LIMIT SWITCH REPLACEMENT - PHASE III Aberdeen Chemical Plant July 22, 1986
Frank G. Jeanson PROCESS ENGINEER REVIEWED BY: J. G. Cole SR. PROCESS ENGINEER APPROVED BY: Veldon E. Messick CHIEF PROCESS ENGINEER
VAB.0001098809
LIMIT SWITCH REPLACEMENT PHASE III Aberdeen Chemical Plant
TABLE OF CONTENTS
I. PURPOSE AND PROCESS DESCRIPTION
II. VALVE LOCATION
III. IV.
INSTRUMENT SPECIFICATIONS
DRAWINGS
*
VAB.0001098810
LIMIT SWITCH REPLACEMENT PHASE III Aberdeen Chemical Plant
Purpose and Process Description
Lack of positive valve position indication in the control room has the potential to cause safety, operational and environ mental problems. The existing limit switches indicate actuator position and not the actual valve stem position. If the coupling fails or is spread, the valve could be open or partially open and still give a closed signal.
This design will provide each of the designated valves in
section A of the following table with a new limit switch that
indicates valve stem position. These new limit switches will
provide accurate indication of valve position to the control
room or the Modicon. The limit switches will be mounted
the bracket between the valve and the actuator, Drawings several different type valves with the new limit switches attached. Limit switches will be replaced on 80 valves.
on of
VAB.0001098811
(
II. Valve Location A. Valves that would cause quality, safety or environmental problems without proper indication
General Location Valve #
1. Reactors 741, 742
1-6
743, 744, 745 & 700
Valve Description Rinse Supply
7-12
Chem Wash (CW) Supply
13-18
Clean Reactor
19-24
Clean Condenser
25-30
Steam stripping
31-36
Emergency AMS Injection
* Two valves would have to leak
valve failure would cause VCM
.2 Reactors 300, 400
500 and 600
37-40
Chem wash to Reactor
41-44
Chem wash to Condenser
45-48
Rinse to Reactor
49-52
Rinse to Condenser
53-56 57-60
Steam Stripping Emergency AMS Injection
Reason
*2--valve leak, VCM enter rinse. Rinse supply valve leak, water dilute chem wash.
VCM Chem wash supply valve leak, CW in rinse
2-valve leak, VCM enter rinse or CW. 2-valve leak, rinse or CW in reactor.
2-valve leak, VCM enter rinse or CW 2-valve leak, rinse or CW in reactor
1-valve leak, steam in reactor or VCM in steam.
AMS
Such as rinse supply and reactor cleaning
2-valve leak. VCM in chem was or chem wash in reactor
2-valve leak. VCM in chem wash or chem wash in reactor
2-valve leak. VCM in rinse or rinse in reactor
2-valve leak. VCM in rinse or rinse in reactor
1-valve leak. steam in reactor or VCM in steam
1-valve leak. AMS in reactor
VAB.0001098812
General Location Valve No.
3. Batch Water Strip- 61-64 pers (North & South)
65-66
Valve Description To Sewer, To Centrate
Fill Line
67-68
VCM Bleed
69-70
Recovery
71-74
To ERS
75 VCM Double Block and Bleed venting to FVSfs.
4. Chem Wash Tank
76-77
78 79
Steam Pressurization
To Reactors (New Module) To Reactor (Old Module)
5. Blowdown Tank
80 To Batch Water Strippers
Reason
1-valve leak, VCM contaminated water to sewer.
2-valve leak, contaminate vessel In stripping mode
2-valve leak, contaminate vessel In stripping mode.
2-valve leak, contaminate vessel in stripping mode.
2-valve leak, contaminate vessel in stripping mode.
Three way valve-if not in correct posi tion, contaminate vessel in stripping mode.
1-valve leak, contaminate vessel in stripping mode.
1-valve leak, safety hazzard when a reactor is blanked out. 1-valve leak, safety hazzard when a reactor is blanked out.
1-valve failure, lead to tank over pressuring and discharging to sewer.
*
B. Remaining valves that are Indicated on the panel or that are tied into the Modicon that will not have limit switches replaced.
General Location 1. New Module
Valve No.
Valve Description
a. Chem Wash Tank
1 2 3 4
Tank Outlet Tank Bypass Tank Inlet Recirculation
b. Blowdown Tank 5 Recirculation 6 To Emission Recovery System 7 To Recovery System 8 To Recovery System
c* Reactors 741-745 d. Recovery System
9-13 14-18
*
19 20 21 22 23 24 25 26 27 28
Inert Vent Steam to Jacket
Compressor suction manifold Compressor suction manifold Suction north compressor Suction middle compressor Suction south compressor
Pressure equalization valve Suction north vacuum pump Suction south vacuum pump Discharge north vacuum pump Discharge south vacuum pump
* These valves have indication for the open position only.
e. Evacuation
29 EE-200 first stage steam 30 Evacuation valve to EE-200
General Location f. Colloid charge
g. Hot water charge
h. Rinse water
1, RVCM charge Old Module a. Chem Wash
b. Batch water strippers c. Reactors d. Recovery system
Valve No,
31 32 33 34 35 36
37 38 39 40
41 42 43 44
45
1
2
3 4
5-6
7-11 12-16
7 8 19
20
Valve Description
PVA pump discharge PVA makeup tank outlet PVA charge tank inlet Methocel pump discharge Methocel makeup tank outlet Methocel charge tank inlet
Pump suction Primary pump discharge Secondary pump discharge Hot water tank make-up
Rinse water supply Rinse pump bypass To top of reactors Cold water swirl
Pump discharge
Tank outlet Tank inlet Tank bypass Chem wash from EA-357 to FA-776
Steam stripping
Inert vent Steam to jacket
Suction east compressor Suction west compressor To ERS From batch water strippers
General Location e. Emission Recovery System f. Evacuation g. Colloid Charge h. Hot water charge
1, Rinse water
j. RVCM charge
Valve No
21 22
23 24
25
26 27 28 29
30 31 32
33
Valve Description
VCM Tank farm recovery Batch water stripper recovery
EE-100 first stage steam Evacuation valve to EE-100
Pump discharge
Primary pump discharge Secondary pump discharge Pump suction Hot water tank make-up
Hot water rinse Rinse supply Rinse pump bypass
Pump discharge
VAB.0001098816
Limit Switch Replacement - Phase III Aberdeen Chemical Plant
III. Instrument Specification Item
PLS-101 through 180
Description Proximity Limit Switches
,,pi
A
r
VAB.0001098817
PLANT
ITEM NO. SERVICE
VtSt\
C'k.fifVX i
4
VISTA CHfMICAl COMPANY PtCATKMSMUT
specification data shut
PROJECT NO A.F.E. NO. P.O. NO.
PROJECT V-- i A\
iA>\,
u`t /W1
'X Rtlnn i nmi <s
* "1
-it-
# *
0 UMUl III 11W U iUUt 11 in Wi UJIUHI lui,
*t
/U'
t ->V
'--I V
/a.
< 4
r *<
. r:&
$$3.* A!{jT
.afci
t '-rf &Wy
ei*<
- *f V j ^
r/- * ' J - -*
*, r V,,r;iv i'* *-'**:... y
^ VO'i'*;-"'.
1 * . f , V*
SS
*+
1 . 1 >*v
*V* v-'- >1 ^-1Pm
\!g$j2
s*& ^
V
t, .-
'% -^w^v . -f
* '*' -1 > '
II
*>
v-w
*i >* t* \ ,u*
**
r
i
11
i *
m fV-: IW.
siJtfocasMKj.v,*,[/5*FSJ*w
i h
' -< *
* ^nV7JOVv'S,jrf */: .^r v
< * ,
"vr-;1-; .tw-r ^>v>v-a,!v' / T s
'*- 'jy vf" 'Vr ( Vtu.
.^
^
'i ^
^ 1 U 't r * t
*V 'twj*
lh wJr^
h 4]T
**
- rA#' / * >/ *
* .VM* ^V,r
`f
-. *
t *
. . . .:. 'v.m'i'.W' "-
iiMi!
