TI1E ROLE OF polychlorinated biphenyls IN El. ECTHICAL EQUIPMENT__________
SIR FIARY
Polychlorinated biphenyls (PCB's) have been used in many applications for .
over forty years, but only recently was evidence discovered that these materials'
are widely dispersed in the environment. Systematic investigations of the
.
toxic and biological effects of PCB's have been undertaken v;ithin the past few
years to establish the effects of specific formulations upon specific species. *
Simultaneously, significant steps-have been taken by U. S. industry to further
limit PC3 releases to the environment.
PCB's have been used in three broad types of applications for the past
*40 years, as follows: (a) "open ended" applications.... for example, in paints,
specialty inks, paper coatings, plastics, etc., (b) "nominally closed" appli-
cations.... for example, as the working fluid in hydraulic or heat transfer
systems; and (c) "closed system" applications....specifically, as the insulating
fluid in certain types of transformers and capacitors.
.
'
The Monsanto Company is the sole U. S. producer of PCB's. It has discontinued
supplying the material for all applications of type (a) and (b). Certain spoRcs-
men have recommended discontinuance of- type (c) applications as well, but appear
to have done so without consideration of the alternatives and risk/benefits
involved. The purpose of this report is to provide information for such consi
deration.
.
Benefits
1. Askarel*-insulated transformers do not burn or explode under conditions
of electrical arcing that can cause fires or incendiary explosions in oil-insulated
transformers. Therefore, they are used in or near public, commercial or industrial
buildings where oil-insulated transformers would.present a potential danger to
life and property.
.'
2. Askarel-fillcd power and industrial capacitors are significantly smaller, more reliable, more durable, and safer than oil-filled capacitors. As a result, askarels have supplanted mineral oils in more than 907. of the power and industrial capacitors made today. Over the past few decades most of the equipment that incorporates such capacitors has been configured to take particular advantage of the size, safety and reliability benefits of askarcl capacitors (e.g., many types are today less than 147. of the size of equivalent oil capacitors and have a life expectance of 10 to more than 20 years).
The vital role that askarel-insulatcd transformers and capacitors have
played in the safe, reliable, and efficient delivery of electric power is
reflected- in various standards, codes, and regulations that now effectively require
or encourage continued use.
_
osw182779
*PCB's used in transformers and capacitors are designated by the international
term "askarcl."
.p
O
STLCOPCB4050883
'r 2
Ri sks
In the United States, nodical records show that over a nearly 40-year
period the only adverse health effects experienced by U. S. workers exposed to
PCB's, cither during the manufacture of these liquids or of electrical equipment
containing these liquids, have been limited to occasional cases of non-chronic '
chloracna or ocher temporary skin lesions or irritations#
i
Askarel-filled transformers and capacitors are delivered to customers as !
sealed units from which there is no escape of askarel under normal operation. #
While certain types of equipment failures can rupture the case and permit loss of
some asknrel to the environment, such failures arc limited to approximately 0.02/.
of the units in service per year. In addition, PCB's can get into the environment
during the manufacture, delivery, improper use, maintenance, repair and disposal
of transformers and capacitors. Specific control measures have already been
'instituted by individual manufacturers and will be supplemented and strengthened
by national standards and procedures which are now being developed by a Committee
of the American National Standards Institute. These forthcoming standards will be
designed to prevent the inadverrent loss of PCB's to the environment at all stages
from equipment manufacture through ultimate disposal,
After implementation of the control measures contemplated, it is estimated that the annual release of PCB's to the environment will be less than one onethousandth of the present burden, mainly from failed, small capacitors. Further more, since in- 1971 the industry standardized on a capacitor formulation containing less than 0.47. pcntachlorinated biphenyls and higher, the fractions of main concern, the ecological significance will be further reduced.
Alternatives
1. Askarel transformers already installed cannot be replaced by oil trans
formers of equivalent rating without major construction changes in buildings and
associated equipment required to compensate for the safety features of the askarel
-units. Fcr certain applications and locations, dry-type transformers can replace
askarel transformers, but not without reduction in system reliability.
.
-
' 2. The principal alternative to askarels for capacitors is mineral oil, but
such replacement would return capacitor technology to its prc-1932 level and would
necessitate redesign and replacement of such widely used equipment as fluorescent
light fixtures and racks for power and induction heating capacitors, which could
not now accommodate the increased size of oil capacitors while maintaining their
present ratings.
.
3. The cost of askarel'liquids is about $2.00 per gallon, compared to about
$0.30 per gallon for mineral oil. Thus, long before there were any environmental
concerns about PCB's, there was a strong economic incentive to find other less
expensive insulating liquids with the desirable characteristics of askarels. Since
the 1930's, at least 10 major chemical or electrical companies have invested large
amounts of time and money in this earch, all with r.o .'access. Vhilc potential sub
stitutes that arc more costly than PCB's have'also received some consideration
(c.g., fluorinated liquids) little is known* about either their electrical performance
or possible ill effects upon the environment. There are today no fluids that can
be used as onc-for-one replacements for PC3's.
qSW 182780
1/31/72
.
STLCOPCB4050884
Dial Comm Dept.
Address Subject
8*234-2275
Date January 11, 1972
Dielectric Systems Laboratory, ISLO
Pittsfield, Massachusetts
WESTINGHOUSE REPORT ON "THE NEED FOR CONTINUED USE OF POLYCHLORINATED BIPHENYLS AS ELECTRICAL INSULATING LIQUIDS" TO NIPCC.
Messrs. J. T. Batty V P. G. Benignus
L. L. Dengler
J. C. Dutton R. W. Frahm W. B. Gaither D. F. Haywood
E. C. Hoffman
T. H. Lee
C. J. Msloun T. L. Mayes F. G. McKerr L. A. Morgan R. C. Osthoff
Gentlemen:
As indicated in my letter of January 10, 1972, I am enclosing a
copy of the Westinghouse report for your information. This was pre
sented at the January 3 1972 meeting of the NIPCC (National Industrial
Pollution Control Council) but was not sent to the Office of Science
and Technology.
'
Very truly yours,
x--
E. L. Raab, Manager Dielectric Systems Laboratory Building 11 - 315
Att.
.
ml
DSW 182781 STLCOPCB4050885
THE NEED i'Cr-i CONTINUED IV? OF WLYCHWKiNATEU : BIHIEWYI.S A3 KLSCTKICAi. JKSUIATIKG LIQUIDS
issao).',u~t x>
\
Why fire* FolychlorinaAefl I'i phr rsyls (PCBs) needed?
The principle use of PCB fluid in the electrical industry is in trans
formers and capacitors (both large ana smll) as an insulator and
coolant. At the protent tine there is only one domestic manufacturer of
this fluid - Monsanto Chemical Company, calling its product Aroclor.
Westinghouse uses the tradename Inerteen and General Electric uses the
name I^ranol. Throughout the transformer and capacitor industries it
is generically known as an Askarel fluid. V/hatever the name, this family
of insulants is characterized by stability -
high flash points and
even higher combustion temperatures essential to safe operation.
PCB's, Aroclors, are essential as dielectric fluids for capacitors and
transformers.
They have been used for.about forty years. They .
possess a unique combination of physical and chemical properties which
allow these devices to operate at high voltages and high power levels, for
long periods of time, under extremely varying conditions, and with
reliability and safety.
.
A brief description of the Aroclors is warranted to explain their usefulness as an electrical insulator. An Aroclor consists of a mixture of variously chlorinated biphenyls, according tc. the formula:
.x + y 1, 2, 3, fc, 5, or 6 (some 7, 8, % 10)
with isomers of each chlorination level. All the bonds in these mole
cules ore covalent. They are particularly strong, being aromatic
carbon-carbon, carbon-hydrogen, and carbon-chlorine bonds. Table 1
lists some of the compositions of liquid chlorinated biphenyls.
.
i
DSW 182782 STLCOPCB4050886
. Table 1 . Composition of Different Liquid Chlorinated Biphenyls
ComDonents
,
- given as $ -
1221
Monsanto Aroclors 1232 MCS 1043 1242 MCS 1016 1248
i i254
1260
Chlorine
21 32
Biphenyl
* / 14.8
Mono-chlorobiphenyl
56.5
Di-chlorobiphenyl
26.9 ^55
Tri-chlorobiphenyl
1.42'
Tetra-chlorcbipheny1
.06
Per.ta-chlorobiphenyl
Hexa-chlorobiphenyl
32
42 , 42'
48
.04 .02 . .02
22.2
.72 .93
74.4 3.3
` 15.6 , 19.4
?
54.5 64.5
22.5 15.0
/s/55
6.7*
.16*
54 .60
.
.
60 '
70
^Includes higher than penta-chlorinatcd isomers.
DSW 182783
v
I
Because of their bond covaleney ancl strengths, Aroclors have ahigh
degree of thermal stability and chemical inertness, and they do not undergo
ionic dissociation, T.iese properties give to Aroclors, with respect to
their use in electrica] power devices:
'
(1) high voltage capability
'
.
.
.
(2) good insulating quality (very low electrical conductivity)
(3) high thermal stability, and
(4) compatibility with various solid dielectric and metallic components
of capacitors and transformers .
'
The chlorine atoms of Aroclors arc specifically beneficial in three
ways, because they give:
(5) a relatively high dielectric constant, e* = 4.0-5.8 which is
particularly useful for capacitors. .1
..
(6) good corona properties (since .most of the products of corona dis
charge are chlorinated and are readily absorbed by the dielectric,
or reacted with relatively little inert gas that remains as bubbles
and sustains corona - so they may be subjected to sporadic over
voltages.
(won't sunoort conbustion by itself)
(7) the property non-flamraabUrty^ waxen occurs at 42^ cnionnation and
above (Aroclor 1242 or KZS 1016, average x + y = 3); thereby
the devices with which tney are used will not support combustion.
Aroclors to 62$ chlorination are liquids because of their mixed molecular
composition, the isolated individual isomers being crystalline with
relatively high melting points. This effect, to prevent crystallization
' (an effect which would cause loss of electric strength), extends to low
temperatures, where they go gradually into a glassy state. Therefore, they
<(8) are effective over a broad temperature range, from as low as -6Cr C
to
_
low).
150 C .(where their vapor pressures are still relatively
.t
.'
No ot.h er insulating fluid is known that equals the Aroclors, . with respect to all these eight properties. It is especially
os\N 182784
3
STLCOPCB4050888
/
difficult, or impossible, to f .nd another fluid thut is non-flammable, having even just adequate th.trt.{.1 and electrical characteristics for power capacitors and Iransfon crs. A replacement for Aroclor i*s almost ` bound to present a fir" hazard i-.s- can be s.'en from Table 2 (Underwriter Laboratory Flammability Rating) ana Tub!r 3 (Alternative Insulating fluids)
. Table 2
-
Underwriter Laboratory Flammability Rating
" Fluid . Ether Gasoline Ethyl Alcohol Kerosene (100 F.P.)
Paraffin Oil Aroclor 1242 ano L0l6
Flammability Rating
100 90-100
60- 70 30- Uo
10- 20
. i 2- 3
As for capacitors, th<: most practical substitute for PCB presently
known is mineral oil. Use of mineral oil impregnated kvaft paper
capacitors was pioneerel by Westinghouse from 1924-1932.
'
' in 1934 Introduction of PCBs in capacitors^resulted in drastic reduction in fire
and explosion hazards a id greatly increased safety to operating and '
maintenance personnel as well as the public. Size and cost were reduced
commensurately. Further advancement resulted from the introduction of
polypropylene film-paper-PCB capacitors in 1967.
.
. Reverting to an oil-pa;*r dielectric system would increase the average
capacitor volume (size) by approximately 600;!-, the weight by 50O and the
cost by approximately 4005'.. At the present levels of demand for capacitor
Vi -- ....
.
kvac, there would .be a shortage of electrical grade papers and a shortage
of capacitor factory facilities further tending to increase the cost to
the utility, and ultimately to the consumer.
/
DSW 182785 -4
STLCOPCB4050889
Table 3 Alternate Insulating Fluids
\
Sane Significant Properties of Certain Candidate Insulating
'Fluids to Replace Aroclor 1242
'-
,
Fluid .
Dielectric Constant, Cleveland Open Cuo ?]arrr.ability
c*,,* at 1C0C C
I Jash
- VC - Tire Point Density
Aroclcr 1?4?
.
Aroclor KCS 1016
Aroclor MC3 1043 (lower chlorinated'diphenyl)
Wemco C Oil (Mineral Oil
4.9 ; 4.8
2.1
" 19U . 191 160
145 `
333 . 319
244
150
1.3? 1.36 1.23
.9
Cost, f Vo
13 13
_^ A. / 1
3
I
Use of oil impregnated paper f<r capacitors has been largely abandoned throughout the world, in favor of one or the other of the PCD systems. The only significant r/nufacturer in the world is Japan. Even during the recent most unfavorable balance of. trade with Japan, this product was never considered for export to the U.S. because of its cost (200-
more) and because cf the flammable rating of the impregnant.
t
/
\
OSW 182787 STLCOPCB4050891
I
ADVERSE KFrdCTS C? rpLyCHLORIIIAT'-lD BIItiEKYIS
.%
.
Chlorinated biphenyls, PCBs, during the past two years have been included among post:bio polluters of the ecology, i-n association with DOT'S. This h if- raised the question about their continued use in the electrical industry, where they have been serving as insulating fluids for capacitors and transformers for almost forty years.
Chlorinated biphenyls were first identified in the environment along
with DDT's and the controls on the levels set by the IDA are ''Action
Levels", which are the s:cv2 as for DDT. They are not levels for which
FCBs have sh' own to lie harmful to mammals. See Table 4 f.or "Ac. tion Levels".
^
. Table 4
,
Medium
Water Butter fat Milk Fish Eggs
Generally Permitted "Action" Levels of FCBs (same as those issued for DOT1)
Parts per Million PCD Permitted
.5 5.0
.2* 5.0
.5
. *for 4$ butter fat.
Tests by Monsanto and others of chlorinated biphenyls, PCBs,
in tne environment h.j.ve rhovn a concentration of higher chlorinated
. compounds and a reduced cr no presence of compounds with three chlorines
or less.
.
Chlorinated biphenyls art considered about l/iO as toxic as DOT for /.
mammals. White rats fed \iy. to 100 ppn of PCBs in their food steadily over a period of 24 montv wore healthy (See Table 5 for accumulative level). Dogs fed up to 100 ppm of the PCBs over 24 months showed a slowed weight gain with the higher chlorinated compounds, but not with
'v
-7-
' DSW182788 STLCOPCB4050892
' ..
the Aroclor 12l2 (See Table f> fur accumulative level). There were no deaths. The higher chjorin'-tcd compounds accumulated in their fatty tissue toan cquilibr: ;n level.
are reported to
;
'
Chlorinated biphenyls .-..'feet the egg shell and hatchability of some
birds. Other breeds of birds have not shown any effects. Birds are
more susceptiblr to the lower chlorinated compounds, di and tri
chlorinated. Three ppm of KB in chicken feed affects the hatcha-
bility'of Leghorn chickens,-but not some other breeds of chicken.
One* incident of ingestion of KBs by humans has been reported frem Japan.
In `tnis case, a rice oil with 2000 ppm of KBs was consumed by 1000 -
people. Severe cases of chloracne, nausea, headaches, and weakness
were experienced. Sane babies of these people were born with brown
pigmented skin, but the pigmentation later disappeared. There were no .
deaths. 'It is suspectrl that the KB involved contained a chlorinated
dibenzofuran e, a toxic impurity found in some European chlorinated
diphenyls.
'
.
Artifically controlled studies of biodegradation using a semi-continuous
activated sludge test, SCAS, and also single bacteria culture tests have
shown that the lower chlorinated compounds are biodegraded, but the rate
of. biodegradation decreases as the percent chlorination increases, and
is very low
for pentachloro compounds and higher (See Table 7
for results of these tests), Monsanto scientists state that they do not
know the correlation of thes-;- artificial biodegradation tests to
.. environmental conditions.
'
Chlorinated biphenyls appear to diffuse very slowly through soil.
. Monsanto feels that their new grade of chlorinated biphenyl, MC3 1016,
is biodegradable, since it contains only 0.16^- of penta' and higher
chlorinated biphenyls. They recommend its use over 12h2, which contains
6.7$ penta-chlorobiphenyl, for capacitors or wherever the waste material is
not strictly controlled.
.
.
..
