Document 5D2R86M7gDdRQy1Bbdx3d68QV
SECTION 6
FINISH APPLICATION
PAGE 1
HI-TEMP
EQUIPMENT'S DUCTWORK
TEMPERATURE RANGE: 351F to 800F
NOTE: No finishes (mastics, laminates or fabrics) shall be applied until the equipment or ductwork has been heated to the operating temperature.
2 INDOOR FINISH
2.1 Indoor equipment and ductwork operating within this temperature range shall be finished the same as indoor equipment and ductwork having an operating temperature
from + 71PF to 350F (see section 5 - para. 1.1 through 1.9) except as follows:
Prior to the application of the canvas and P.V.A. coating, Polybeistos cloth shall be cemented on the surfaces of the insulation adjacent to uninsulated protrusions such as nozzles, probes, T.C.s, supports, etc., and components of the equipment or ductwork that require portable insulation covers. Fibrous adhesive shall be used as the adhesive for the polybestos cloth. The polybeatos cloth shall extend back from the portable covers at least 6" and around
the uninsulated protrusion a minimum of 4". It shall be fitted snug to the uninsulated surface or lap upon
them about 3/5".
The canvas shall over lap, about 1^", the polybestos cloth around the protrusion etc., but both coats of the P.V.A. insulation coating shall be applied on all polybestos cloth surfaces.
*2A PORTABLE COVERS
2A.1 Portable covers for this temperature range shall be finished the same as those for the + 71F to 350F temperature range (see section 5 - para. 1A.1 thru 1A.3).
FIGURE 1 illustrates the preceeding instructions for INDOOR finish on equipment and ductwork having an operating temp
erature from 351F to 800F.