Document 5DX9ERpdgmNb9rGGjB6aRqgEz

i LIMIT SWITCH REPLACEMENT - PHASE III Aberdeen Chemical Plant July 22, 1986 Frank G. Jeanson PROCESS ENGINEER REVIEWED BY: J. G. Cole SR. PROCESS ENGINEER APPROVED BY: Veldon E. Messick CHIEF PROCESS ENGINEER VAB.0001098809 LIMIT SWITCH REPLACEMENT PHASE III Aberdeen Chemical Plant TABLE OF CONTENTS I. PURPOSE AND PROCESS DESCRIPTION II. VALVE LOCATION III. IV. INSTRUMENT SPECIFICATIONS DRAWINGS * VAB.0001098810 LIMIT SWITCH REPLACEMENT PHASE III Aberdeen Chemical Plant Purpose and Process Description Lack of positive valve position indication in the control room has the potential to cause safety, operational and environ mental problems. The existing limit switches indicate actuator position and not the actual valve stem position. If the coupling fails or is spread, the valve could be open or partially open and still give a closed signal. This design will provide each of the designated valves in section A of the following table with a new limit switch that indicates valve stem position. These new limit switches will provide accurate indication of valve position to the control room or the Modicon. The limit switches will be mounted the bracket between the valve and the actuator, Drawings several different type valves with the new limit switches attached. Limit switches will be replaced on 80 valves. on of VAB.0001098811 ( II. Valve Location A. Valves that would cause quality, safety or environmental problems without proper indication General Location Valve # 1. Reactors 741, 742 1-6 743, 744, 745 & 700 Valve Description Rinse Supply 7-12 Chem Wash (CW) Supply 13-18 Clean Reactor 19-24 Clean Condenser 25-30 Steam stripping 31-36 Emergency AMS Injection * Two valves would have to leak valve failure would cause VCM .2 Reactors 300, 400 500 and 600 37-40 Chem wash to Reactor 41-44 Chem wash to Condenser 45-48 Rinse to Reactor 49-52 Rinse to Condenser 53-56 57-60 Steam Stripping Emergency AMS Injection Reason *2--valve leak, VCM enter rinse. Rinse supply valve leak, water dilute chem wash. VCM Chem wash supply valve leak, CW in rinse 2-valve leak, VCM enter rinse or CW. 2-valve leak, rinse or CW in reactor. 2-valve leak, VCM enter rinse or CW 2-valve leak, rinse or CW in reactor 1-valve leak, steam in reactor or VCM in steam. AMS Such as rinse supply and reactor cleaning 2-valve leak. VCM in chem was or chem wash in reactor 2-valve leak. VCM in chem wash or chem wash in reactor 2-valve leak. VCM in rinse or rinse in reactor 2-valve leak. VCM in rinse or rinse in reactor 1-valve leak. steam in reactor or VCM in steam 1-valve leak. AMS in reactor VAB.0001098812 General Location Valve No. 3. Batch Water Strip- 61-64 pers (North & South) 65-66 Valve Description To Sewer, To Centrate Fill Line 67-68 VCM Bleed 69-70 Recovery 71-74 To ERS 75 VCM Double Block and Bleed venting to FVSfs. 4. Chem Wash Tank 76-77 78 79 Steam Pressurization To Reactors (New Module) To Reactor (Old Module) 5. Blowdown Tank 80 To Batch Water Strippers Reason 1-valve leak, VCM contaminated water to sewer. 2-valve leak, contaminate vessel In stripping mode 2-valve leak, contaminate vessel In stripping mode. 2-valve leak, contaminate vessel in stripping mode. 2-valve leak, contaminate vessel in stripping mode. Three way valve-if not in correct posi tion, contaminate vessel in stripping mode. 1-valve leak, contaminate vessel in stripping mode. 1-valve leak, safety hazzard when a reactor is blanked out. 1-valve leak, safety hazzard when a reactor is blanked out. 1-valve failure, lead to tank over pressuring and discharging to sewer. * B. Remaining valves that are Indicated on the panel or that are tied into the Modicon that will not have limit switches replaced. General Location 1. New Module Valve No. Valve Description a. Chem Wash Tank 1 2 3 4 Tank Outlet Tank Bypass Tank Inlet Recirculation b. Blowdown Tank 5 Recirculation 6 To Emission Recovery System 7 To Recovery System 8 To Recovery System c* Reactors 741-745 d. Recovery System 9-13 14-18 * 19 20 21 22 23 24 25 26 27 28 Inert Vent Steam to Jacket Compressor suction manifold Compressor suction manifold Suction north compressor Suction middle compressor Suction south compressor Pressure equalization valve Suction north vacuum pump Suction south vacuum pump Discharge north vacuum pump Discharge south vacuum pump * These valves have indication for the open position only. e. Evacuation 29 EE-200 first stage steam 30 Evacuation valve to EE-200 General Location f. Colloid charge g. Hot water charge h. Rinse water 1, RVCM charge Old Module a. Chem Wash b. Batch water strippers c. Reactors d. Recovery system Valve No, 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 1 2 3 4 5-6 7-11 12-16 7 8 19 20 Valve Description PVA pump discharge PVA makeup tank outlet PVA charge tank inlet Methocel pump discharge Methocel makeup tank outlet Methocel charge tank inlet Pump suction Primary pump discharge Secondary pump discharge Hot water tank make-up Rinse water supply Rinse pump bypass To top of reactors Cold water swirl Pump discharge Tank outlet Tank inlet Tank bypass Chem wash from EA-357 to FA-776 Steam stripping Inert vent Steam to jacket Suction east compressor Suction west compressor To ERS From batch water strippers General Location e. Emission Recovery System f. Evacuation g. Colloid Charge h. Hot water charge 1, Rinse water j. RVCM charge Valve No 21 22 23 24 25 26 27 28 29 30 31 32 33 Valve Description VCM Tank farm recovery Batch water stripper recovery EE-100 first stage steam Evacuation valve to EE-100 Pump discharge Primary pump discharge Secondary pump discharge Pump suction Hot water tank make-up Hot water rinse Rinse supply Rinse pump bypass Pump discharge VAB.0001098816 Limit Switch Replacement - Phase III Aberdeen Chemical Plant III. Instrument Specification Item PLS-101 through 180 Description Proximity Limit Switches ,,pi A r VAB.0001098817 PLANT ITEM NO. SERVICE VtSt\ C'k.fifVX i 4 VISTA CHfMICAl COMPANY PtCATKMSMUT specification data shut PROJECT NO A.F.E. NO. P.O. NO. PROJECT V-- i A\ iA>\, u`t /W1 'X Rtlnn i nmi <s * "1 -it- # * 0 UMUl III 11W U iUUt 11 in Wi UJIUHI lui, *t /U' t ->V '--I V /a. < 4 r *< . r:& $$3.* A!{jT .afci t '-rf &Wy ei*< - *f V j ^ r/- * ' J - -* *, r V,,r;iv i'* *-'**:... y ^ VO'i'*;-"'. 1 * . f , V* SS *+ 1 . 1 >*v *V* v-'- >1 ^-1Pm \!g$j2 s*& ^ V t, .- '% -^w^v . -f * '*' -1 > ' II *> v-w *i >* t* \ ,u* ** r i 11 i * m fV-: IW. siJtfocasMKj.v,*,[/5*FSJ*w i h ' -< * * ^nV7JOVv'S,jrf */: .^r v < * , "vr-;1-; .tw-r ^>v>v-a,!v' / T s '*- 'jy vf" 'Vr ( Vtu. .^ ^ 'i ^ ^ 1 U 't r * t *V 'twj* lh wJr^ h 4]T ** - rA#' / * >/ * * .VM* ^V,r `f -. * t * . . . .:. 'v.m'i'.W' "- iiMi! */ GS=i V~ Am 4 Ip g$& Ui \*9 'JH t-ui*<'fJ1 >nJ (/</>"*** ^ Mt* < / 'A *1 ^ .% v t/t. * I.i *1^ rh -s * K *. < ri ^j4- ^ ''V-iA J' 1>* r * |i> v 1 k " ' 'i^*v^4-+7}?'X .fO'Zfr f - i jt'- -1 f;` I 'A ;* , ^ I .Tit'/, **V * r-4.- j' . v~ v rvl*rw,ft{?;v;. .* : : tS&&'!;v'''* '' n j.^: s r * - * I*** *,,,* - * < j> - rV*;*h>.; * -w ft t VAB.0001098819 iH. - t u:i i I End Cap: .050" Stainless Steel (304) End Cap. available with thicker End Caps for higher pressure. Pressure Options: Normally the standard 5/8" diameter will withstand 2000 PSI. Larger cases with thicker walls and front End Caps will allow the switch to function at much higher pressures (up to 10,000 PSI). Certification available as factory option. Case: 300 Series Stainless Steel case, plain or threaded body (5/8-18 NF). Different body lengths available, SEE options on MODELS AVAILABLE. Magnets: Made with a high energy product magnet. An excellent coercive force which converts into grams of Contact Pressure for reliable operation. Meets MM PA Specifications. External Threads: Machines to meet SAE 5/8-18 UNF Specifications. Units available with or without threads. Contacts: Type Silver, Cadmium Oxide, resists welding and is some of the most widely used Contact Material in the industry. Sized to withstand approved ratings. Hermetically Sealed Contact Chamber. Bearing: Consists of a finely ground Stainless Steel Pin and durable plastic housing. Sized to withstand a wide temperature range. Resists seizing and gives millions of free operations. Potting: Terminal cavity filled with epoxy resin com pound for sealing and mechanical support of wire/ cable connections. 4 Body Tube: Made of Free Mechanical Stainless Steel. Resists most all harsh environments and withstands high working pressures. Impervious to water, oils and gases. Internal Threads:1/2-14 NPT. complies with CSA requirements for Explosion Proof Applications. Wire or cable leads available to meet Customer's Specifications. i VAB.0001098820 When time, accuracy, and dependability count... you can count on the 70 Series GO* Switch Maintenance tree; engineered for precision, performance and reliability. The standard 70 Series GO* Proximity Limit Switch has been designed and built to rugged specifications for use in most industrial and environmental applica tions. Each switch is totally enclosed, hermetically sealed and capable of operating in hostile environments. The standard stainless steel housing is impervious to oils, caustic acids, water laden areas and most Standard Models atmospheric conditions, with a broad operating temperature range. (See specification) Many different models of the switch are available for your design needs. (See ordering information for specifications, detail and options.) Hazardous Location approved models for Class I, Division 1, Ail Groups Model 713360 No conduit connection. 