to 100 lb. of steam per 1,000 pieces capacity of machine, per hour. An allowance of 150 lb. steam per person per hour will meet all steam requirements for kitchens, except dishwashing machine and water heating.
The average steam requirements for a kitchen serving 300 to 500 persons will be cared for by .a 25 to 30 hp. boiler- The annual consumption of such a kitchen will be about 2,000,000 lb. of steam.
Connections for Steam Supply
Steam connections to jacketed kettles, soup kettles, vegetable steamers, steam tables, coffee urns, plate warmers and roll warmers are J4 in. each, for smaller sizes and 34 in. each for larger sizes and in cases where runs are long. Steam connections to dishwashing machines are 34.t 134 inaccording to size.
In sizing mains to take care of two or more items make the area about orie-half the sum of the branch areas, keeping the sizes well up toward the ends of the runs.
390
Chapter 22--Piping and Equipment for Laundry, Kitchen and Hospital Service
Return Connections
Return connections are uniformly 34 in- size and are made to all kitchen equipment having steam connections, except the spray to dishwashing machine. However, the coil in this machine requires a return connection.
Each unit or separate- coil should be provided with a J4 in- thermo static trap. If more than one unit or coil is connected to the same trap, air binding will result. Connections of the same size as for the traps are made to return mains. .
Steam Pressure Limits
Not less than 30 lb. and not over 50 lb. are the usual pressure limits for steam cooking. Lower pressures down to 1 lb. are ample for warmers, but the steam kettles require higher pressures and it is customary to carry the higher pressures mentioned on all equipment. All jacketed pots have safety valves usually set at 50 lb. and usually vacuum breakers are required on the jacketed fixtures to prevent collapse under vacuum con ditions.
Grease Traps
The dishwashing machine, all pot sinks, pan sinks and any sinks into . which grease may find its way should be provided with grease traps. When grease traps on the individual fixtures are used the cold water supply to the fixture is connected to pass through the jacket of the grease trap.
Connections to Gas Appliances
Obtain from the manufacturer the gas consumption per hour of the different fixtures to be used and size the gas pipes accordingly. - Excellent tables for this purpose, when the gas consumption and length of run are known, are-given by the American Gas Association. .
As an approximation the following connections commonly are found in equipment of average size: Bake shop oven, 134 >n-: pastry oven, % in.;
dishwashing machines, 34 to 134 in.; broilers, 1 to 134 in-; ranges, 1 to
2 in.; small ranges in diet kitchens, 1 in.; salamanders and warmers, 34 in. and steam tables, 1 in. .
Motor Sizes Required
Dishwashing machines require 1 to 2 hp. per 5,000 pieces capacity per hour to drive, with the smallest machine using 34 hp. motor. Kitchen mixing machines take 34 t0 1 hp.; bake shop combinations, 2 hp. per barrel rating of machine. The 17 in. meat, food and vegetable choppers require 1 hp. and the 20-in. size requires 2 hp. Coffee grinders, knife polishers,-silver burnishers need nominal amounts, about J4 hp. Vege table peelers take 34 to 1 hp. according to size. Allow 34 hp. for a 25-qt. ice-cream freezer and 1 hp. for 40-qt. size:
Electricity Required for Cooking
In a complete electric kitchen, i.e.t one in which ranges, broilers and hot-plates are electric, the minimum amount of electricity required for a complete mealis-about as follows: