American Society of Heating and Ventilating Engineers Guide, 1924-25 In order to illustrate just how important this iteni of air temperature at the registers really is, the results of three tests on the piped furnace plant Fig. 47 are presented in Fig. 49 and analyzed; Absolutely no changes were made in the furnace or plant during these tests. In the right hand half of the figure each inclined line represents one test; the lowest line American Society of Heating and Ventilating Engineers Guide, 1924-25 For example, during the first or low temperature test, each square inch of leader pipe to the first floor registers supplied 50 B.t.u. per hr. for useful heating effects in the rooms, each square inch of leader, pipe, to second floor registers supplied 89 B.t.u. per hr. for useful heating effect in the rooms, and each square inch of leader pipe to third floor registers supplied 122 B.t.u. pier hr. for useful heating effect in the rooms. At this time the draft was 0.05 in. of water and the combustion rate was 3.8 lb. of coal per sq. ft. of grate. By merely increasing the draft to 0.14 in. of water, the combustion rate in the Second test increased to 5.6 lb. of coal per sq. ft. of grate and the average air temperatures at the registers became 175.8 deg. fahr. This raised the useful heat carrying capacity of each square inch of leader pipe for the first floor from 50 to 103 B.t.u. per hr., for the second floor from 89 to 153 B.t.u. per hr., and for the third floor from 122 to 204 B.t.u. per hr. A further increase of the draft to 0.16 in. of water gave a still higher combustion rate of 6.5 lb. per. sq. ft. of grate and correspondingly greater heat carrying capacities for each square inch of leader as shown in the upper curve of the right-hand half of Fig. 49. The left-hand half of Fig. 49 shows the air velocities in the leaders to each floor for each test. A glance at the curves (each curve represents one test) will show that the velocity and hence the quantity of air de livered was materially increased each time the register temperature was increased, hence an increase in register temperature not only adds more heat to each pound of air supplied at the registers, but also increases the number of pounds of the hotter air which is supplied. In all cases the leader area was the same. It is also possible to determine exactly just what effect the changes in air temperature at the registers have had on the heating capacity of this furnace and plant. The first floor leader area is 4 X 113 = 452 sq. in., the second floor leader area is 2 X 50 + 2 X 64 = 228 sq. in., and the third floor leader area is 2 X 64 = 128 sq. in., or a total of 808 sq. in. The free area of the furnace is 838.4 sq. in. Hence this furnace developed the following useful heating capacities (that is, heat supplied at registers for heating rooms to 70 deg. fahr.) in each of the three tests: Fig. 48. An Improved Recirculating Duct Which Increased Leader Test Number 1. Register temperature = 141.2 deg. fahr. (Draft = 0.05 in. and combustion rate = 3.8 lb. per sq. ft. of grates.) 452 X 50. - 22,600 228 X 89 = 20,300 128 X 122 = 15,600 58,500 B.t.u. per hr. shows the results from a test with the air temperatures at the registers Test Number 2. for the three floors averaging 141.2 deg. fahr., the middle line is taken from a test with an average register temperature of 175.8 deg. fahr,, and the Register temperature -- 175.8 deg. fahr. (Draft = 0.14 in. and combustion rate = 5.6 lb. per sq. ft. of grate.) upper line represents the results of a test with an average register tem perature of 197.5 deg. fahr. The horizontal axis indicates the height of the register above the grate in feet, and the vertical axis gives the heating effect produced in the room per square inch of leader pipe area. 452 X 103 = 46,600 228 X 153 = 34,900 128 X 204 = 26,100 107,600 B.t.u. per hr. 122 II 123