18" 3 conductor cable with water resistant squeeze connection, tyoe 300 stainless steel housing with K-18 NF x 1.5" threads with 2 lock nuts. Model 713570 V% NPT conduit outlet. 181* 3 conductor cable, type 300 stainless steel housing with K-18 NF x 2.813" threads with 2 lock nuts. Model 713524 Va NPT conduit outlet with 18" potted, 3 conductor cable, type 300 stainless steel housing, no threads. Model 713420 No conduit outlet. 18" potled. 3 conductor cable, type 300 stainless steel housing; no threads. m0 j^ Model 713460 No conduit outlet. 10" potted, 3 conductor cable, type 300 stainless steel housing with K-18 NF x 1.5" threads with 2 lock nuts. Model 713660 No conduit outlet, 18" potted. 3 wire leads, type 300 stainless steel housing with K*18 NF x 1.5" threads with 2 lock nuts. Model 713720 Va NPT conduit outlet with 18" potted, 3 wire leads, type 300 stainless steel housing, no threads. Model 713564 Va NPT conduit outlet with 18" potted. 3 conductor cable, type 300 stainless steel housing with K-18 NF x 1.5" threads with 2 lock nuls. Model 713574 Va NPT conduit outlet with 18" potled, 3 conductor cable, type 300 stainless steel housing with K-18 NF x 2.813" threads with 2 lock nuts. rtodel 713520 4 NPT conduit outlet. 18!' 3 conductor cable, ype 300 stainless steel housing, no threads. Model 713760 Va NPT conduit outlet with 18" potled, 3 wire leads, type 300 stainless steel housing with K-18 NF x 1.5" threads with 2 lock nuls. Model 713724 Va NPT conduit outlet with 18" potted. 3 wire leads, type 300 stainless steel housing, no threads. odel 713560 NPT conduit outlet with 18!' 3 conductor able, type 300 stainless steel housing with -18 NF x 1.5" threads with 2 lock nuts. Model 713770 Va NPT conduit outlet, 18" potted 3 wire leads, type 300 stainless steel housing with K-18 NF x 2.813" threads with 2 lock nuts. Model 713764 Va NPT conduit oullet with 18" potted. 3 wire leads, type 300 stainless steel housing with K-18 NF x 1.5" threads with 2 lock nuls. *1> I**Jr V i r *t Approved switches are in compliance with current bulletins 1243. 1273 and 1308 Model 713774 Va NPT conduit outlet with 18" polled. 3 wire leads, type 300 stainless steel housing with " 18 NF x 2 BIS*1 threads jeso switches are U/L and CSA approved for Industrial control, general purpose use. See hazardous locatioiy^*000^0988^ tproved models in Column 3, this page. "1 1 4 11 .'J - DATE S' / t * / 'S/j-JS DESCRIPTION Jr'' ' * BY CKD)APD /ISTA Vista Polymers Inc Aberdeen,Mississippi ; Mi_-'w A/siv :////; ~ PiuJ- V 4l V V//\' K_ l jT Z/A//T scale: A-57m >1 V\s>\ i!fV ii > I A 41 VAB.O&Jl098822 vr* A NO t CHK. BY APPO NUTlCf ' I| ON 6600 JAMASBURY VALVE WITH BETTIS ACTUATOR VISTA POLYMER 3300 FERN VALLEY ROAO P O BOX 372BO LOUISVILLE. KENTUCKY. USA. 40033 (5021 960-2366. TWX 610-336-2766 DWG. NO REV V402800-1947 B VAB.OOC 10988 >3 TOLERANCES Unltw ottwwtM tptclfltd Anglo* 1*. Frodton* 1/32". .XX .01". .XXX 000 Surteeoo mutt bt Conoontrlc, Ptrtllfl, Plot Squtrt (et Appltcabtt) to Mdt other within____________ T.I.R. 1 11 > t pi ^* NO REVISION MATERIAL LIST ItemjQty. | 1 2 3 4 5 6 7 8 1 1 1 1 4 4 2 4 DATE BY APPO A 4 k MW* rOLERANCES Unlooo otherwl** pociflod ft Anglos: 1*. Fractions: 