-8"
DSW182789
STLCOPCB4050893
.TAttbU 5
"Storage" of.' Chlo; iimtcd Biphenyls in Albino Rots;, _Aftyr 24 .':3 nhs* Exposure in Eccd
Note: *.
ConeenCvation in lipid bocar.e appvov.inntely constant
at about. 6* 12 r.ionths; except for Arocltir 1234 and 1260
exposures at higher concentrations, noted by *, where
it tended to increase continuously with tiiae, and the
liver* to brain weight ratio increased.
.
Aroclor - in Teed
1242 1254
*
, 1260
Concentration in Lipid, ppm,
at * 1
10 100
.
10 70
200
EXU3 feed
50
' r ?
200 ?
a 1,500* -*
5,000-10,000
TABL'E 6
"Storage" of Chlorinated Biphenyls in Dogs, _After Ihuiths1 Exposure in Teed
Aroclor - in Feed 1242
Concent rati on in Lipid, ppm
at__1,
.3
JSL
.
5
--10--0-- in?*
feed
6
1254 '
1260 ' -
.
.0 18 *
33 . . 86
* 109
* / 579
.
*
%
*
reduced weight gain, increase in liver to `brain weight ratio
*
* ' i
.
' ' .-9-
DSW 182790
STLCOPCB4050894
I
Tabic Y
.* HiVy of Different Chi orinnl.c-d Biphcnvls
- Semi. Continuous Ac I i voted Sludge Test,. 2 x 10 8 cdlls;/cc -
(observations aftn preconditioning sludge to Aroclor tested)
.
j"
Aroclor
7 Chlorine
7, feisnppcarance in 48 hrs
.-
Mono-chlorob'iphcnyl
18.5
100 . ^
1221 MCS 1043 MCS 1018 1242
-
21 30 41
4* '
'
' *
i
88
*55 *
35 .
25
- .
Distillate of MCS 1036
51
. ` 15
'
` 1254
\ 15
DDT Linear Alkyl Sulfonate-Standard
<10
100
Noted concentrating of 4-, 5-, and 6- chlorinated isomers
/
Single Cultures, C-'J and C-3, with specific isoners (Europe)
Both cultures have tpproxi.inatcly the same effect..
'
ChlorinaU ri i phenyl di and t ri tetra
Time for 50% Pi snppearance.
*v26 days
.
. *v30 days
-10- DSW 182791 STLCOPCB4050895
Where are we today?
In the past twelve yet rs 6ll Trillion pounds of Arcclors have been used
by U.S. industry in their productc (See Table 8 for details). 231
million pounds have d ren used in jjroductr; that may be classified as
open systems, i.e. paJnt formulations, pj stJcizcrs, hydraulic fluids,
and seni-closed systems such as heat exchangers. During this same
period of time the electrical industry used 330 million pounds of the
-Aroclors in closed systems which are essentially capacitors and trans
former's. In the electrical industry the Aroclors arc confined to
equipment where the containers are sealed and the system is considered
to have a "closed" cycle.
,
An estimate of the total Aroclor used in the U.S. in closed system electrical usage since 193^ is about 690 million pounds. The closed systems can be broken Into two categories estimated at^4H0 million ** pounds_for capacitors md 250 million pounds for transformers. Host of this 69O million pounds is still in use in closed systems today. Some of this amount has escaped into the environment, and this will be analyzed a little later, but the major impact on the environment has been through open system usage, or ser?i-closed system usage (heat exchangers).
The ratio of usage in opu. systems to usage in closed systems over the
past twelve years was 61/. Using a conservative ratio of 30/ for the
earlier years, 193^-19^0, v< aid add approximately 93 million pounds in
open systems prior to I960 c a total to date in open systems of 3?^
million pounds maximum coma ; vid to 69O million pounds in closed
electrical systems.
.
.
