Document 50w553y40G5pybdY9NRJV1jRV
462
CHAPTER 20
'1953 Guide
size in the case of rectangular ducts. Warm air ducts passing through' cold' spaces or located in exposed walls, should have 1 to 2 in. of insulation?1
Special attention should be given to the problem of noisd'eliinination. The metal duct connection to and from the furnace casing arid'fan housing' should' be broken by strips of canvas. Motors and mountings must1 be;carefully selected for quiet operation. Electrical conduit and water piping must not be fastened to, nor make contact with the fan housing. Instal lation of a fan directly under a retum.air grille is usually avoided.
STANDARD COMBINATIONS OF PARTS ' ^
- The combinations of parts selected as standard by the National Warm Air Healing and Air Conditioning Association are shown in'Tables l and' 2. A method for selecting these combinations is indicated in the following section Simplified Method of Design.
Fig. 3. Recommended Type of Floor or Low Sidewall Installation on Out side Wall0
e Registers set to direct air upward along the wall at as wide an angle as possible.
SIMPLIFIED METHOD OF DESIGN
A simplified method for selecting the combinations of branches, boots, stacks, and registers, is given3 in Manual 7 of the National Warm Air Heating and Air Conditioning Association. In this method, the sizes of the branch ducts are obtained from two tables giving their Btu capacities. The proper combination of parts for each branch can be determined if the follow ing information is available.
a. Location of room, that is, whether on first or second story. b. Actual horizontal length of duct from bonnet to boot, in feet. c. Btu loss from room to be heated. d. Equivalent lengths in feet of all fittings and of the register. Fig. 4 shows the values of'equivalent lengths of fittings commonly used for domestic systems.
Forced Warm Air Systems
463
This simplified method is applicable to structures having heat losses not in excess of approximately 120,000 Btu per hour. The capacities shown in Tables 3 and 4 are based upon the most reliable data pertaining to fric tion, losses, and temperature drops in ducts. They are also based upon a
100 deg temperature rise of the air, and a static pressure available for overcoming friction losses in the external duct system alone of 0.20 in. water gage. The use of this method assumes that the fan in the fanfurnace assembly will be capable not only of overcoming the resistance of
the external duct system alone, but also the resistances imposed by the blower inlet, the filter, and the furnace casing. The combination numbers shown in the right hand column of Tables 3 and 4 correspond to those given
Table 1. Warm Air Duct System Combinations of Parts Selected as Standard
COMBINA
TION NO.
Branch Pipe, Size n.
Register Size, In. (See Figs. 1, 2, 3 and 4)
Stack. Size, In.
. REC Round TANGULAR
Base-board High or Low
Sidewall
Floor Registers* .
PERIMETER
REPLACE MENT
Required
in Width op Trunk Duct, In.
1.
2 34
5
6 78
- 41
10 x3H
5 3x8
10 x 6
4 x 12
8 x 10*
i
42
10 x 3a - 6 4x8
10 x 6
43
12 x3M
7 5x8
12 x 6
4 x 12 4 x 14
8 x 10* 9 x 12*
2 3
44
14 x 3K
8 6x8
14 x 6
6 x 14
9 x 12*
4
or longer
45
10 x 3M
9 ' 8x8 (2) 10 x 6 (2) 4 x 12 10 x 12*
5
(2-Stacks)
or
(1) 24 x 6
46
12 x 3M . 10 10 x 8 . (2) 12 x 6 ' (2) 4 x 14 12 x 14*
7
(2-Stacks)
or
(1) 30 x 6
* Use these items only when the installation necessitates the use of existing floor openings. The sizes listed for floor registers correspond to the standard sizes for gravity warm air furnace systems, except for the size of the floor box collars. The use of standard blind boxes is suggested. A 12 x 51 in. stack may be used on Combination 45, and a 14 x 51 in. stack on Combination 46 with floor registers.
in Tables 1 and 2. Tables 3 and 4 are also applicable for the selection of the return air branches. A depth of 8 in. has been adopted as the standard for the trunk ducts. The width of a trunk duct serving two branches is determined by adding to the width of the remote branch the value shown in column 8 of Table 1, or column 8 of Table 2.
DESIGN PROCEDURE FOR LARGE SYSTEMS4
For buildings having a heat loss in excess of 120,000 Btu per hour, the design procedure6 given in Manual 9 of the NWAH & ACA, may be used. Work sheets 9a, 9b, and 9c are available to simplify calculations.4 The procedure consists of:
1: Calculation of design heat losses from individual spaces in the structure. The calculation of these losses is explained in Chapter 12.