1/32", .XX .01", .XXX .005 Surfaces mutt bo Concentric. Parti1st. Flat & Squor# faa aoDllcabtai to each other within T.l.R. # ACTUATOR MTO. BRKT. REVISION DATE APPD Item Qt 1 2 34 44 52 6i 4 MATERIAL LIST A Description Dug. No. 9wtch Activator V126411-1943 Mounting Bracket V126411-1944 1/4-20 x 1/2 Hex Hd. Screw 1/4 L.W. 5/8 Shakeproof L W. 5/8 F.W. (1-5/16 O.D.) DRILL 8 TAP 1/4-20 UNC GO Switch FIG. ACTUATOR MTA ARK T FIG. 2 XD GO Switch COUPLING INSTALLATION INSTRUCTIONS 1. Disassemble Actuator and Coupling from Valve and remove existing pointer. 2. Slide 9witch Activator (item 1) onto drive shaft. 3. Drill and Tap Actuator Mtg. Brk't. for 1/4-20UNC screws and attach Mount ing Bracket (item 2) with items 3 & 4. 4. Mount GO Switches in Mounting Bracket (item 2) with two jam nuts supplied with switch and washers items 5 & 6. 5 Adjust Switches in slots on Mounting BRacket (item 2) to sense Switch Activator (item 1) in full open and full closed positions. Note: 1. GO Switches cure not included in V.I.P. (Valve Indication Package) and should be orde separately. 2. Use Model 713774 GO Switches DWN. BY RON S. CHK. BY DATE 9-28-83 APPO. qNMoWflOnOo4ieltiTotwMmNICwigEKlnmnnIiiimqmaOAmriotiAaofopwoIxMNm#unfupitoaMoolanamoUonfoaMiltrfna*mmCrow. aI*g*< 70 SERIES GO SWITCH V.I.P. ON DURCO 6M 150# G411 Valve WITH BETTIS ACTUATOR FOR CONOCO GENERAL EQUIPMENT & MANUFACTURING CO , INC. 3300 FERN VALLEY ROAD P.O. BOX 37290 LOUISVILLE. KENTUCKY. USA. 40233 SYSTEMS (902) 909-2380, TWX 810-535-2700 DWG. NO. V126411-1942 vab.ooo: I TOLERANCES Unlest othrwiM specified Angles: 1*. Fractions: 1/32", JCX .01", .XXX .005 Surfaces must be Concentric, Parallel, Flat & Square 4 (as applicable) to each other within ______ T.l.R. ft [rJ 1 O/ovO * I \ i< l A* t t JAM NUT GO SWITCH (OPEN) FIG. MATCH DRILL FOR THREE 10-24 UNC*28 THREADED HOLES -- ACTUATOR MTG. BRKT. SWITCH (SH UT) NO. REVISION 1* F DATE ' ! BY APPO. 1A MATERIAL LIST Item w: Description Dwa. Mo. 1 1 Switch Activator V40280Q-1948 2 1 Mounting plate V492800-1949 3 3 #10-24 x 1/2 Rd. Hd. Screw 4 3 #10 Ext. Tooth L. W. INSTALLATION INSTRUCTIONS With Valve Actuator removed slide Switch Activator (item 1) onto drive shaft as shown in figure 1. To Mount Mountinn Bracket (item 2) match drill and tap for three #10-24 screws and attach item 2 to Actuator mountinn bracket with items 4 & 5. Screw GO Switches Into threaded holes on Mounting Bracket (item 2) and secure with jam nuts included with Switches. Adjust Switches to sense triangular bars on Switch Activator when Valve is In full open or full closed positions. SWITCH JAM NUT If FIG. 2 FIG, 3 OWN. BY RON S DATE 10-3- 83 70 SERIES GO SWITCH V. I. P. GENERAL EQUIPMENT & MANUFACTURING CO., INC. CHK. BY 3300 FERN VALLEY ROAO f APPD. ON KTM 6" VALVE E0800 WITH JAMES8URY ACTUAt&tf P.0, BOX 37290 LOUISVILLE, KENTUCKY, USA. 40233 SYSTEMS (S02) 969*2386, TWX 810-535*2786 I NOtlCt. Orawtng ccatalM CpMMtetnl 4 proprietary materiel eno i> lurneiM upon conplipi that ll will not be uead In any OeOtmenlel lo the intereel m Oeneraf IpHpwint 4 Mtp. Co . Inc FOR CONOCO DWG. NO V402800-I947 REV VAB.00 31098: >26 14 11 10LERANCES Uoioii ollwwtM jpcciheo Angles: 1\ Fractions: 1/3r. XX 01". XXX M 005 Surfaces must be Concentric. Parallel. Flat & Square (aa applicable) lo each other within ______T I.R ACTUATOR MOUNTING BRACKET NO n REVISION * OATE BY APPO. i Item Qty. 1 21 31 44 54 62 72 MATERIAL LIST Description CXvg. No. Switch Activator V907310-1955 Mounting Bracket V907310-1954 Set Screw #12-24 x 1/4 1/4-2C x 1/2 Hex Hd. Screw 1 1/4- L.W. 5/8 Ext. Ttoth L.W 1 5/8 F.W. GOv SWITCH ACTUATOR MTG. BRK7. JAM NUT FIG. I GO SWITCH DRILL 8 TAP 1/4-20 UNC f J= . k" : j : 1 3. ---- H FIG. 2 ' 1 INSTALLATION INSTRUCTIONS 1. Remove Actuator, Coupling and Existing position indication plate. n 2. Slide Switch Activator (item 1) onto drive shaft and secure with set screw (item 3). 3. Place Mounting Bracket (item 2)onto Actuator Mtg. Brk1t. and mark position of two holes. Drill and tap for 1/4-20 UNC holes. Secure Mounting Bracket (it (item 2) with items 4 & 5. 4. Screw GO Switches into Mounting Brk't. (item 2) till Gap between end of switch & Switch Activator (item 1) is approx. 1/16". Secure with Jam Nuts that are included with Switches and with washers (items 6 & 7). 5. Switches should sense Switch Activator when Valve is in full open and full NOTE: GO Switches are not included in V.I.P. (Valve Indication Package) and should be ordered as a Separate item. L* OWN. BY RON S. CHK. BY NOfiCI 0*t A SERIES GO SWITCH V.I ON 310 BALL VALVE FOR CONOCO GENERAL EQUIPMENT & MANUFACTURING CO . INC 3300 FtAN VALIEV ROAD P O BOX 3/290 LOUISVILLE. KENTUCKY. USA. 40233 SYSTEMS (902) 999-23M. TWX 910-939-2799 * TOLERANCES Unlos* otherwise specified Angles: t 1`, Fractions: 1/32", .XX .0V\ .XXX .005 Surfaces must b# Concentric, Parallel, Flat & Square fas applicable) to each other within______ ______ T.l.R. ACTUATOR MOUNTING 1 *1 BRACKET tf Item REVISION DATE APPD MATERIAL LIST Description Dwg. No, Svitch Activator V907310-1951 Mounting Bracket V907310-1952 Set Screw #12-24 x 1/4 1/4-2Q x 1/2 Hex Hd. Screw 1/4- L.W. 5/8 Ext. Tboth L 5/8 F.W. m t- *4 GO SWITCH JAM NUT FIG. ACTUATOR MTG. BRKT. *4 FIG. 2 RILLS TAP t 1/4-20 UNC (4) HOLES GO SWITCH INSTALLATION INSTRUCTIONS Remove Actuator, Coupling and Existing position indication plate. Slide Switch Activator )item 1) onto drive shaft and secure with set screw (item 3). 3. Assemble GO Switches to Mounting Bracket (item 2) with Jam Nuts supplied with switches and washers items 6 & 7. 4. Place Switch mounted on bracket on sides of Actuator mounting bracket and align . switch with Activator (item 1) then natch drill Actuator mounting bracket with holes in Mounting Bracket (item 2). Secure with items 4 & 5. 5. Switches should sense Switch Activator when Valve is in full open and full closed positions. NOTE: GO Switches are not included in V.I.P. (Valve Indication Package) and should be ordered as a Separate item. DWN. BY RON S. CHK. BY APPD iNOTICE: DftiujMtQgphtiftcy dimvtriMHfifftttel to Ml* *7 Gnwii Equip mint E k% C*, in*. 70 SERIES GO SWITCH V.I.P ON W-K-M 310 BALL VALVE 14." FOR CONOCO GENERAL EQUIPMENT & MANUFACTURING CO., INC. 3300 FERN VALLEY ROAD P.O. BOX 37200 LOUISVILLE. KENTUCKY, USA, 40233 SYSTEMS (902) 069-2306. TWX 610-535-2786 DWG. NO. REV V 907310-1950 VAB.00010988 8