Calculations show, that the amount of Aroclor that has possibly escaped from the closed electrical t y items is small. Based upon worst case failure modes and failure i n vs a maximum of .025$ or 110,000 lbs. from
11 DSW182792
STLCOPCB4050896
capacitor failures and a max in;an" of .040p^ or 101,250 lbs,, from trans
former failures could have be on introduced into the environment since
193*! This amount jui compared to total introduced by open systems is
very small 211,'-:5C__ or 0.06j. 32-;,0o0/C:0
"
* !' Looking at the most recent electrical usage figures (Reference Table 7)
and projecting ahead, the maximum amount of leakage that could be ex
pected, from continuing use of Aroclors in closed electrical systems
would be 0.03$ or
lbs. per year assuming no increase in pre
cautions, han.dling, procedures, etc. This amount when compared to
what is already in tic environment is very small
9,000 or .003^.,
*.
324,211,256
1
/
-12-
.;
V
os*^193 STLCOPCB4050897
V.-ible 8
Monsanto Product ion cud Sales of Aroclors for 1960--1971,
with IveaV:dovn Showi n;; Electrical, tirade
'*
(from c:.: N e.cs, Dc-fr;.!-r 6, 1971)
.
.
U.S. Production
Figures in short tons
- ` Ponc: fie Salles
.> .
Insulating
Liquids^ . `Others^
Exports
1960
20,786
12,444
1961
* 20,333
11,108
1962 1963 1964 .
20,986 22,367 25,417
* 11,683 11,448
.
' 13,769
1965
30,240
16,203
1966
32,925
18,897
1967
37,655
20,387
1968 1969
41,427
. 20,568
. /
38,194
18,564
1970
42,527
20,268
--1971c
------20,236 .
14,417 "
5,163
-. 1827*
7,661
7,33.9 *
7,618
8,666 9,695
.
2076 1809 1824 2048 2117
10,642
.3426
10,846
4062
13,990
5312
15,034
5312
16,263
6826
4,401
4938
a. For closed electrical systems - transformers and capacitors.
^ Includes heat-transfer systems, hydraulics/lubricants, and plasticizers.
c Estimated.
.....
j.
Source: Monsanto
'
.*
............... " --------- =13-............................... ' "
"~
'
DSW182794
STLCOPCB4050898
Existing Controls
Monsanto has already taken the following actions:
'
(a) Stepped sales to "open" users (paint formulator3, plasticisers, . hydraulic fluid mnTifuctursrs, etc.)
(b> Stopped sales for use in heat exchangers - particularly food
processors.
.
(c) Alerted all recipient manufacturers to exercise care in use of * fluids. ,
(d) Provided for waste fluids incineration.
(e) Modified capacitor fluids, eliminating the more highly chlorinated and environmentally more objectionable fractions.
.
^ `
All of these actions lave greatly improved the control of PCBs to prevent future environmental damage by eliminating future open system -usage which has provided over 99$ of PCBs introduced into the environment.
The electrical industry is aware and hes been alerted to the environmentally
hazardous nature of PCBs. The industry in general exercises high
standards of control as it incorporates the fluid into its capacitors
and transformers. Safe Practice Procedures for use and handling of PCBs
have been in use for many years. The recent (1SK56) knowledge of PCBs
being possible environmental hazards has resulted in warnings and
special instructions to customers and handling personnel about the
hazardous nature of PCBs. In addition, when sealed systems containing
PC3 must be opened and drained for repairs, the instructions ca]J. for .
*/
,
collection of all waste liquid PCB and contaminated materials for special ,
destructive incineration.
=.
14-
i
DSW 182795 i
STLCOPCB4050899
I
Recomendations
.
Although the electrical industry hos recognized and is implementing . control systems to dccr-visc the amount of PCBs entering the environ ment from its handling ar.J use, it supports federal legislation designed to protect the environment. The industry is working with ANSI and other standard organinations to. prepare high standards for ,,thc use, handling, and disposal of PCBs, however, it is vitally concerned that PCBs not he pre-enptorily banned from manufacture and use in closed electrical systems, since it is felt that the public can be adequately protected without such action , and there are other hazards, particularly fire, associated with known substitute material.
ANSI C-107 committee c<n the use and disposal of PCBs in electrical -
equipment is working on a plan to control PCBs. The development of
this plan in conjunction with Federal legislation kind regulation of
the manufacture, use, .arid disposal of ICBs should bring the FCB situation
to a point where regulated electrical industry usage can represent no
more threat to the environment than that for numerous other necessary
and beneficial materials likewise requiring precautions in use, dis-
. tribution, and disposal.
'* . .
E.R. Boquist 1/3/72