*/ GS=i
V~
Am 4
Ip g$& Ui \*9 'JH
t-ui*<'fJ1 >nJ (/</>"*** ^ Mt* <
/
'A *1
^
.%
v
t/t. * I.i
*1^
rh
-s
* K *. <
ri ^j4- ^
''V-iA
J' 1>* r * |i> v 1 k
" '
'i^*v^4-+7}?'X
.fO'Zfr
f - i jt'- -1 f;`
I 'A
;*
,
^
I
.Tit'/, **V * r-4.- j' . v~ v
rvl*rw,ft{?;v;. .* : :
tS&&'!;v'''* ''
n
j.^: s r * - * I*** *,,,* - *
< j> -
rV*;*h>.;
* -w
ft t
VAB.0001098819
iH. - t
u:i i I
End Cap: .050" Stainless Steel (304) End Cap. available with thicker End Caps for higher pressure.
Pressure Options: Normally the standard 5/8" diameter will withstand 2000 PSI. Larger cases with thicker walls and front End Caps will allow the switch to function at much higher pressures (up to 10,000 PSI). Certification available as factory option. Case: 300 Series Stainless Steel case, plain or threaded body (5/8-18 NF). Different body lengths available, SEE options on MODELS AVAILABLE.
Magnets: Made with a high energy product magnet. An excellent coercive force which converts into grams of Contact Pressure for reliable operation. Meets MM PA Specifications. External Threads: Machines to meet SAE 5/8-18 UNF Specifications. Units available with or without threads.
Contacts: Type Silver, Cadmium Oxide, resists welding and is some of the most widely used Contact Material in the industry. Sized to withstand approved ratings. Hermetically Sealed Contact Chamber. Bearing: Consists of a finely ground Stainless Steel Pin and durable plastic housing. Sized to withstand a wide temperature range. Resists seizing and gives millions of free operations.
Potting: Terminal cavity filled with epoxy resin com pound for sealing and mechanical support of wire/ cable connections.
4
Body Tube: Made of Free Mechanical Stainless Steel. Resists most all harsh environments and withstands high working pressures. Impervious to water, oils and gases.
Internal Threads:1/2-14 NPT. complies with CSA requirements for Explosion Proof Applications. Wire or cable leads available to meet Customer's Specifications.
i
VAB.0001098820
When time, accuracy, and dependability count... you can count on the 70 Series GO* Switch Maintenance tree; engineered for precision, performance and reliability.
The standard 70 Series GO* Proximity Limit Switch has been designed and built to rugged specifications for use in most industrial and environmental applica tions. Each switch is totally enclosed, hermetically sealed and capable of operating in hostile environments.
The standard stainless steel housing is impervious to oils, caustic acids, water laden areas and most
Standard Models
atmospheric conditions, with a broad operating temperature range. (See specification) Many different models of the switch are available for your design needs. (See ordering information for specifications, detail and options.)
Hazardous Location approved
models for Class I, Division 1, Ail Groups
Model 713360 No conduit connection. 18" 3 conductor cable with water resistant squeeze connection, tyoe 300 stainless steel housing with K-18
NF x 1.5" threads with 2 lock nuts.
Model 713570
V% NPT conduit outlet. 181* 3 conductor cable, type 300 stainless steel housing with K-18
NF x 2.813" threads with 2 lock nuts.
Model 713524 Va NPT conduit outlet with 18" potted, 3 conductor cable, type 300 stainless steel housing, no threads.
Model 713420 No conduit outlet. 18" potled. 3 conductor cable, type 300 stainless steel housing; no
threads.
m0
j^
Model 713460 No conduit outlet. 10" potted, 3 conductor cable, type 300 stainless steel housing with
K-18 NF x 1.5" threads with 2 lock nuts.
Model 713660 No conduit outlet, 18" potted. 3 wire leads, type 300 stainless steel housing with K*18 NF x 1.5" threads with 2 lock nuts.
Model 713720 Va NPT conduit outlet with 18" potted, 3 wire leads, type 300 stainless steel housing, no threads.
Model 713564 Va NPT conduit outlet with 18" potted. 3 conductor cable, type 300 stainless steel housing with K-18 NF x 1.5" threads with 2 lock nuls.
Model 713574 Va NPT conduit outlet with 18" potled, 3 conductor cable, type 300 stainless steel housing with K-18 NF x 2.813" threads with 2 lock nuts.
rtodel 713520 4 NPT conduit outlet. 18!' 3 conductor cable,
ype 300 stainless steel housing, no threads.
Model 713760
Va NPT conduit outlet with 18" potled, 3 wire leads, type 300 stainless steel housing with
K-18 NF x 1.5" threads with 2 lock nuls.
Model 713724
Va NPT conduit outlet with 18" potted. 3 wire leads, type 300 stainless steel housing, no threads.
odel 713560 NPT conduit outlet with 18!' 3 conductor
able, type 300 stainless steel housing with -18 NF x 1.5" threads with 2 lock nuts.
Model 713770
Va NPT conduit outlet, 18" potted 3 wire leads, type 300 stainless steel housing with K-18 NF x 2.813" threads with 2 lock nuts.
Model 713764
Va NPT conduit oullet with 18" potted. 3 wire leads, type 300 stainless steel housing with K-18 NF x 1.5" threads with 2 lock nuls.
*1>
I**Jr V i r *t
Approved switches are in compliance with current
bulletins 1243. 1273 and 1308
Model 713774 Va NPT conduit outlet with 18" polled. 3 wire leads, type 300 stainless steel housing with " 18 NF x 2 BIS*1 threads
jeso switches are U/L and CSA approved for Industrial control, general purpose use. See hazardous locatioiy^*000^0988^
tproved models in Column 3, this page.
"1 1
4
11 .'J - DATE
S' / t * / 'S/j-JS DESCRIPTION
Jr'' ' *
BY CKD)APD
/ISTA Vista Polymers Inc Aberdeen,Mississippi
; Mi_-'w
A/siv :////;
~ PiuJ- V 4l V
V//\' K_
l jT Z/A//T
scale:
A-57m
>1 V\s>\
i!fV
ii >
I A
41
VAB.O&Jl098822
vr*
A
NO
t
CHK. BY APPO
NUTlCf '
I|
ON 6600 JAMASBURY VALVE WITH BETTIS ACTUATOR
VISTA POLYMER
3300 FERN VALLEY ROAO P O BOX 372BO
LOUISVILLE. KENTUCKY. USA. 40033 (5021 960-2366. TWX 610-336-2766
DWG. NO
REV
V402800-1947 B VAB.OOC 10988 >3
TOLERANCES Unltw ottwwtM tptclfltd Anglo* 1*. Frodton* 1/32". .XX .01". .XXX 000 Surteeoo mutt bt Conoontrlc, Ptrtllfl, Plot Squtrt (et Appltcabtt) to Mdt other within____________ T.I.R.
1 11
>
t
pi ^*
NO REVISION
MATERIAL LIST ItemjQty. |
1 2 3 4 5 6 7 8
1 1 1 1 4 4 2 4
DATE BY APPO
A
4
k
MW*
rOLERANCES Unlooo otherwl** pociflod ft Anglos: 1*. Fractions: 1/32", .XX .01", .XXX .005
Surfaces mutt bo Concentric. Parti1st. Flat & Squor#
faa aoDllcabtai to each other within
T.l.R.
#
ACTUATOR MTO. BRKT.
REVISION
DATE
APPD
Item Qt
1 2 34 44 52
6i 4
MATERIAL LIST
A
Description
Dug. No.
9wtch Activator V126411-1943 Mounting Bracket V126411-1944 1/4-20 x 1/2 Hex Hd. Screw
1/4 L.W. 5/8 Shakeproof L W. 5/8 F.W. (1-5/16 O.D.)
DRILL 8 TAP 1/4-20 UNC
GO Switch
FIG.
ACTUATOR
MTA ARK T
FIG. 2
XD
GO Switch
COUPLING
INSTALLATION INSTRUCTIONS
1. Disassemble Actuator and Coupling from Valve and remove existing pointer.
2. Slide 9witch Activator (item 1) onto drive shaft.
3. Drill and Tap Actuator Mtg. Brk't. for 1/4-20UNC screws and attach Mount ing Bracket (item 2) with items 3 & 4.
4. Mount GO Switches in Mounting Bracket (item 2) with two jam nuts supplied with switch and washers items 5 & 6.
5 Adjust Switches in slots on Mounting BRacket (item 2) to sense Switch Activator (item 1) in full open and full closed positions.
Note: 1. GO Switches cure not included in V.I.P. (Valve Indication Package) and should be orde separately.
2. Use Model 713774 GO Switches
DWN. BY RON S.
CHK. BY
DATE 9-28-83
APPO. qNMoWflOnOo4ieltiTotwMmNICwigEKlnmnnIiiimqmaOAmriotiAaofopwoIxMNm#unfupitoaMoolanamoUonfoaMiltrfna*mmCrow. aI*g*<
70 SERIES GO SWITCH V.I.P. ON DURCO 6M 150# G411 Valve
WITH BETTIS ACTUATOR FOR CONOCO
GENERAL EQUIPMENT
& MANUFACTURING CO , INC.
3300 FERN VALLEY ROAD P.O. BOX 37290
LOUISVILLE. KENTUCKY. USA. 40233 SYSTEMS (902) 909-2380, TWX 810-535-2700
DWG. NO.
V126411-1942
vab.ooo:
I
TOLERANCES Unlest othrwiM specified
Angles: 1*. Fractions: 1/32", JCX .01", .XXX .005
Surfaces must be Concentric, Parallel, Flat & Square
4
(as applicable) to each other within
______ T.l.R.
ft
[rJ 1
O/ovO
*
I
\
i<
l
A*
t
t
JAM NUT
GO SWITCH (OPEN)
FIG.
MATCH DRILL FOR THREE 10-24 UNC*28 THREADED HOLES -- ACTUATOR MTG. BRKT.
SWITCH (SH UT)
NO. REVISION
1* F
DATE
'
!
BY APPO.
1A
MATERIAL LIST Item w: Description
Dwa. Mo.
1 1 Switch Activator V40280Q-1948
2 1 Mounting plate
V492800-1949
3 3 #10-24 x 1/2 Rd. Hd. Screw
4 3 #10 Ext. Tooth L. W.
INSTALLATION INSTRUCTIONS
With Valve Actuator removed slide Switch Activator (item 1) onto drive shaft as shown in figure 1.
To Mount Mountinn Bracket (item 2) match drill and tap for three #10-24
screws and attach item 2 to Actuator mountinn bracket with items 4 & 5. Screw GO Switches Into threaded holes on Mounting Bracket (item 2) and secure with jam nuts included with Switches. Adjust Switches to sense triangular bars on Switch Activator when Valve is In full open or full closed positions.
SWITCH
JAM NUT
If
FIG. 2
FIG, 3
OWN. BY RON S
DATE 10-3- 83
70 SERIES GO SWITCH V. I. P.
GENERAL EQUIPMENT
& MANUFACTURING CO., INC.
CHK. BY
3300 FERN VALLEY ROAO
f APPD.
ON KTM 6" VALVE E0800 WITH JAMES8URY ACTUAt&tf
P.0, BOX 37290
LOUISVILLE, KENTUCKY, USA. 40233 SYSTEMS (S02) 969*2386, TWX 810-535*2786
I NOtlCt. Orawtng ccatalM CpMMtetnl 4 proprietary materiel
eno i> lurneiM upon conplipi that ll will not be uead In any OeOtmenlel lo the intereel m Oeneraf IpHpwint 4 Mtp. Co . Inc
FOR CONOCO
DWG. NO
V402800-I947
REV
VAB.00 31098: >26
14
11
10LERANCES Uoioii ollwwtM jpcciheo
Angles: 1\ Fractions: 1/3r. XX 01".
XXX
M
005
Surfaces must be Concentric. Parallel. Flat & Square
(aa applicable) lo each other within
______T I.R
ACTUATOR MOUNTING BRACKET
NO
n
REVISION
*
OATE BY APPO.
i
Item Qty.
1
21
31
44 54
62
72
MATERIAL LIST
Description
CXvg. No.
