Wing Featherweight Unit Heaters and Process Heating Units; Utility Unit Heaters; Wing Scruplex Safety Ventilating Fans, Fog Eliminators and Exhausters; Wing Forced Draft Blowers, Turbine or Motor-Driven; Steam Turbines; Man-Coolers.
THE original and exclusive features of Wing Feather
Standard Discharge. Outlets for. Type
HC
weight Unit Heater design--
their light weight, the vertical
downward discharge of the heat
ed air, and multiple discharge
outlets which step up the velocity
of the air leaving the heater---are
directly responsible for definite
economies in the actual cost of
industrial plant heating and in
the cost of the equipment itself.
TYPE LC UNIT Cross-Section showing location of motor and fan. Used in buildings having low roofs .
or ceilings
TYPE HO UNIT Complete coverage accomplished with any
New Wing Featherfin Heating Element--(Tested to 1000 lbs. Pressure). Extremely light in weight. By simple variations of the heating surface any desired final air temperature may be ob tained with any given steam pressure. Standardized for steam pressures of 5, 40, 70, 100 and 130 lbs. all producing the same low final air temperatures.
Fin and tube extended surface type. Hairpin or return bend design. Headers of steel, tubu lar design. Tubes secured to headers by steam-tight compres sion union. Easily removed and replaced in case of damage.
Condensed Table of Engineering Data Type H. C.
Size
13-HC 17-HC 19-HC 22-HC 25-HC 30-HC 36-HC
C.fjn. at
inlet
800 1400 2000 2750 4300 6600 9800
R.p.m.
1750 1150 1150 1150 1150 850 850
13-LC 17-LC
19-LC 21AJC
2S-LC 30-LC
36-LC
750 1310 I860 2530 . 4000 6150 9130
1750
1150 H50 1150
1150
650 850
Fan Hp.
0.06 0.10 0.21 0.25 0.40 1.03 2.01
0.06 0.10 0.19 0.23 0.36 1.01 1.90
Rated' Air Temp. F. Motor
Hp. In. Out.
1/15 1/10 '/<
2
60 60 60
60 60
60 60
Type L C
123
125 123
128 126 123
120
1/15 1/10
'/. Va Vi ' i 2
60 60 60 60 ' 60 60
60
122
124
122 127
125
122 119
B.tu.
Hour
55.500 100.500 139.500 206.000 315.000 461.000 656.000
Equiv. Approx.
Direct Net Wt. Rad. Lb.t
231 418
581 859
1312
1920
2730
95 130 160
200
285 430 560'
47.500 85.500 118,500 175,000
268.000 392.000 557.500
198
356 494 729
1117
1633 2320
95 130
160
200 285
430
560
Inlet and Outlet temperatures, also B.t.u. same for 5^ 40, 70, 100 and 130 lb. steam pressure. fThis weight does not include weight of discharge outlet. . Space does not`permit complete table but this data will gladly be furnished on application.
640
L. J. Wing Mfg. Co.
Fans and Ventilating Equipment
^'V' '-VA*' y'VV' ''/VV'
Method of Heater Installation-First diagram shows a Type HC Unit installed above a traveling crane, the heater arranged so that the lower left portion of the building is also heated. Second diagram shows a plan view illustrating the general distribution and diffusion of heated air from Wing Heaters. The third pictures a typical multistory building heated with type LC Wing Units. The best and most economical installation of Wing Featherweight Unit Heaters is when they are placed close to roof or ceiling.
Wing Utility Unit Heater
Wing Featherfin Process. Heating Units
I I 1 II
A general purpose heater. Delivers heated air in one general direction. With vane diffusers and safety guard for fan. Capacity data same as Type HC on preceeding page.
For manufacturing processes such as drying, ageing, etc., requiring the recirculation of the heated air. Motor or turbine located, outside air current.
Wing-Scruplex Fog Eliminators supply tempered fresh air to completely de-fog any building or room where steam, ?fog or fumes are liberated in manufacturing processes.
Wing-Scruplex Safety Ventilating Fans
An integral guard of strong steel rings welded to the frame features every model of the WingScruplex Safety Ventilating Fan. This guard removes the ever-present danger which exists . whenever fans are in an exposed location, and
does not reduce fan efficiency. The high volumetric efficiency of Wing-
Scruplex SaftHfy Fans is due to their true screw propeller design which . moves the air forward in straight lines without eddy. Motor is fully enclosed, easily accessible and generously proportioned. Can also be supplied
with pulley or turbine drive. Wing-Scruplex Safety Fans are built in the following sizes: 10, 13, 17, 22, 25, 30,
36, 42, 48, 54 and 60 in.--capacities from 950 c.f.m. to 33,000 c.f.m. Up to 25 in. dia. propellers are made of cast-aluminum--larger sizes of pressed steel.
641'