CHAPTER 20
1955 Guide * V -
cold air from infiltration thus'effectively preventing drafts. This has been'
called perimeter heating. In any case, the warm air registers should be
located so that the air stream never discharges directly against people at
rest. Tests2 in Warm Air Research Residence No. 1 at the University of
Illinois, have indicated that continuous blower operation gave better re
sults than intermittent operation. \ - *:
i
Register and Grille Openings
Tests also conducted in Warm Air Research Residence No. 1 have in dicated that comparable results are obtainable with either high side wall or baseboard registers, if proper registers and air velocities are selected. Baseboard registers should'be of a deflecting-diffuser type which'throw the"
- Forced-Warm Air Systems
469
of Manual 7, these manuals being publications of the National Warm Air Heating arid, Air-Conditioning Association.
Registers should be well proportioned and decorated to harmonize with the trim.' Air supply registers should: be equipped with dampers, and all registers should be sealed against leakage around edges. The register types shown in Figs. 1, 2 and.3 have been recommended as standard by" the National Warm Air Heating and Air Conditioning Association.
Return air grilles may be located in hallways, near entrance doors, under windows, in exposed corners; Or inside walls, depending on location of supply registers. Baseboard returns are preferable to floor grilles where warm air registers are located on inside walls. Where perimeter heating is used, returns placed high'on inside walls are preferred.
Fig. 1. Recommended Type of Baseboabd and Low Sidewall Installation on Warm Wall*
* Vertical bare with adjustable deflection, or fixed vertical bare with deflections to right and left not exceeding about 22 deg. For low sidewaU location, the deflection for horizontal, multiple vane registers should not exceed 22 deg. For baseboard locations, the deflection for horizontal, multiple vane registeiz should not exceed about 10 deg.
air downward toward the floor and diffuse it at the same time. For base board registers, air velocities over 500 fpm, should be avoided as they may cause discomfort.
High side wall registers should be of such type that the air: is delivered horizontally or in a slightly-downward direction, and should be so located as to avoid impingement of air on ceiling or wall;; Directional flow din fusing type registers should be used to insure best , results. Register air velocities should be such that the air velocity will be about 50 fpm three quarters of the distance from the register to the opposite wall; -.
Velocities through registers may be reduced by the use of registers larger than the connecting ducts. Diffusers should be used to spread the air uniformly over the register face. Basic rules for the location and selection of registers, together with explanations of factors affecting .^operation, are given2 in Section 6 of Manual 4, Sections 3 and'4 of Manual 10; of-Section
Fig. 2. Recommended Type of High Sidewall Installation on Warm Wall*
* Horizontal vanes, in back or front, to give downward deflections not to exceed from 15 to 22 deg.
Dampers
Suitable dampers for air direction or volume control are essential to any duct system. Special; care must be used in the design of any system, to minimize resistance. Sharp elbows, angles, and offsets should be avoided. Three types of dampers are commonly used. Volume dampers are used to completely cut off or reduce the flow through ducts. Splitter dampers are used where a branch is taken off from a main trunk. Squeeze dampers are used for adjusting the volume of air .flow and resistance through a given duct. It is essential that a damper with positive locking device be. pro vided for each main or duct branch. Labels placed on ducts should indi cate the room being served. Damper positions should be marked for summeT and winter operation, and to avoid tampering.
Ducts
The ducts may be either round or rectangular in. cross section. The centerline radii of elbows should preferably.be not less than one and oneualf times the pipe diameter for round pipes. The throat radius of a turn