Switch Activator V907310-1955
Mounting Bracket V907310-1954
Set Screw #12-24 x 1/4
1/4-2C x 1/2 Hex Hd. Screw
1
1/4- L.W.
5/8 Ext. Ttoth L.W
1
5/8 F.W.
GOv SWITCH
ACTUATOR MTG. BRK7.
JAM NUT
FIG. I
GO SWITCH
DRILL 8 TAP 1/4-20 UNC
f
J=
. k" : j
: 1
3.
---- H
FIG. 2
'
1
INSTALLATION INSTRUCTIONS
1. Remove Actuator, Coupling and Existing position indication plate.
n
2. Slide Switch Activator (item 1) onto drive shaft and secure with set screw (item 3).
3. Place Mounting Bracket (item 2)onto Actuator Mtg. Brk1t. and mark position of two holes. Drill and tap for 1/4-20 UNC holes. Secure Mounting Bracket (it (item 2) with items 4 & 5.
4. Screw GO Switches into Mounting Brk't. (item 2) till Gap between end of switch & Switch Activator (item 1) is approx. 1/16". Secure with Jam Nuts that are included with Switches and with washers (items 6 & 7).
5. Switches should sense Switch Activator when Valve is in full open and full
NOTE: GO Switches are not included in V.I.P. (Valve Indication Package) and should be ordered as a Separate item.
L*
OWN. BY RON S.
CHK. BY
NOfiCI 0*t
A
SERIES GO SWITCH V.I ON
310 BALL VALVE FOR
CONOCO
GENERAL EQUIPMENT
& MANUFACTURING CO . INC
3300 FtAN VALIEV ROAD P O BOX 3/290
LOUISVILLE. KENTUCKY. USA. 40233 SYSTEMS (902) 999-23M. TWX 910-939-2799
*
TOLERANCES Unlos* otherwise specified Angles: t 1`, Fractions: 1/32", .XX .0V\ .XXX .005 Surfaces must b# Concentric, Parallel, Flat & Square fas applicable) to each other within______ ______ T.l.R.
ACTUATOR MOUNTING 1 *1 BRACKET
tf
Item
REVISION
DATE
APPD
MATERIAL LIST
Description
Dwg. No,
Svitch Activator V907310-1951 Mounting Bracket V907310-1952 Set Screw #12-24 x 1/4 1/4-2Q x 1/2 Hex Hd. Screw
1/4- L.W. 5/8 Ext. Tboth L 5/8 F.W.
m t-
*4
GO SWITCH
JAM NUT
FIG.
ACTUATOR MTG. BRKT.
*4
FIG. 2
RILLS TAP
t 1/4-20 UNC
(4) HOLES
GO SWITCH
INSTALLATION INSTRUCTIONS
Remove Actuator, Coupling and Existing position indication plate.
Slide Switch Activator )item 1) onto drive shaft and secure with set screw (item 3).
3. Assemble GO Switches to Mounting Bracket (item 2) with Jam Nuts supplied with switches and washers items 6 & 7.
4. Place Switch mounted on bracket on sides of Actuator mounting bracket and align . switch with Activator (item 1) then natch drill Actuator mounting bracket with holes in Mounting Bracket (item 2). Secure with items 4 & 5.
5. Switches should sense Switch Activator when Valve is in full open and full closed positions.
NOTE: GO Switches are not included in V.I.P. (Valve Indication Package) and should be ordered as a Separate item.
DWN. BY
RON S. CHK. BY
APPD
iNOTICE: DftiujMtQgphtiftcy
dimvtriMHfifftttel to Ml*
*7
Gnwii Equip mint E k% C*, in*.
70 SERIES GO SWITCH V.I.P
ON W-K-M 310 BALL VALVE 14."
FOR CONOCO
GENERAL EQUIPMENT
& MANUFACTURING CO., INC.
3300 FERN VALLEY ROAD
P.O. BOX 37200
LOUISVILLE. KENTUCKY, USA, 40233 SYSTEMS (902) 069-2306. TWX 610-535-2786
DWG. NO.
REV
V 907310-1950 VAB.00010988 8